MANAGEMENT
SYSTEMS
Assessed to ISO 9001:2008
Cert/LPCB ref. 010
Assessed to ISO 14001:2004
Cert/LPCB ref. 010 EMS
MANAGEMENT
SYSTEMS
Cert/LPCB ref. 010
PRODUCT
CERTIFICATION
Apollo Test Set - User Manual
17
Tap the Fast Test button, the fast test
is activated immediately. If a fast test
cannot be done - a message ‘Fast test
cannot be performed’ appears and the
splash screen returns to the single
address view.
If the message shown on the left appears,
the fast test is active and you should
apply smoke or heat to the detector as
appropriate.
When the sensor in the detector has
entered alarm, the green ‘Pass’ text will
appear and the sensor name changes
to green. The sensor name remains
green until the analogue value returns
to its initial value, the sensor name then
changes to white.
To stop the test or close the Fast Test
splash screen, tap on the main screen to
the left of it. The data restore operation
starts.
(a)
(b)
If the device successfully passes the data
restore operation, the ‘Data restored’
splash screen (a) appears. If the data
restore is not successful the ‘Issue during
restore operation’ splash screen appears
along with details of the initial device
settings (mode, polling LED status).
Tap either ‘Retry’ or ‘Dismiss’ as appro-
priate.
‘Retry’ will start the test again.
‘Dismiss’ closes the Fast Test splash
screen.
Содержание SA7800-870APO
Страница 1: ...Apollo Test Set User Manual 1 Apollo Test Set User Manual...
Страница 45: ...Apollo Test Set User Manual 45 Appendix C Loop supply from direction OUT...
Страница 47: ...Apollo Test Set User Manual 47 Appendix E Earth fault location search...
Страница 49: ...Apollo Test Set User Manual 49 Appendix G Line Voltages...