9
FUNCTIONS OF PANELMETER MENU
Parameters of functions ALA-1 to ALA-4
ALSP
- setting of alarm value
HYST
- setting of alarm hysteresis
MODE
- assignment of limit switch mode (absolute or as a deviation from required menu)
Options:
State
limit switch value ALSP is directly connected to comparator
shift
value SP (required) is directly connected to comparator, shifted by limit switch
value ALSP (see limit switch functional characteristics)
RELE
- state of output relay when limit switch value is achieved (relay 3)
Options:
Off
relay switches off when set value for limit switch is exceeded
On
relay switches on when set value for limit switch is exceeded
IN
-
selection of input for which limit switch shall be configured, see limit switch diagram
Options:
IN-1
input 1
in-2
input 2
addin
sum of inputs IN-1 + IN-2
subin
difference of inputs IN-1 - IN-2
IN-3
input 3
IN-4
input 4
TRAL
- state of relay contacts after alarm conditions subside
Options:
no
temporary switching of limit switch – after limit switch alarm conditions subside,
limit switch returns to original state
yes
permanent switching of limit switch – after limit switch alarm conditions subside,
limit switch remains permanently switched. It can be switched off only after
subsiding of alarm conditions and disconnecting of regulator from supply voltage
If alarm relays are not connected, alarm MENU is not displayed.
Press MENU key to enter configuration menu. Scroll to required function (ALA-1)with keys UP and DOWN .
Press MENU to enter submenu of required function. Set required parameter using keys UP and DOWN . Press
MENU key again to get to parameter setting mode. Set required value or parameters with UP and DOWN keys.
Press SET to return to submenu of required function. Press key SET again to return to configuration menu.
Press SET key again to return to working menu and to save selected parameters.
9.2.2
Configuration of limit switches - ALA-1 to ALA-4
measured value
function selection