9. 

top1

 end of scale for the 

exceeded range alarm 

in the measurement range of the specific input 

999.9

 °C

 

10: 

cALo

 calibration of the 

zero

 

zero offset for measurements: 

 

/00.0

 ÷ 

100.0

 °C   

or 

/000

 ÷ 

1000

 units (

1

)

 

0.0

 

°C

 

11: 

cALG

 gain

 

-85.0

 ÷ 

115.0

 %

 

calibration of inclination (sensitivity) for measurements

 

100.0

 %

 

12: 

Addr

 MODBUS address of 

the device 

1

 ÷ 

247

 

13: 

br

 transmission speed 

[bps] 

0

=600, 

1

=1,200, 

2

=2,400, 

3

=4,800, 

4

=9,600, 

5

=14,400, 

6

=19,200, 

7

=38,400, 

2

 = 2400 

 

Notes:   (1)

 – applies to analog inputs ( mA, V, mV, Ω ), 

 

 

(2)

 – applies only to display of data in the connected programmer (AR950, AR956), 

 

 

(3)

 – for 

Filt

=

1

, the response time is approx. 0.135 s; for 

Filt

=

10

 - approx. 1.5 s. Higher degree of filtration  

 

 

       means a more smooth measured value and a longer response time, which is recommended in the case  

 

 

       of turbulent measurements (e.g. water temperature in a boiler). 

 
 

10. CONFIGURATION OF THE ALARM OUTPUT

 

The type of alarm characteristics for the OC output is determined by parameter 5: 

oVt1

  (see chapter 9, Table 9).  

For 

oVt1

=

retr

, the OC output is connected after the measured value exceeds the range defined by parameters 8: 

bot1

 and 9: 

toP1

. In this mode, the alarm condition is additionally indicated by the blinking of the 

A

 LED diode on 

the front panel.  
When the 

oVt1

 parameter becomes equal to 

inu

 or 

dir

parameter 6:  

SEt1

 and 7: 

H1

 apply, the status of the 

output is indicated by the 

A

 LED (it is on when the output is switched on). 

The principle of operation of the OC output in the individual operating modes is shown in the figures below. 
 

 

 
 

11. SIGNALING OF MEASUREMENT ERRORS 

 

The transducer detects the following measurement errors: 
- exceeded processing time, downward or upward (se chapter 10, figure 

a

); 

- connected sensor or input signal other than the one set in the configuration parameters; 
- defective sensor circuit. 
 
Methods of signalization of measurement errors: 
- blinking of the 

A

 LED (when parameter 5: 

out1

=0: 

retr

 ); 

- measured value equal to -19999 or 19999 (see chapter 14, table 14.6, register address = 0). 

Содержание AR594

Страница 1: ...INSTRUCTION UNIVERSALTRANSDUCER AR594 Version 2 0 1 2016 03 01 APAR SALES OFFICE 05 090 Raszyn ul Ga czy skiego 6 Poland Tel 48 22 101 27 31 48 22 853 49 30 E mail automatyka apar pl Website www apar...

Страница 2: ...TERMINAL STRIPSAND ELECTRICAL CONNECTIONS 6 8 LOCATIONAND DESCRIPTION OF ELEMENTS OF THE FRONT PANEL 6 9 SETTING OF THE CONFIGURATION PARAMETERS 7 10 CONFIGURATION OF THEALARM OUTPUT 9 11 SIGNALING OF...

Страница 3: ...inity of and parallel to power distribution and power supply cables it is recommended to use twisted pair signal cables in the case of sensing resistors in 3 wire connections use identical wires avoid...

Страница 4: ...9 4 CONTENTS OF THE SET a transducer with a set of connections a user instruction a warranty card 5 TECHNICAL DATA 1 universal programmable input measurement range Pt100 RTD 3 or 2 wire 200 850 C Ni10...

Страница 5: ...range 0 90 C no condensation Protection rating IP20 Operating position any Weight approx 70 g Separation in out sup 1 5 kV 50 Hz 1 min Electromagnetic compatibility EMC immunity according to the PN EN...

Страница 6: ...interface with a 120 resistor termination switched on when JP1 is closed 8 LOCATIONAND DESCRIPTION OF ELEMENTS OF THE FRONT PANEL Table 8 Description of the elements of the front panel Symbol Descrip...

Страница 7: ...485 converter or the AR956 programmer restart the computer if the AR955 programmer is used instead of the AR956 programmer connect the power supply voltage to the transducer 2 Use the autonomous AR950...

Страница 8: ...1 800 C 8 tc r thermoelectric sensor thermocouple type R 40 1 600 C 9 tc t thermoelectric sensor thermocouple type T 25 350 C 10 tc E thermoelectric sensor thermocouple type E 25 740 C 11 tc n thermo...

Страница 9: ...m characteristics for the OC output is determined by parameter 5 oVt1 see chapter 9 Table 9 For oVt1 retr the OC output is connected after the measured value exceeds the range defined by parameters 8...

Страница 10: ...he lines or clamps JP1 closed see chapter 7 Equipment from different manufacturers that form the RS485 network e g RS485 converters USB may have integrated polarizing and terminating resistors in such...

Страница 11: ...mber Example 14 5 Error frame for a non existing read register address 0x01 0x84 0x02 0x0001 0x5130 Table 14 6 Map of registers for the MODBUS RTU protocol Register address HEX DEC Value HEX or DEC De...

Страница 12: ...munication with the device via the PR port AR956 or AR955 The detailed descriptions of the aforementioned applications can be found in the installation folders NOTE Before a connection is established...

Отзывы: