Transmission signaling
Red LED diode (Rx/Tx)
Alarm output
12 V, bistate type OC (open collector, NPT transistor),
current limiting resistance 440 Ω
Processing errors
(at ambient temperature of 25 °C):
- basic
- for RTD, mA, V, mV, Ω
0.1% of the measurement range ±1 digit
- for thermocouples
0.2% of the measurement range ±1 digit
- additional for thermocouples
<2 °C (temperature of cold tips)
- additional from ambient temperature changes
< 0.01% of the input range /°C
Resolution of measured temperature
programmable, 0.1 °C or 1 °C
Resolution of analog input
(programmable)
-1999 ÷ 9999 (parameters
3:
Abot
, 4:
Atop
)
Response time
(10 ÷ 90%)
135 ÷ 1500 ms (programmable with
parameter 1:
FiLt
), factory 270 ms
Power supply
(Usup)
24 VAC/DC (18÷50 VDC, 14÷35 VAC)
Power consumption
< 500 mW
Operating temperature range
0 ÷ 65 °C
Relative humidity range
0-90 °C (no condensation)
Protection rating
IP20
Operating position
any
Weight
approx. 70 g
Separation (in/out/sup)
1.5 kV, 50 Hz, 1 min.
Electromagnetic compatibility (EMC)
immunity: according to the PN-EN 61000-6-2:2002(U)
standard
emissivity: according to the PN-EN 61000-6-4:2002(U)
standard
Transmission parameters for the AR956 programmer
Factory: 2400 bit/s, address MODBUS = 1
(parameter 12:
Addr
=
1
and 13:
br
=
2
, see chapter 9)
NOTE:
Measurements performed by the transducer when supplied from the AR956 programmer are not reliable.
The AR956 programmer is intended only to supply the transducer during configuration of parameters using the
ARSoft-CFG software. During normal operation, the transducer should be supplied in the standard manner.
6. ENCLOSURE DIMENSIONS AND INSTALLATION DATA
Enclosure type
rail-mounted
Material
polycarbonate, ABS UL94V-0
Enclosure dimensions
79 x 101 x 17.5 mm
Fixing methods
on a 35 mm DIN rail
Conductor cross-
sections
2.5 mm
2
(supply, outputs),
1.5 mm
2
(inputs)
!