Analog Low (AL SET) & Analog High (AH SET) Setpoints:
Allows the user to define the reading values associated with the Low Analog
signal (i.e. 4mA or 0V) and the High Analog signal (i.e. 20mA, 2V or 5V).
NOTE:
The analog signal can be spanned over any portion of the pressure
range, and can also be inverted by setting the Analog Low Setpoint as
the higher pressure value. Negative pressure values can also be used
as either the Analog High or Analog Low Setpoints.
Setting the Analog Signal Span:
Step 1: Press the On/Off button once to enter the main setup menu.
Step 2: Press (Z) to cycle through the options until AdVSET is displayed.
Step 3: Press (S) to access the Advanced Settings menu.
Step 4: Press (Z) to cycle through the options until AL SET is displayed.
Step 5: Press (S) to access the Analog Low setpoint value. A 5-digit number
will appear with the first digit flashing.
Step 6: Press (Z) to change the value of the first flashing digit
(options: 0-9 or “-”).
Step 7: Press (S) to accept the value of the flashing digit and advance to the
next digit......repeat steps 7 and 8 until the desired Analog Low reading
is fully entered. After the last digit is accepted by pressing (S), the
display will return to the main options menu.
Step 8: Press (S) to reenter the Advanced Settings menu.
Step 9: Press (Z) to cycle through the options until AH SET is displayed.
Step 10: Repeat Steps 5-7 to enter the Analog High setpoint value.