Installation and Operation Manual
ECN: 003155
Date: 06/4/2013
15
AC-SmartStart-7608-Series_IOM Rev 04
AFFT04 05
Sets outlet #5 to turn on fourth in the programmed se-
quence.
UFFT04 05
AFFT05 04
Sets outlet #4 to turn on fifth in the programmed sequence.
UFFT05 04
AFFT06 03
Sets outlet #3 to turn on sixth in the programmed sequence.
UFFT06 03
AFFT07 02
Sets outlet #2 to turn on seventh in the programmed se-
quence.
UFFT07 02
AFFT08 01
Sets outlet #1 to turn on eighth in the programmed se-
quence.
UFFT08 01
UNDERVOLTAGE SETPOINTS
AFFUA
Returns the current value of the “A” channel undervoltage
dropout setpoint in Hex format. ... 5A = 90 VAC
UFFUA 5A
AFFUA D2
Changes the value of the “A” channel undervoltage dropout
setpoint to D2 Hex. D2 = 210VAC Valid range from 00 to
FF hex.
UFFUA D2
AFFUB
Returns the current value of the “B” channel undervoltage
dropout setpoint in Hex format. 5A = 90 VAC
UFFUB 5A
AFFUB D2
Changes the value of the “B” channel undervoltage dropout
setpoint to D2 Hex. D2 = 210VAC Valid range from 00 to
FF hex.
UFFUB D2
SOFTWARE VERSION
AFFv
Returns the microprocessor software version
UFFvSSJR 1X8 v3.4
LINE VOLTAGE MEASUREMENT
AFFVA
Returns the input voltage level for channel “A”
UFFVA123.5 Volts
AFFVB
Returns the input voltage level for channel “B”
UFFVB118.5 Volts
REMOTE MESSAGE/WORD FUNCTION
AFFW1
Returns the value of the #1 remote message.(FF not active,
00 active)
UFF W1 FF
AFFW1 00
Activates the #1 remote message function.
UFFW1 00
N/A
Remote message indicator word
UFFW1 01
AFFW2
Returns the value of the #2 remote message.(FF not active,
00 active)
UFFW2 FF
AFFW2 00
Activates the #2 remote message function.
UFFW2 00
N/A
Remote message indicator word
UFFW2 01
RESTORE FACTORY DEFAULTS
AFFZ
Changes all settings back to factory default
UFFZ
Operational Commands