SETUP & TESTINg
System setting
Description
Factory default setting (bold)
and setting range
28. Blast Offset
Amount of heating when Heat Blast is initiated.
3°F (1.5°C)
3°F to 5°F (1.5°C to 2.5°C)
37 . Stage Rate
Accumulation of equipment run time in
equipment staging determination.
1 = more rapid staging of equipment (comfort).
5 = slower staging of equipment (economy).
2
1 to 5 or “OFF” to ignore accumulated
run time .
38. Progressive Recovery
Enable or disable progressive recovery.
0: Disable
1: Enable
39. Low Balance Point
Outdoor temperature low balance point .
Note:
This option is only available if the outdoor
sensor is enabled .
20°F or -8°C
0°F to 60°F (-18°C to 12°C) or OFF to
ignore LBP
40. High Balance Point
Outdoor temperature high balance point .
Note:
This option is only available if the outdoor
sensor is enabled .
65°F or 14.5°C
0°F to 80°F (-18°C to 22°C) or OFF to
ignore HBP
41 . Program Format
Enables the 7 day program.
0: 7-Day
1: Non-Prog
54. Change Air Filter Reminder
The period displaying the Change Air Filter
reminder .
OFF
1 to 12 months
SYSTEM SETUP INSTRUCTIONS
(CONTINUED)
SETUP & TESTINg
System setting
Description
Factory default setting (bold)
and setting range
55. Change Water Panel
Reminder
The time until the first Change Water Pnl
message is displayed .
OFF
1 to 12 months
56 . Humidifier Type
Selects the type of humidifier . If humidifier type
is set to Drain-less, then the first reminder is
based on the system setting 55, the second
reminder will activate 3 months later. If
humidifier type is set to Flow through, then the
first reminder is based on system setting 55, the
second reminder will activate 12 months later.
0: Flow through type humidifier
(1 reminder per season)
1: Drain-less type humidifier
(2 reminders per season)