16
4
CONNECTION
Connect sources of current signals to connectors 11, 12, 16 as shown on the diagram where connector no.
16 is minus. Press
MENU
key and enter apparatus configuration menu, browse to the function of sensor se-
lection
SEN -1
,
SEN -2
,
SEN -3
,
SEN -4
. With repeated press get to submenu for selection of
sensor type typ. With press the menu key again and enter submenu, where with keys
UP
and
DOWN
set
for active current signal 0/4 - 20 mA select
0- 20
or
4 - 20
for iputs
SEN – 1
and
SEN – 2
. If option
-no-
is selected, input is disabled and press key SET to confirm the selection. Then setup range of mea-
surement. Start of range define in
MENU
with function
STRS
, and ending of the range with function
ENDS
.
Connect voltage signals to connectors 13, 14, 16 as shown on the diagram where connector no. 16
is common, connected to minus. Press
MENU
key and enter apparatus configuration menu, brow-
se to the function of sensor selection
SEN -1
,
SEN -2
,
SEN -3
,
SEN -4
. With repeated
press get to submenu for selection of sensor type typ. Press the menu key again and enter subme-
nu, where with keys
UP
and
DOWN
set for voltage signal 0 – 10 V select
0 - 10
for inputs
SEN -2
,
SEN – 3
. If option
-no-
is selected, input is disabled and press key
SET
to confirm the selection
. Then setup range of measurement. Start of range define in
MENU
with function
STRS
, and ending
of the range with function
ENDS
.
Ordering code of input 36
( AP11-36-x..... )
Ordering code of input 36
( AP11-36-x..... )
fig. 10
fig. 11
4.4.5
Current signal 0/4 - 20 mA (active current signal)
4.4.6
Voltage signal 0 – 10 V
Auxiliary input
for setup of MENU
parameters
Auxiliary input
for setup of MENU
parameters