803877 Rev. 00  

5.

 

Locate the 24 Volt wiring harness shipped with the 
unit. The harness is employed if a remote 24 Volt AC 
wall thermostat will be used instead of the unit-
mounted touchpad. If a 24 volt remote thermostat 
will be used, connect the multi-wire 24 volt wiring 
harness to the mating plug protruding beneath the 
control box, as applicable, following the detailed 
instructions on the particular wiring diagram affixed 
to the specific unit being installed. Insulated crimp-on 
connectors are provided at the end of every 
connection lead to facilitate connections/insulation.  

6.

 

Set the manual damper operator (if present) in the 
open or closed position depending on the desired 
operation. If the unit is equipped with a powered 
damper, it will open and close whenever the indoor 
fan is operated on high speed, as the factory default. 

7.

 

Plug the heat/cool chassis cord into the power 
receptacle located either in the sub-base or the wall, 
as applicable. 

8.

 

Install the filter and filter bracket/screw, and then 
lock the front panel on by inserting the tabs into the 
corresponding slot and sliding the front cover down 
until it seats. 

 

WARNING:

 Operating the unit without the filter in 

place can not only damage the unit, but also expose the 
user to a hazard from rotating parts, potentially 
resulting in bodily injury. The filter is intended to be 
removable with the use of a tool. The filter bracket and 
screw secure the filter. Always remember to re-install 
the filter, filter bracket, and screw after servicing the 
chassis, or replacing/cleaning the filters. 

 
9.

 

Wipe unit cabinet/wall sleeve to remove dirt, etc. 

10.

 

The unit is now ready for operation, when supplied 
with power from the distribution panel and wired to a 
remote thermostat (if applicable). 

 
START-UP CHECKLIST 

 
Note: Once the unit is installed, it should be checked 
for proper function by qualified service personnel 
before turning it over to the User. 
 

 

Circuit breakers, wire size, and electrical 
connections tight and correct 

 

Filter clean and properly in place 

 

Condenser air inlet and outlet free of 
obstructions and no short-circuiting of 
condenser air  

 

Unit operated for 20 minutes to prove stability 

 

Controls operation OK 

 

Unit installed in compliance with all codes and 
ordinances 

 

All panels in place and secured with required 
fasteners 

 

Mylar overlay applied to cover up touch pad 
for 24 Volt Remote Thermostat installations. 

 

Work area clean and free of debris 

 

Owner or operator instructed on control 
operation and routine maintenance. 

  

USER CONTROLS - GENERAL 

 
NAEC series is available with advanced-function 
electronic controls with membrane switch type keypad. 

 
ELECTRONIC CONTROLS

 

 
The chassis incorporating electronic controls is factory-
shipped with an active keypad control and display 
mounted directly to the control panel. The unit 
functions are controlled by the user by pressing the 
keys on the keypad, and reading the display. However, 
the unit also has the latent ability to be field-converted 
by qualified service personnel for use with a field-
supplied 24 volt AC wall thermostat. These 
instructions will address both unit-mounted control 
operation, and remote 24 volt AC wall thermostat 
operation.  
 

CONTROL AT THE UNIT, KEYPAD/DISPLAY  

 

THE KEYPAD CONTROL 

 
Become familiar with the keypad keys as shown in 
Figure 1. 
 

Display 

Red light emitting diodes (LEDs) display the actual 
temperature of the air entering the unit at floor level. 
The display can also be used to indicate the desired set 
point temperature for room comfort. It is important to 
remember that the temperature displayed is the 
temperature sensed at the unit’s indoor air inlet and can 
be significantly different from the bulk room 
temperature at a distance from the unit. 
 

 
 

 

Содержание NAEC SERIES

Страница 1: ...PFLOW PACKAGED TERMINAL AIR CONDITIONER PTAC Cooling with Electric Heat INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Страница 2: ...hout an air filter will void the warranty WARNING To avoid bodily injury ensure power is disconnected before removing the air filter as there will be potential exposure to rotating parts Always replace the air filter filter bracket and screw to close off the bottom of the unit to prevent unintended contact with the blower wheels before operating the unit Clean Coils As part of regular servicing cl...

Страница 3: ... on the unit Rating Plate for the specific chassis Wire sizing must also take into account any distance from fuse box or breaker panel to receptacle to prevent excessive voltage drop in undersized wires IMPORTANT Low voltage to the unit will cause compressor starting problems and decrease the performance and reliability of the compressor BRANCH CIRCUIT PROTECTION The Current Rating of branch circu...

Страница 4: ... chassis must be level from side to side and sloped toward the outdoors from front to rear in the order of 1 8 inch per foot once the chassis side flanges are drawn up tight to the wall sleeve using the four flange screws If the sleeve was originally installed with a slope in the bottom of the sleeve in the order of per foot downward from the indoor to outdoor side the chassis will still operate p...

Страница 5: ...TART UP CHECKLIST Note Once the unit is installed it should be checked for proper function by qualified service personnel before turning it over to the User Circuit breakers wire size and electrical connections tight and correct Filter clean and properly in place Condenser air inlet and outlet free of obstructions and no short circuiting of condenser air Unit operated for 20 minutes to prove stabi...

Страница 6: ...ds and then decreases room temperature by 1 degree for every subsequent press of the key F C Key This key toggles the display between Fahrenheit and Celsius temperature modes and affects all displayed temperatures Heat Key The Heat Key toggles the unit in and out of heating mode for every press of the key provided the On Off Key is ON Cool Key The Cool Key toggles the unit in and out of cooling mo...

Страница 7: ...g A factory supplied 24 Volt wiring harness is provided with every unit to facilitate connection to the wall thermostat wiring One end has a multi pin connector which mates with a connector exiting the unit The other end has preinstalled butt splice connectors which play a dual role in insulating any unused connectors and can also be used to make the wire connections for wires that are used The fi...

Страница 8: ...is detected at the location of the wall thermostat and is usually a much more accurate representation of bulk room temperature The thermostat used may have advanced features beyond the basic functions described below Consult your thermostat Installation and Operating Instructions for further information In addition to controlling room temperature the room thermostat is also used to select whether ...

Страница 9: ...d whether the unit is configured for keypad or remote thermostat The protection remains active when the unit is OFF for either keypad or remote thermostat application as long as the unit is plugged in power is available and a heat source is configured in the unit and is working Compressor Short Cycle Protection If the electronic control shuts the compressor down for any reason a 3 minute time dela...

Страница 10: ...only but it can be changed to open with low speed fan operation only by having qualified service personnel re wire the unit as shown on the specific wiring diagram affixed to the unit WARNING The conversion procedure involves exposure to high voltage electrical circuits in the control box in order to make the necessary change to the damper action tied to motor speed and must be performed by qualif...

Отзывы: