FUNCTIONING LOGIC 

 

INSTALLATION MODE - This functioning mode is only used by the installer and makes it possible to select 
the  rotation  direction.  Once  selected,  the  only  active  input  is  the  start  input  and  therefore  when  the  open 
pushbutton is pressed the open relay is energised and when this is released this is de-energised. 

SEMIAUTOMATIC  MODE  -  When  this  functioning  mode  is  selected,  one  start  pulse  commands  opening, 
until the limit switch is tripped. If a start pulse is sent during opening, the operator will stop where it is. In this 
case, with the gate fully open or halted at an intermediate position, the next start pulse will command closing, 
after a 3 sec. warning given by the flashing beacon and the pilot light. The closing phase will continue until the 
limit  switch  is  tripped.  Furthermore,  during  closing,  if  a  start  pulse  is  given  or  if  one  of  the  photocells 
intervenes after closing has started, this commands reopening of the operator. 

STEP BY STEP MODE - Only differs from the semiautomatic logic due to the fact that a pulse during closing 
does not command reopening but stop. 

OPEN-CLOSE MODE - Uses the start input as the open command and the close input. Useful for a porter’s 
lodge. One start pulse commands opening until the limit switch is reached. One close pulse during opening 
commands a stop, a second pause and then closing. 

AUTOMATIC  MODE  -  When  this  type  of  functioning  is  selected,  a  pulse  sent  commands  opening  until  the 
limit  switch is reached, the gate remains open for the selected pause time and then is automatically closed 
after a warning of 3 sec. provided by the flashing beacon and the pilot light. 

  If a pulse is sent during opening, the control system ignores it and the gate continues to open. 

  If  a  pulse  is  sent  when  the  gate  is  open,  this  pulse  zeroes  the  pause  time  (the  count  starts  again  from 

zero).  If  the  photocells  are  obscured  before  the  pause  time  starts,  the  count  will  only  start  when  the 
photocells are cleared. 

  Finally, if a pulse is sent during closing, the movement direction is reversed (i.e. the gate opens). 

SUPER  AUTOMATIC  MODE  -  This  logic  is  identical  to  the  automatic  logic,  the  only  difference  being  that 
when a pulse is sent during the opening phase, the movement is reversed without terminating the cycle, after 
a warning of 3 sec. given by the flashing beacon and pilot light. 

DIAGNOSTIC  MODE:  Check  the  correct  functioning  of  the  microprocessor,  stimulating  the  various  outputs 
one at a time for approximately one second. At the end of this phase, the installer must command the various 
inputs and see that these commands are received (flashing of test LED). 

DEAD MAN MODE - Uses the inputs: the start input as the open command and the close input as the close 
command. These inputs must be connected to normally open pushbuttons. To move the gate an person must 
hold down one of the two commands. When the pushbutton is released, the gate stops. The safety devices 
remain active. 

OPENING/CLOSING  PREFLASHING  –  The  function  of  the  preflashing  is  to  provide  a  warning  of  the 
imminent movement of the gate. The preflashing can be programmed by setting the dip-switches S3 and S4 
(see programming table).  

The output which commands the flashing light also establishes the flashing frequency: active for 0.5 sec and 
not active for 0.5 seconds, or steady. 

 

PARTIAL OPENING - This is an N.O. input (pedestrian start), which commands the timed functioning of the 
operator, so that a portion of the sliding gate is opened to allow pedestrian passage. This size of this portion 
is adjusted on a trimmer RV3 (from 3 to 30 sec.). All the logic functions and safety devices selected are also 
enabled during pedestrian opening. 

  If  a  pulse  for  total  opening  is  given  when  the  pedestrian  opening  start  input  is  active,  the  operator  will 

continue to open completely until the limit switch is reached. 

  If this input is constantly active, it is necessary to command a complete closing cycle and then the block; 

the flashing light will signal the fault with fast flashing for 5 sec. intervals and pauses of 10 sec. 

 

OPENING/CLOSING SAFETY INPUT This is an N.C. input which must function during opening and closing. 
It functions as follows: if the safety device intervenes during opening or closing, this causes a reversal of the 
gate  movement  for  10  sec.  and  then  blocks  the  movement  until  a  start  pulse  is  received  which  commands 
closing. 

Содержание A86M

Страница 1: ...A APERTURA DL16 LED FOTOCELLULA M1 MORSETTIERA SEGNALI M2 MORSETTIERA POTENZA J3 MORSETTIERA RICEVENTE RADIO T1 TRASFORMATORE RV1 TRIMMER VELOCITA DI RALLENTAMENTO RV3 TRIMMER APERTURA PARZIALE RV2 TR...

Страница 2: ...V 24 V 5 11 3 9 7 13 15 2 12 4 10 8 14 16 21 18 17 M 25 23 20 22 19 24 6 Luce spia max 5 W Lampada ET2 max 5 W Start Stop Finecorsa apre Finecorsa chiude Sicurezza apre chiude Fotocellula Start pedon...

Страница 3: ...LOGICA AUTOMATICA SUPER Questa logica identica all automatica con la sola differenza che inviando un impulso in fase di apertura si inverte il moto senza terminare il ciclo dopo un preavviso di 3 sec...

Страница 4: ...EGGIO S8 FUNZIONE FOTOCELLULA ON FISSO ON BLOCCO STAND BY OFF INTERMITTENTE SEC OFF NO CONTROLLO JP2 SELEZIONE SENSORE RPM ON NO SENSORE RPM OFF SI SENSORE RPM Per maggiore chiarezza agendo nella zona...

Страница 5: ...ING SAFETY DEVICE LED DL16 PHOTOCELL LED M1 SIGNAL TERMINAL BOARD M2 POWER TERMINAL BOARD J3 RADIO RECEIVER TERMINAL BOARD T1 TRANSFORMER RV1 BRAKING TIME RV3 PARTIAL OPENING TRIMMER RV2 PAUSE TRIMMER...

Страница 6: ...4 V 5 11 3 9 7 13 15 2 12 4 10 8 14 16 21 18 17 M 25 23 20 22 19 24 6 Pilot light max 5 W ET2 light max 5 W Start Stop Open limit switch Close limit switch Open close safety device Photocell Pedestria...

Страница 7: ...AUTOMATIC MODE This logic is identical to the automatic logic the only difference being that when a pulse is sent during the opening phase the movement is reversed without terminating the cycle after...

Страница 8: ...ITTENT SEC OFF NO CONTROL Partial opening time Pause JP2 RPM SENSOR SELECTION ON RPM SENSOR NO OFF RPM SENSOR YES Braking Details zone A allows you to set the braking efficiency or time which is alway...

Страница 9: ...DL16 LED FOTOC LULA M1 REGLETA DE CONEXIONES SE ALES M2 REGLETA DE CONEXIONES POTENCIA J3 REGLETA DE CONEXIONES RECEPTOR RADIO T1 TRANSFORMADOR RV1 VELOCIDAD DE DECELERACI N RV3 TRIMMER APERTURA PARC...

Страница 10: ...5 11 3 9 7 13 15 2 12 4 10 8 14 16 21 18 17 M 25 23 20 22 19 24 6 Luz piloto m x 5 W Luz ET2 m x 5 W Start Stop Final carrera abre Final carrera cierra Disp Seguridad abre cierra Fotoc lula Start pea...

Страница 11: ...nica diferencia de que enviando un impulso en fase de apertura se invierte el movimiento sin terminar el ciclo tras un previo aviso de 3 seg ofrecido por la luz intermitente y la luz piloto MODO DIAG...

Страница 12: ...ON NO SENSOR RPM OFF SI SENSOR RPM Para una mayor claridad en la zona A se puede regular la eficacia o velocidad durante la deceleraci n que permanece siempre programada en 3 segundos mientras que al...

Страница 13: ...RE DL16 LED CELLULE PHOTOELECTRIQUE M1 BORNIER SIGNAUX M2 BORNIER PUISSANCE J3 BORNIER RECEPTEUR RADIO T1 TRANSFORMATEUR RV1 VITESSE DE RALENTISSEMENT RV3 POTENTIOMETRE OUVERTURE PARTIELLE RV2 POTENTI...

Страница 14: ...15 2 12 4 10 8 14 16 21 18 17 M 25 23 20 22 19 24 6 T moin lumineux max 5 W Lampe ET2 max 5 W March ee Arr t Fin de course Fin de course meture S curit ouverture fermeture Cellule photo lectrique Marc...

Страница 15: ...nvertit la barri re s ouvre FONCTIONNEMENT AUTOMATIQUE SUPER Cette logique est identique l automatique avec comme seule diff rence qu en envoyant une impulsion en phase d ouverture le mouvement s inve...

Страница 16: ...ECTEUR TR MIN ON PAS DE DETECTEUR TR MIN OFF PAS DE DETECTEUR TR MIN Plus pr cis ment si on agit dans la zone A on intervient sur la vitesse au cours du ralentissement qui dure toujours 3 secondes si...

Страница 17: ...ITSEINRICHTUNG FFNEN DL16 LED LICHTSCHRANKE M1 SIGNALKLEMMLEISTE M2 NETZSTROMKLEMMLEISTE J3 FUNKEMPF NGERSTECKER T1 TRANSFORMATOR RV1 TRIMMER BREMSGESCHWINDIGKEIT RV3 TRIMMER TEIL FFNUNG RV2 TRIMMER P...

Страница 18: ...5 2 12 4 10 8 14 16 21 18 17 M 25 23 20 22 19 24 6 Kontrolleuchte max 5 W Lampe ET2 max 5 W Start Stop Endschalter ffnen Endschalter Schlie en Sicherheitseinr ffn Schlie en Lichtschranke Start Fu g ng...

Страница 19: ...b wobei jedoch bei bertragung eines Impulses beim ffnen nach einer Vorwarnung von 3 Sekunden des Blinklichts und der Kontrolleuchte die Laufrichtung umgekehrt wird DIAGNOSE Diese Betriebsart dient der...

Страница 20: ...PM OFF SENSOR UPM Der Deutlichkeit halber kann folgendes bemerkt werden Durch den Eingriff im Bereich A wird die Wirkung oder Geschwindigkeit w hrend der Bremsung ver ndert die stets auf 3 Sekunden ei...

Отзывы: