PANELMETER FUNCTIONS
Limit switch mode with MODE set to STATE
(limit shift mode related to measured value)
After limit switch value is achieved relay state set to OFF
After limit switch value is achieved relay state set to ON
Example:
Switching off of the limit switch with temperature increase over 60 °C. Required value will not be used.
Alarm shall be set to the value of limit switch. Deactivating of limit switch alarm is required at 55 °C.
Panelmeter setting:
In configuration menu set input with sensor connection (function in) e.g. in-1. Then set value of limit
switch ALSP to 60 and function MODE to value STATE. State of output relay set in RELE menu to OFF. Set de-
activating of limit switch in menu HYST to value 5. Confirm and leave the setting by pressing key SET.
Example:
Switching of the limit switch with temperature increase over 60 °C. Required value will not be used. Deac-
tivating of limit switch alarm is required at 58 °C.
Panelmeter setting:
In configuration menu set input with sensor connection (function in) e.g. in-1. Then set value of limit
switch ALSP to 60 and function MODE to value STATE. Set state of output relay in RELE menu to ON. Set de-
activating of limit switch in menu HYST to value 2. Confirm and leave the setting by pressing key SET.