12.5. RECORDING SETTINGS

 

Data is archived in a text file with a 

csv

 extension in the internal memory or the USB memory; a detailed 

description of the storage format is given in chapter 14. Data is recorded until the memory is full (at least 2 years of 
continuous operation with recording of 4 channels every 1 s) and then the recording is stopped and the message 

Memory full. Recording rejected

” is displayed (chapter 15). The recording must then be stopped (the 

Recording 

type

 must be set to the 

Off 

value, Table 12.5), the archive files must be copied for further analysis, and space must 

be freed up in the memory for future recordings. The selection of the memory for recording and the copying and 
deleting  of existing 

csv 

files are accessible in the 

Main Menu

 -> 

Memory and file options

; a detailed description of 

operations performed on files is given in chapter 12.6. The

 Data recording interval

 must be adjusted according to 

the needs of a specific application. 

Table 12.5. Configuration parameters in the 

Recording settings

 menu 

Parameter  

 

Range of variability of the parameter and description 

Default 

settings 

Data recording interval

     1 s to 8 h (note 3 in the technical data, chapter 5)

     (1)

 

1 minute 

Recording type    

(2) 

(chapter 14)

 

 
 

 Off

 

recording switched off 
permanently 

possibility to set those values using 
the 

[F]

 button, chapter 10, item c 

Disabled

 

  

Continuous

 

recording switched on 
permanently

 

 Limited by 

date and time 

recording is active within the range of the 

Date

 and the 

Time

 

defined by the parameters 

Start

 and 

End of time limit 

  Periodic 

daily (hourly) 

recording is active within the range of the 

Time

 defined by the 

parameters 

Start

 and 

End of time limit 

  Above the 

permission 
threshold 

recording is active when the measured value defined by the 

Selection of permission channel

 parameter is larger than the 

value of the 

Permission threshold value

 parameter 

  Below the 

permission 
threshold 

recording is active when the measured value defined by the 

Selection of permission channel

 parameter is smaller than the 

value of the 

Permission threshold value

 parameter

 

 Only during 

control 

recording is active when there is a permission for control for all 
outputs (can be controlled from the 

[F]

 button level of from 

the level of the optional input 

BIN5

, chapters 7b, 10c, and 12.0 

Start of time limit 

Date

01.06.2008

 ÷ 

31.12.2099

Time

00:00:00

 ÷ 

23:59:59

, the parameter is 

active when the 

Type of recording 

=

 Limited by date and time 

or

 Cyclical daily

 

2013.06.01 

00:00:00 

End of time limit 

Date

01.06.2008

 ÷ 

31.12.2099

Time

00:00:00

 ÷ 

23:59:59

, the parameter is 

active when the 

Type of recording 

=

 Limited by date and time 

or

 Cyclical daily

 

2013.06.01 

00:00:00 

Selection of permission 
channel 

menu items (values) the same as for the 

Measured value to be displayed

 

 

parameter in the 

Display channels configuration

 menu (chapter 12.2), the 

parameter is active when the 

Recording type 

=

 Above 

or 

Under the permission 

threshold

 

Measurement 

from input 1

 

Permission threshold 
value 

-999.9

 ÷ 

9999.9°C

-9999 

÷

 19999

 

(3) 

or 

-9999 

÷

 99999

 units  

(3) 

the parameter is active when 

Type of recording 

=

 Above 

or 

Below the 

permission threshold

 

50.0 °C  

Notes:  

(1)

 - the recording interval is counted from the moment the device is disconnected from the USB port 

 

         

(2)

 - the device does not record data in a file when it is connected to the computer's USB port 

 

        

(3)

 – applies to analogue inputs (mA, V, mV, Ω) 

 
 
 
 
 

Содержание AR654

Страница 1: ...IVERSAL FOUR CHANNEL CONTROLLER WITH PROCESS RECORDING AND ATIMER Version 1 0 1 2017 03 24 APAR SALES OFFICE 05 090 Raszyn ul Ga czy skiego 6 Tel 48 22 101 27 31 48 22 853 49 30 E mail automatyka apar...

Страница 2: ...TOUCHSCREEN 10 11 DESCRIPTION OF DATA SHOWN ON THE LCD DISPLAY 12 11 1 UPPERAND LOWER DEVICE STATUS BAR 12 11 2 VIEW OFAMEASUREMENT GROUPAND CONTROL PARAMETERS CONTROL 13 11 3 VIEW OFAMEASUREMENT GRO...

Страница 3: ...MODBUS RTU TCP 37 21 USER S NOTES 40 Please pay particular attention to the text marked with this sign The manufacturer reserves the right to make changes to the design and the software firmware of t...

Страница 4: ...N to change the operating modes of the associated outputs control start stop selection of the day night setpoint value manual automatic mode for outputs the analogue outputs are logically connected to...

Страница 5: ...d transducers current output depending on the version compensation of line resistance for resistance sensors automatic or permanent compensation of thermocouple cold tip temperature automatic or perma...

Страница 6: ...e 200 620 C thermocouple E TC NiCr CuNi 25 850 C Pt1000 RTD 3 or 2 wire 200 620 C thermocouple N TC NiCrSi NiSi 35 1 300 C thermocouple J TC Fe CuNi 40 800 C current mA Rin 100 0 4 20 mA thermocouple...

Страница 7: ...B s depending on the type of the memory RS485 MODBUS RTU protocol SLAVE speed 2 4 115 2 kbit s sign format 8N1 galvanic separation Ethernet type 100base T socket RJ45 data transfer up to 135 kB s depe...

Страница 8: ...signals a measurement connections RTD TC mA V mV R INPUT1 INPUT4 the parameters configuration is described in chapter 12 3 a 1 connection of the 2 and 3 wire transducer Iou output current Uou output...

Страница 9: ...site In the Windows 7 system from the Device Manager level manual installation is performed in the following manner 1 Right click the item Apar Composite Device and select Update the driver software a...

Страница 10: ...guration display of current measurement data as well as the date and the time configuration of the real time clock RTC and other parameters such as types measurement inputs names of measurement channe...

Страница 11: ...ling the Device status screen hardware information operation and Ethernet services parameters current record number in the csv archive file etc the function is available also from the level of the F b...

Страница 12: ...ching the area of the displayed measured value PV or setpoint value SP change of the setpoint value selected with the Setpoint SP selection parameter chapter 12 4 1 limit of settings defined by parame...

Страница 13: ...iew of a measurement group text and an analogue indicator none single measurement chart Quick configuration screen for main parameters of the control channel 9 Tx Rx signalling of presence of serial t...

Страница 14: ...haracters and unit up to 4 characters of the measurement channel name and unit taken from the AR654 txt file chapter 12 2 measured value PV with signalling of exceeded measurement range chapters 12 3...

Страница 15: ...easured value PV and unit of the measurement channel chapters 11 2 and 11 3 graphic presentation of the measurement analogue indicator works in the range set by the parameters Bottom of the range for...

Страница 16: ...ter to be changed viewed use the SET button or touch the selected item in the menu also in order to edit the parameter use the UP DOWN LEFT or RIGHT button or the scroll bar to change the value of the...

Страница 17: ...eypad or on line via the computer s USB port because the changed parameter values are stored in the internal memory after the user exits the Main Menu by pressing the ESC button or disconnects the dev...

Страница 18: ...2 IN3 IN4 The smallest of the measurements IN3 and IN4 Sum of the measurements IN1 IN2 The smallest of the measurements IN1 IN2 and IN3 Sum of the measurements IN3 IN4 The smallest of IN1 IN2 IN3 IN4...

Страница 19: ...signal 0 10 V 0 60 mV voltage signal 0 60 mV 0 850 resistance signal 0 850 Line resistance 1 0 00 50 00 total resistance of leads for 2 wire RTD sensors and 850 0 00 Thermocouple cold tip temperature...

Страница 20: ...For outputs that are not related to any displayed measurement channels the Quick configuration screen chapter 11 7 is not available and the operating parameters of those outputs must be configured in...

Страница 21: ...arameters Setpoint value for the manual mode and Pulsing period for the manual mode described further in this table Setpoint value SP selection Setpoint alarm value SP1 applies to SP1 and H1 from the...

Страница 22: ...ter is insignificant chapter 12 4 1 3 5 sec Output emergency state No change status of the control alarm outputs if the measurement range of the control signal is exceeded or in the case of a failure...

Страница 23: ...ement channel is to use the Quick configuration screen chapter 11 7 As an alternative it is possible to change the setpoint values in the parameter configuration mode using the methods described in ch...

Страница 24: ...program control chapter 12 4 3 which can be useful to control the actuator elements e g heating cooling with power control or for impulse optical acoustic signalling The operation status and the setp...

Страница 25: ...nu for the selected PID set 1 8 Parameter Range of variability of the parameter and description Default settings Assigned and active outputs the numbers 1 4 or None are displayed of the control output...

Страница 26: ...location of the range of proportionality Pb in relation to the setpoint value SP for heating parameter Control type Reverse heating b location of the range of proportionality Pb in relation to the se...

Страница 27: ...used buttons or BIN inputs The power supply must be switched on immediately after the tuning is started in the output switch on delay phase If the power supply is switched on later an erroneous analy...

Страница 28: ...2 and in the Quick configuration screen the status of operation of the program is shown in the line starting with the phrase PRGx where x is the number of the program the meaning of the individual fie...

Страница 29: ...and the Pulsing period taken from the parameters of the associated auxiliary output chapter and table 12 4 1 Sound signal Disabled signalling of the duration of the section with a built in acoustic tr...

Страница 30: ...active within the range of the Time defined by the parameters Start and End of time limit Above the permission threshold recording is active when the measured value defined by the Selection of permis...

Страница 31: ...ected or the internal memory when there is no USB memory Identification number ID 0 999 an individual device number entered into the initial records in the archive file csv in order to distinguish arc...

Страница 32: ...e names as well as access to the archive files with the exception of the RS485 Moreover the Ethernet enables displaying information on the operating status and on measurements of the controller in any...

Страница 33: ...hout a fixed public IP address an active account in a DDNS service is required the description can be found in chapter 12 8 1 Disabled Enabled Dynamic DNS settings and status Configuration data and st...

Страница 34: ...ary unavailability of the service or permanent nature which indicates inadequate Internet connection improper configuration of the connection or service codes 2 to 12 e g DDNS 5 means invalid username...

Страница 35: ...switched on the control status is exactly the same as at the time of switching off the power supply no change chapter 12 6 Touch panel lock touch screen and keypad lock except for F BIN5 input functi...

Страница 36: ...tes text files with the csv extension in the internal memory or the USB memory Additional new csv files are created each time the power supply is switched on and each time a new recording is started e...

Страница 37: ...disk operations being performed In order to close the message window appearing in the display use the SET or ESC button Fig 15 Appearance of an example message window 16 IMPORTANT COMMENTS PERTAINING...

Страница 38: ...both ends of the line 150 each between lines Equipment from different manufacturers that form the RS485 network e g RS485 converters USB may have integrated polarizing and terminating resistors in su...

Страница 39: ...unctions READ 3 or 4 WRITE 6 Table 19 1 Request frame format of the MODBUS TCP protocol for the READ and WRITE functions frame length 12B Heading of the MODBUS protocol 7 bytes Function code READ or W...

Страница 40: ...reserved R 0x42 66 0x0101 0x630C years HB and months LB Parameter Start of the time limit chapter 12 5 R W 0x43 67 0x0100 0x1F17 days HB and hours LB R W 0x44 68 0x0000 0x3B3B minutes HB and seconds...

Страница 41: ...2 Parameter State of control after power up R W 0xAA WY 32 0 2 Parameter Control time R W 0xAB WY 32 0x0101 0x630C years HB and months LB Parameter Start of control time R W 0xAC WY 32 0x0100 0x1F17...

Страница 42: ...R W 0x14E 334 0x0000 0xFFFF Octet2 HB Octet1 LB 0x14F 335 0x0000 0xFFFF Octet4 HB Octet3 LB Parameter Default gateway chapter 12 8 R W 0x150 336 0x0000 0xFFFF Octet2 HB Octet1 LB 0x151 337 0x0000 0xFF...

Отзывы: