• Operation Modes
MODE DESCRIPTION PARAMETERS
1
Units
Range = 0-2
Default = 0
0 = feet
1 = inches
2 = mm
Mode 1 is used to select the units of measurement that will be used throughout the setup process and also
for display. The units will also determine the resolution of the display and the outputs. The resolution is: feet
0.01, inches 0.1, and millimeters 1.
NOTE
: All modes must be set using the units selected in Mode 1.
MODE DESCRIPTION PARAMETERS
2
4 mA distance
Units = Mode 1
Range = 0-9999
Default = 1.00 ft.
Mode 2 sets the 4 mA distance, measured from the Zero Point (See mode 10).
MODE DESCRIPTION PARAMETERS
3
20 mA distance
Units = Mode 1
Range = 0-9999
Default = 25.00 ft.
Mode 3 sets the 20 mA distance, measured from the Zero Point (See mode 10).
For Distance configuration (i.e., greater mA output for target surface further from sensor), set the mode 2
distance to be less than the mode 3 distance (See Figure 3.3).
For Fill configuration (i.e., greater mA output for target surface closer to sensor), set the mode 2 distance to
be greater than the mode 3 distance (See Figure 3.4).
Zero Point
Max. Distance
Zero Point
Max. Distance
mode 2 mode 3
mode 3 mode 2
20 ma
4 ma
20 ma
4 ma
Figure 3.3
Figure 3.4