background image

803877 Rev. 00  

Set Fan Mode 

Press Fan key to cycle through the fan settings as 
indicated by the small green circular LEDs. Select 
continuous High Speed fan, continuous Low Speed 
fan, or Intermittent Fan by selecting Auto. Auto cycles 
the fan on and off with the calls for heating or cooling. 
Auto also sets fan speed according to the amount of 
heating or cooling demanded. In Auto mode, the fan 
will start up periodically to establish airflow; air 
temperature will be sampled, and then the fan will shut 
off again if there is no demand. 
 

Disable Heating or Cooling, but Initiate Fan-Only 

Press On/Off key to turn off LED display. Press Fan 
key to cycle through the fan settings as indicated by the 
small circular LEDs. Select continuous High or Low 
speed. Do not select Auto, as it will turn the fan off.   
 
 

CONTROL AT THE WALL THERMOSTAT 

 

CONVERSION TO 24V REMOTE 
THERMOSTAT 

 
Except for the wall thermostat and thermostat cable, 
everything is included with the unit to field convert a 
keypad-operated unit to 24 Volt AC wall thermostat 
operation by qualified service personnel. Specific 
conversion instructions are detailed on the wiring 
diagram affixed to each particular unit to be converted. 
Conversion involves accessing the high voltage wiring 
compartment and changing a DIP switch setting on the 
electronic board. Once the DIP switch setting has been 
changed, operation will be in remote thermostat mode 
as soon as power is restored to the control.   
 

WARNING: 

The conversion procedure involves 

exposure to high voltage electrical circuits in the 
control box in order to make the necessary change to 
the DIP switch, and must be performed by qualified 
service personnel. Failure to do so could result in 
property damage, personal injury or death. Disconnect 
electric power to the unit before servicing. 

 
A factory-supplied 24 Volt wiring harness is provided 
with every unit to facilitate connection to the wall 
thermostat wiring. One end has a multi-pin connector 
which mates with a connector exiting the unit. The 
other end has preinstalled butt splice connectors, which 
play a dual role in insulating any unused connectors, 
and can also be used to make the wire connections for 
wires that are used.   

 
The final step is to apply the masking label provided, 
to cover up the keypad. The keypad and display will be 
disabled and no longer be available for control. The 
masking label markings instruct the user to go to the 
wall thermostat for controlling the unit. 

 

 
COMPATIBLE THERMOSTATS 

 
The features of the 24 VAC wall thermostat chosen 
will dictate the extent of the features available from the 
unit.  
Electric Heat / Cool units can accommodate the 
following thermostats in either manual or automatic 
changeover: 
 

 

Single Stage Heat/Cool, Single Speed Fan 

 

Single Stage Heat/Cool, Two Speed Fan 

 

Note: The thermostat selection must be verified to 
ensure its control logic will always energize a Fan 
output (G) on a call for heat – also known as an 
Electric Heat Type Thermostat.  

 
General: 
 
All the above can have single speed or two speed fan 
control. 
 
The wiring diagrams affixed to the units will guide the 
specific connection strategies for the particular 
thermostats used.  

 
THERMOSTAT LOCATION: 

 
Proper functioning of the thermostat depends on 
accurate room temperature sensing. Be conscious of 
locating the thermostat where temperatures near the 
thermostat are not representative of room temperature. 
For example, do not install the thermostat where it is 
subjected to direct sunlight, other sources of heat, or to 
cold drafts, including air discharged from a supply air 
register. A common error is forgetting to seal the hole 
in the wall where the thermostat cable passes through, 
directly behind the thermostat body. Air bleeding from 
behind the wall can drastically affect the temperature 
sensed by the thermostat.    
 

Содержание NAEC SERIES

Страница 1: ...PFLOW PACKAGED TERMINAL AIR CONDITIONER PTAC Cooling with Electric Heat INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Страница 2: ...hout an air filter will void the warranty WARNING To avoid bodily injury ensure power is disconnected before removing the air filter as there will be potential exposure to rotating parts Always replace the air filter filter bracket and screw to close off the bottom of the unit to prevent unintended contact with the blower wheels before operating the unit Clean Coils As part of regular servicing cl...

Страница 3: ... on the unit Rating Plate for the specific chassis Wire sizing must also take into account any distance from fuse box or breaker panel to receptacle to prevent excessive voltage drop in undersized wires IMPORTANT Low voltage to the unit will cause compressor starting problems and decrease the performance and reliability of the compressor BRANCH CIRCUIT PROTECTION The Current Rating of branch circu...

Страница 4: ... chassis must be level from side to side and sloped toward the outdoors from front to rear in the order of 1 8 inch per foot once the chassis side flanges are drawn up tight to the wall sleeve using the four flange screws If the sleeve was originally installed with a slope in the bottom of the sleeve in the order of per foot downward from the indoor to outdoor side the chassis will still operate p...

Страница 5: ...TART UP CHECKLIST Note Once the unit is installed it should be checked for proper function by qualified service personnel before turning it over to the User Circuit breakers wire size and electrical connections tight and correct Filter clean and properly in place Condenser air inlet and outlet free of obstructions and no short circuiting of condenser air Unit operated for 20 minutes to prove stabi...

Страница 6: ...ds and then decreases room temperature by 1 degree for every subsequent press of the key F C Key This key toggles the display between Fahrenheit and Celsius temperature modes and affects all displayed temperatures Heat Key The Heat Key toggles the unit in and out of heating mode for every press of the key provided the On Off Key is ON Cool Key The Cool Key toggles the unit in and out of cooling mo...

Страница 7: ...g A factory supplied 24 Volt wiring harness is provided with every unit to facilitate connection to the wall thermostat wiring One end has a multi pin connector which mates with a connector exiting the unit The other end has preinstalled butt splice connectors which play a dual role in insulating any unused connectors and can also be used to make the wire connections for wires that are used The fi...

Страница 8: ...is detected at the location of the wall thermostat and is usually a much more accurate representation of bulk room temperature The thermostat used may have advanced features beyond the basic functions described below Consult your thermostat Installation and Operating Instructions for further information In addition to controlling room temperature the room thermostat is also used to select whether ...

Страница 9: ...d whether the unit is configured for keypad or remote thermostat The protection remains active when the unit is OFF for either keypad or remote thermostat application as long as the unit is plugged in power is available and a heat source is configured in the unit and is working Compressor Short Cycle Protection If the electronic control shuts the compressor down for any reason a 3 minute time dela...

Страница 10: ...only but it can be changed to open with low speed fan operation only by having qualified service personnel re wire the unit as shown on the specific wiring diagram affixed to the unit WARNING The conversion procedure involves exposure to high voltage electrical circuits in the control box in order to make the necessary change to the damper action tied to motor speed and must be performed by qualif...

Отзывы: