![Apollo SA7800-870APO Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/apollo/sa7800-870apo/sa7800-870apo_user-manual_2954611016.webp)
MANAGEMENT
SYSTEMS
Assessed to ISO 9001:2008
Cert/LPCB ref. 010
Assessed to ISO 14001:2004
Cert/LPCB ref. 010 EMS
MANAGEMENT
SYSTEMS
Cert/LPCB ref. 010
PRODUCT
CERTIFICATION
Apollo Test Set - User Manual
16
Changing the output bit status
To change the output bit status of a
particular device, tap on the required
address, the single address splash
screen appears.
Tap the output bit icon that you want to
change the status of.
ON
OFF
To close the single address splash
screen, tap on the main screen to the left
of it.
However, for details of self test, fast
test, isolator control and configuration
settings - read on.
Self test
Tap the Self Test button, the self test
is activated immediately. The circle
represents a countdown timer which
is set at 20 seconds. If the analogue
value increases to 55 before the timer
expires, a ’Pass’ splash screen appears,
otherwise a ‘Fail’ splash screen appears.
If you want to stop the self test, or close
the splash screen after the test, just tap
on the main screen, to the left of it.
Fast Test