background image

– 37 –

24. Place a drop of “BLUE” Loctite on the blower 

setscrews and tighten all of the setscrews.

25. Align the blower and motor sheaves using a laser 

or straight edge and tighten the blower sheave to 
the shaft.

26. Replace the belts and tighten the motor base 

adjustment for the proper belt tension. Over 
tightening the belt tension will severely reduce 
belt and bearing life. Belt defl ection should be 
approximately 1/64 inch for every inch of span 
length.

27. Monitor for excessive heat or vibration during 

operation.

28. All bearings are pre-lubricated and should not 

initially require greasing. See previous section for 
bearing maintenance instructions.

Note: Drive side Sleevlock bearing installation 

(USRB5000A 115C)

WARNING: Do not apply grease, oil, or anti-seize 

compound to the tapered surface, bore, or 
shafting. If any of these substances are applied, 
equipment failure and personal injury may 
result.

1.  Mount all the bearings and leave all of the bolts 

and setscrews loose.

 2.  Tighten setscrews on the bearing to the 

tightening pattern as described in the 
installation sheet that comes with the bearing 
to a fi nal 30 inch lbs torque while rotating the 
shaft. Check to make sure the insert of the 
bearing is centered in the bearing housing and 
then bolt bearing down.

3.  Tighten down the bolts and setscrews on 

the remaining bearings per installation sheet 
starting from the non-drive end bearing back 
towards the Sleevlock while rotating the shaft.

3. Dampers – Dampers should be inspected monthly 

(daily in icy or snowy weather)

 for securely fastened 

linkages, and smooth operation. If dampers are binding 
or excessively noisy, then lubrication may be required. 
Place one drop of #20 wt. machine oil on each blade 
bearing, and linkage ball joint. Do not over lubricate, 
and wipe any excess from the area. Be sure to note 
that dampers over 49 inches long have intermediate 
bearings which require lubrication. On outdoor models 
with factory supplied discharge dampers, you will need 
to remove to top cover to access the damper bushings. 
Replace cover and caulk as necessary.

C. Air Filters

All fi lter banks should be equipped with a manometer 
or differential pressure switch to indicate when the 
fi lters are dirty. Filters should be replaced when 
the differential pressure across them reaches the 
manufacturer’s recommended fi nal value. Dirty fi lter 
elements should be replaced with a clean element of 

the same type and size. In addition, the factory not 
only suggests, but insists, that air fi lters be 

checked 

every 30 days (daily in icy or snowy weather)

 and 

replaced with new fi lters (throw-away type) or cleaned 
(washable type) as required. Cleanable fi lters should 
be given new application of fi lter coating after washing 
to maintain optimum fi lter performance.

The frequency of cleaning and replacing air fi lters 
applies twelve months of the year, 

where blowers 

are used for ventilation and heating.

D. Belt Tensions and Adjustments

Belt tension is adjusted during the initial run-in and test 
periods at the factory. However, the belts are run as 
slack as possible to prevent excessive damage to the 
bearings, yet tight enough to prevent slippage.

It is necessary, therefore, to tighten all belts during the 
fi rst few months of operation, and to 

check for proper 

tension weekly during

 

the

 

fi rst 60 days,

 after which 

30-day check intervals are suffi cient.

NOTE: Turn off all power to the equipment before 
checking belt tensions.

CAUTION: Do not attempt to tighten any belt or belts 
by changing the pitch of an adjustable pulley, as this 
will change the speed of a driven pulley, causing the 
unit to be rendered OUT OF AIR BALANCE. Do not 
overtighten belts.

Suggested Belt Tension Method is with the use of a 
Belt Tension  Checker

1.   Check tension frequently during the fi rst 24-48 

hours of run-in operation. Ideal tension is the 
lowest tension at which the belt will not slip under 
peak load conditions. Over tensioning shortens belt 
and bearing life.

Alternate Belt Tension Method

2.   To properly tension a conventional V-belt drive use 

the following procedure:
a. Measure the span length.
b. At the center of the span, apply a force perpen-

dicular to the span to defl ect the belt 1/64 inch 
for every inch of span length. For example, for a 
40 inch span, apply a force that will defl ect the 
belt 40/64 or 5/8 of an inch.

c. Compare the force you have applied with the 

values given in the table below. If the force is 
between the values for normal tension and 1-1/2 
times normal tension, the belt tension should be 
satisfactory. If the belt tension is not within this 
range, it can be adjusted by loosening the motor 
mounting bolts, and adjusting the position of the 
motor along its base.

Содержание IOMDFCDFM-1

Страница 1: ...errupteur 3 Éteindre toute flamme ouverte 4 Appelez immédiatement votre fournisseur de gaz AVERTISSEMENT Une installation déficiente de même qu un mauvais réglage modification entretien ou maintenance peuvent occasionner des dommages matéri els corporels voire causer la mort Lire attentivement les instructions d installation d utilisation et d entretien avant d installer ou d intervenir sur cet ap...

Страница 2: ...ion company when the claim is filed They will give you disposition instructions Packing We comply with the packing requirements of the transportation companies and your bill of lading proved that everything was in good condition when shipped That bill of lading contract requires them to deliver in perfect condition SECTION I FOREWARD As is the case with any fine piece of equipment care must be tak...

Страница 3: ... it should be protected from the weather with tarpaulins or plastic coverings Do not assume that simply covering a unit will keep insects dust and condensation out of the unit and critical components Rotate the fan s monthly Prior to beginning installation of a unit that has been in storage for weeks or months the unit and its components should be closely inspected Shipments are made F O B Dallas ...

Страница 4: ...ectrical Code and applicable local codes in Canada to the Cana dian Electrical Code Part 1 CSA Standard C22 1 The following recommendations are not intended to sup plant any requirement of federal state or local codes having jurisdiction Authorities having jurisdiction should be consulted before installations are made Lo cal codes may require additional safety controls and or interlocks All instal...

Страница 5: ...m the factory Use extreme caution in handling the curb Proper han dling and positioning will assure a water tight curb unit installation Re check approval prints prior to installation Be sure that there are no obstructions to ducting and that proper planning has been exercised in connection of piping and or electrical services The curb assembly may be bolted or welded to either trusses or roof dec...

Страница 6: ...unité devait être remplacé il doit être remplacé avec des câbles prévus pour résister à une chaleur d au moins 105 C F Field Piping Gas Piping All gas piping must be in accordance with the require ments outlined in the National Fuel Gas Code ANSI Z223 1 It is required that a ground union be installed adjacent to the manifold for easy servicing A drip leg and or filter should be provided upstream o...

Страница 7: ...pstream connection and low side to the downstream connection of the Airflow Station as shown in Drawing C000643 below Be sure that all tubing is clean and clear of any debris before installing tubes on the transducer Refrigerant Piping Evaporator Coil Blow Through The cooling coil section is located in the unit so that the supply air is blown through the evaporative coil s A properly piped trap sh...

Страница 8: ...TIONS TO TRANSDUCER PT 15 IN UNIT CONTROL ENCLOSURE 10 30 09 C000659B DRAIN PAN NOTE G TO BE A MINIMUM OF 1 2 PLUS THE TOTAL SYSTEM STATIC PRESSURE W C J TO EXCEED THE POSITIVE STATIC PRESSURE IN W C OF THE SECTION OF THE UNIT WHERE THE DRAIN IS INSTALLED PVC ADAPTER FITTING FPT x SLIP NIPPLE 10 30 09 C000659B DRAIN PANS UNDER A POSITIVE PRESSURE SUGGESTED P TRAP DESIGN FOR CONDENSATE G J PVC PIPE...

Страница 9: ...the standing roof seam Fig 3 and side seams where the sections come togeth er Fig 1 It is mandatory to seal the roof and side seams along the entire outside of the unit and it is strongly suggested that the seams also be sealed along the inside of the unit if possible 4 Apply caulking material along the top of both sides of the standing roof seam Fig 4 Place roof cap Fig 4 on top of the seam and s...

Страница 10: ...its are in the normal operating position 12 Check that system duct work is installed and free from obstructions 13 Check that fans turn free in housing 14 Check that the area around the unit is clear of flammable vapors or containers of flammable liquids 15 Check that all piping connections particularly unions are tight Check all gas piping for leaks using a soap bubble solution The most common ty...

Страница 11: ... call for heat 3 Watch for ignition spark following prepurge See IP module specifications 4 Time the length of the spark operation See the IP module specifications 5 After the module locks out open the manual gas cock and make sure no gas is flowing to the pilot or main burner 6 Reset the flame safeguard relay RE 02 7 Operate system through one complete cycle to make sure all controls operate prop...

Страница 12: ...fferent functions that control the fans and unit operation They are a Time Clock Heating and Cooling Night Setbacks and signal from an external source to an auxiliary digital input To disable the fans go to Unit Modes and enter OFF NOTE A BACview or PC is required to change Unit Modes For a more detailed control sequence see the Digital Control System User Manual If power supply meets requirements...

Страница 13: ...erature if you have disconnected plug wiresTS 01 andTS 03 Referred to in Section X NOTE 3 OR 4 TRIALS MAY BE NEEDED TO PURGE AIR FROM PILOT LINE IF BURNER HAS MAIN FLAME ROD OR SCANNER YOU WILL NEED TO DISABLE TIMER CIRCUIT RE 75 NOTE Pilot regulator adjustment may be needed if the adjustment of the needle valve does not yield the required reading Typical adjustment of the needle valve is 1 1 2 to...

Страница 14: ...low into the switch connection Switch operation will shut off the burner Recycle is automatic when the sensing tube is replaced The low air pressure switch is checked by removing the sensing tube from the leaving air side of the burner Switch operation will shut off the burner Recycle is automatic when the sensing tube is replaced E Adjustable Temperature and Limit Controls The limit controls are ...

Страница 15: ... valve terminal is energized RM7897A e Delayed second stage main valve terminal is energized RM7897C f Internal system fault occurred g Purge card is removed h Purge card is bad 5 MAIN FLAME ESTABLISHING PERIOD MFEP RM7897A teminal 21 a Airflow lockout feature is enabled and the airflow switch opens b Ignition terminal is energized c Ignition pilot valve terminal is not energized d Main valve term...

Страница 16: ...sence of flame the main fuel valve terminal 9 is powered If a flameout occurs the relay module locks out or recycles depending on status of jumper JR2 within 0 8 or 3 seconds depending on the Flame Failure Response Time FFRT of the amplifier b The RM7897A terminal 21 has a ten second MFEP After the Ignition Trials the interupted pilot valve terminal 8 is de energized If a flameout occurs the relay...

Страница 17: ... SERVICE NOTE Clipping and removing a site con figurable jumper enhances the level of safety Figure 5 Sequence Status LEDs Figure 6 Selectable Site Configurable Jumpers Table 7 Site Configurable Jumper Options Jumper Number Description Intact Clipped JR1 Pilot Flame Establishing Period PFEP 10 Seconds 4 Seconds JR2 Flame Failure Action Recycle Lockout JR3 Airflow Switch ILK Recycle Lockout Failure...

Страница 18: ...ECTOR SEE FLAME DETECTOR SPECIFICATIONS FOR CORRECT WIRING PROGRAMMED ON SETUP USING S7800A1142 DISPLAY PURGE TIME DEPENDS ON WHICH ST7800 IS INSTALLED 3 3 4 5 PREIGNITION INTERLOCK 10 SECOND INTERRUPTED PILOT POWER OPERATING CONTROLS AND INTERLOCKS BURNER FLAME SIGNAL INITIATE INITIAL POWERUP ONLY POWER STANDBY POWER PILOT FLAME MAIN PFEP 10 SEC 4 SEC IF JR1 CLIPPED POWER MFEP PILOT FLAME MAIN RU...

Страница 19: ... sure they are functioning properly 5 Inspect the Airflow Switch and make sure that it is functioning properly 6 Check the flame detector sighting position reset and recycle Measure the flame signal strength Verify that it meets specifications If not refer to the flame detector and or flame amplifier checkout procedures in the installation instructions 7 Replace the flame amplifier and or the flam...

Страница 20: ...t VPS connected to terminal 16 is functioning properly replace if necessary 4 Reset and sequence the relay module 5 If fault persists replace the relay module 1 Make sure the purge card is seated properly 2 Inspect the purge card and the connector on the relay module for any damage or contaminants 3 Reset and sequence the relay module 4 If the fault code reappears replace the purge card 5 Reset an...

Страница 21: ...quence the relay module 3 If fault does not repeat on the next cycle check for electrical noise being copied into the relay module through the external loads or possibly an electrical grounding issue 4 If the fault persists replace the relay module 1 Check wiring and operation of special OEM inputs 2 Reset and sequence the relay module 3 If fault reappears remove power from the device reapply powe...

Страница 22: ...heck power source 2 Check and replace 3 Close or connect customer inter lock 4 Enable the fan 5 Check time clock night setback thermostat and field installed con trols for proper settings 6 Reset freeze stat by interrupting power Check for proper setpoint and burner operation 7 See Digital Control System User Manual 8 Check power source and or re place 9 Check for power at damper motor and that en...

Страница 23: ...ame rod is in main flame check wiring and flame rod 5 Check for power and or replace 1 Manual pilot shut off valve closed 2 Inlet gas pressure lower than required gas pressure 3 No gas through pilot regulator with inlet gas pressure ok 4 No gas through pilot solenoid 5 Type of gas natural LP supplied different from factory required type Note components may change 6 Flame detection system not spark...

Страница 24: ...ectly 4 Unit Control Module UC 01 defective 5 Unit Control Module UC 01 not wired correctly 6 Damper motor defective 7 Dampers binding and or loose 1 Building Pressure Transducer PT 13 Damper Control Potentiometer or null switch defective or not calibrated 2 Building Pressure Transducer PT 13 Damper Control Potentiometer or null switch not wired correctly 3 Building Pressure Transducer PT 13 Dampe...

Страница 25: ... 1 signal conditioner provides signal conversion for a high impedance 2 10VDC signal source to drive a 24VDC solenoid The control should be powered by an isolated 24VAC transformer to drive up to a 5A dc solenoid Power Status LED A solid green LED indicates power and normal operation A slow blinking green LED indicates power but the 10 second start up delay has not completed A fast blinking green ...

Страница 26: ... RE 26 terminals 7 8 2 Check item B1 Check for 0 10 VDC input signal from UC 01 at terminals 1 2 Check for 0 20 VAC output signal to gas valve at terminals 5 6 3 Check DC Voltage on AO 1 4 Inspect 1 Measure resistance across modulator terminals 5 6 with connecting wires detached 2 Inspect Plunger should be installed to operate freely in solenoid sleeve 1 See valve adjustments in Section X 2 Close ...

Страница 27: ...plus pressure drop of the valve 2 Read manifold pressure using manometer and compare with the pressure stated on the specification plate 1 Check setpoint on Unit Enable Potentiometer MP 15 2 Check Discharge Air Temperature Sensor TS 03 and wiring See Thermistor curve 3 Check setpoint with BACview or PC 1 Measure resistance across modulator terminals with red lead wires disconnected 2 Inspect wirin...

Страница 28: ...d check limit controls for normal operation 1 Arrow on side of valve should point in direction of gas flow 1 Remove wires connected to amplifier terminals 5 6 and measure resistance MR212 60 80 ohms M611 45 55 ohms 2 Inspect plunger should be installed to operate freely in solenoid sleeve 3 Disassemble valve for inspection of internal parts 1 Check for 24V AC at amplifier terminals 7 8 2 Measure r...

Страница 29: ...it in Discharge Air Temperature Sensor TS 03 2 Incorrect Maximum Heating Discharge Temperature Setpoint 1 Short in modulator coil circuit 1 Incorrect Minimum Heating Discharge Temperature Setpoint 2 Incorrect space setpoint 3 Insufficient burner capacity G Continuous High Fire Electronics Problem H Continuous High Fire Electronics OK I Incorrect High Fire J Continuous Maximum Discharge Air Tempera...

Страница 30: ... are energized and condensing unit or evaporative cooler is not on C Incorrect Space Temperature 1 Enable the cooling mode 2 Check auxiliary circuit wiring and contact 3 Adjust the air flow and external static pressure to match the unit rating plate DO NOT ADJUST SWITCHES 4 Change to correct setpoints See Digital Control User Manual 5 See Digital Control System User Manual 1 Check and or replace 2...

Страница 31: ...ow Station Pressure Transducer PT 15 1 Remove the tubes at the Low and High pressure fittings 2 The voltage at COM and OUT should be O VDC If not adjust Z do not adjust S 3 Make sure the Low and High fittings are clean do not insert any sharp objects into the pressure fittings make sure the static pressure sensing pitot tubes and all tubing is also clean clear of any debris and then reinstall the ...

Страница 32: ...Some adjustments can be made by repositioning the burner profile plates If the velocity will allow the High Velocity Switch to open you can open the profile plates If the velocity will allow the Low Velocity Switch to open you can close the profile plates REMEMBER to keep the opening between the burner and profile plates the same on both top and bottom of the burner when making these adjustments D...

Страница 33: ...ILURE SW 72 RS 01 100 OA or 100 OUTPUT IN 4 RE 27 RS 04 BURNER STATUS RE 65 RS 03 FAN STATUS RE 12 TO GND RS 02 CLOGGED FILTER SW 09 RS 01 1 36 1 73 1 87 1 92 1 36 1 73 1 87 1 92 AUXILIARY UNIT ENABLE MULTIPLEXED VOLTAGE VALUES CHECK ALL TERMINAL CONNECTIONS FOR TIGHTNESS The DC voltage is to be checked at the UC 01 board With the Fan Enabled When the fan status relay RE 65 is energized the contac...

Страница 34: ...or latches p Check that cabinet is weathertight replace door gas kets and recaulk as necessary NOTE Keep screened air intakes clear of obstruc tions at all times WARNING Failure to comply with the general safety information may result in extensive property damage severe personal injury or death Periodic maintenance is essential to the efficient operation and extended service life of this equipment...

Страница 35: ... been pre lubricated with high quality lithium complex base grease with an EP additive The grease is a lithium complex base mineral oil NLGI Grade 2 consistency with a base oil viscosity of ISO VG220 Re lubrication should be done with lithium complex thickened grease with a compa rable NLGI consistency and base oil type and viscosity Wipe all grease fittings clean before adding grease Grease shoul...

Страница 36: ...s end of the shaft by pushing on the inner ring Do not use a hammer 10 Slide the shaft through the next blower wheel hub and add another bearing Continue this procedure until the shaft is through all of the blower wheels 11 Place a bearing on each end of the shaft 12 Replace the shims as required 13 Install bearing mounting bolts do not tighten and check alignment 14 Tighten the bearing bolts to r...

Страница 37: ...ed when the differential pressure across them reaches the manufacturer s recommended final value Dirty filter elements should be replaced with a clean element of the same type and size In addition the factory not only suggests but insists that air filters be checked every 30 days daily in icy or snowy weather and replaced with new filters throw away type or cleaned washable type as required Cleana...

Страница 38: ...er supply so there can be no accidental start up during inspection b Inspect the burner carefully including upstream and downstream sides of mixing plates as well as burner body face Note that complete burner assembly may have to be removed for proper inspection and cleaning Any accumulation of scale or foreign material on either side of the mixing plates should be removed with a wire brush Check ...

Страница 39: ...dequate once the initial piping debris is removed The operating conditions of the burner will determine how frequently maintenance is actually required P001117C Mestek Line Burners Use of an electric drill motor is not suggested unless both Pin Vise and Drill can be chucked up in a vari speed drill unit Use caution because it is easy to snap the bits off in a port when using a drill motor Removal ...

Страница 40: ... WITH DDC MR212 High Fire Manifold Adjustments Note Low fire may need to be set first to get the burner to light off properly 1 Disconnect the plug where the Temperature Sensors TS 01 and TS 03 are wired to the unit control module UC 01 A minimum of 15vdc is required at terminals 5 and 6 on electric relay RE 26 This causes the valve to call for continuous high fire Caution The unit will shut down ...

Страница 41: ...e voltage Above approximately 15 volts DC the Valve should be delivering full flow to the heater and the unit should be on full fire If the DC voltage is obtained on the Valve terminals but the heater does not respond as described the problem can be isolated to the valve itself or to the gas control manifold of the heater If the proper voltages are not obtained the problem can be isolated to the e...

Страница 42: ...entilation requirements for the facility must be ad dressed separately The heater inlet shall be located in accordance with applicable building code provisions for ventilation air Field constructed intake accessories should be prop erly designed to minimize the entry of snow and rain All ventilation air to the heater shall be ducted directly from the outdoors If in doubt regarding the application ...

Страница 43: ... 43 ...

Страница 44: ...4830 Transport Drive Dallas TX 75247 Phone 214 638 6010 Fax 214 905 0806 www appliedair com ...

Отзывы: