– 17 –
SEQUENCE
STATUS
LEDs
RESET
PUSHBUTTON
FLAME
SIMULATOR INPUT
FLAME CURRENT
TEST JACKS
RUN/TEST SWITCH
(RM7895C,D;
EC7895C;
RM7896C,D)
CAPTIVE
MOUNTING
SCREW
PLUG-IN
PURGE
CARD
DUST
COVER
RELAY
MODULE
FLAME
AMPLIFIER
M7552A
RUN/TEST SWITCH
(EC7895C; RM7895C,D; RM7896C,D)
SELECTABLE CONFIGURATION JUMPERS
M7553A
Figure 4 - RM7897A,C Relay Module Exploded View
SECTION VII - TROUBLE SHOOTING
continued
SETTINGS AND ADJUSTMENTS
Selectable Site-Confi gurable Jumpers
The relay module has three site-confi gurable jumper
options, see Fig. 6 and Table 7. If necessary, clip the
site-confi gurable jumpers with side cutters and remove
the resistors from the relay module.
SERVICE NOTE: Clipping and removing a site-con-
fi gurable jumper enhances the level of safety.
Figure 5 - Sequence Status LEDs
Figure 6 - Selectable Site-Confi gurable Jumpers
Table 7 - Site-Confi gurable Jumper Options
Jumper
Number Description
Intact Clipped
JR1*
Pilot
Flame
Establishing
Period
(PFEP)
10 Seconds 4 Seconds
JR2
Flame
Failure
Action Recycle Lockout
JR3
Airfl
ow
Switch
(ILK)
Recycle Lockout
Failure
IMPORTANT: Clipping and removing a jumper after
200 hours of operation causes a nonresettable Fault
110. The relay module must then be replaced.
L
L
E
W
Y
E
N
O
H
R
E
W
O
P
PILOT
FLAME
MAIN
ALARM
RESET
PURGE
TIMER
WIRING
SUBBASE
CAPTIVE
MOUNTING
SCREW
RUN/TEST (C,D ONLY)
SWITCH
CONFIGURATION
JUMPERS
RELAY
MODULE
SEQUENCE
STATUS
LED PANEL
RESET
BUTTON
FLAME
AMPLIFIER
M22827
:
T
I
D
E
K
C
A
B
-
R
E
T
N
E
-
R
E
N
R
U
B
T
N
O
C
L
O
R
_
+
KEYBOARD
DISPLAY
MODULE