Table 14.2. Claim frame format for the WRITE function

 (frame length - 8 bytes):  

address of 
the device 

function  
0x06 

write register address:  

write register value 

CRC check sum 

1 byte 

1 byte 

2 bytes (HB-LB) 

2 bytes (HB-LB) 

2 bytes (LB-HB) 

Example 14.2.

 Entry in a register with address 10 (0xA) with the 0 value: 0x01 - 0x06 - 0x000A - 0x0000 - 0xA9C8 

Table 14.3. Response frame format for the READ

 function (minimum frame length - 7 bytes): 

address of 
the device 

function  
0x04 

number of bytes in the 
data field (max. 20*2=40 
bytes) 

data field - register value 

CRC check sum 

1 byte 

1 byte 

1 byte 

2 bytes (HB-LB) 

2 bytes (LB-HB) 

Example 14.3

. Response frame for register value equal to 0: 0x01 - 0x04 - 0x02 - 0x0000 - 0xB930 

Table 14.4. Response frame format for the WRITE

 function (frame length - 8 bytes):   

copy of the claim frame for the WRITE function (Table 14.2) 

Table 14.5. Special answer

 (errors:

 

function field = 0x84 or 0x83 in the case of the READ function and 0x86 in the 

case of the WRITE function, High Byte in the data field = 0): 

Error code 

(HB-LB in the data field)

 

Error description 

0x0001 

non-existing register address 

0x0002 

erroneous value of parameter to be saved 

0x0003 

improper function number 

Example 14.5.

 Error frame for a non-existing read register address: 

          0x01 - 0x84 - 0x02 - 0x0001 –0x5130 

 

Table 14.6. Map of registers for the MODBUS-RTU protocol

 

Register address  

HEX (DEC)

 

Value  

(HEX or DEC) 

Description of register and access type 

(R- read only register, R/W - read and write register) 

0x00 (0) 

-19999 ÷19999  measured value 

0x01 (1) and 0xC8 (200) 

5940 

device type identifier (AR594) 

0x02 ÷ 0x05 (2 ÷5)

 

reserved (do not use) 

0x06 ÷ 0x13 (6 ÷ 19) 

 

Reading/writing of parameter ( 

inp

filt

dot

,…) 

Register address = parameter number from Table 9 
(chapter 9) 

+ 6

 

R/W 

 
 
 

15. CONNECTING THE CONTROLLER TO A COMPUTER AND AVAILABLE SOFTWARE

 

It may be useful (or necessary) to connect the transducer to a computer in order to configure parameters, which 
also enables copying the setting to other transducers of the same type. 
As a standard, the transducers are equipped with a 

PR

 port, which enables connecting to a computer using an 

AR956 programmer. Attention should be paid to the configuration of transmission parameters in the options of 
the ARSOFT-CFG software.  
During the first startup, the (default) transmission parameters should have the following values:  
Speed = 2,400 bit/s, MODBUS address = 1. 
The following applications are available (on a CD supplied with the AR956 programmer or to be downloaded from 
the Internet at 

www.apar.pl

Download

 section, for operating systems Windows Vista/7/8/10): 

Содержание AR594

Страница 1: ...INSTRUCTION UNIVERSALTRANSDUCER AR594 Version 2 0 1 2016 03 01 APAR SALES OFFICE 05 090 Raszyn ul Ga czy skiego 6 Poland Tel 48 22 101 27 31 48 22 853 49 30 E mail automatyka apar pl Website www apar...

Страница 2: ...TERMINAL STRIPSAND ELECTRICAL CONNECTIONS 6 8 LOCATIONAND DESCRIPTION OF ELEMENTS OF THE FRONT PANEL 6 9 SETTING OF THE CONFIGURATION PARAMETERS 7 10 CONFIGURATION OF THEALARM OUTPUT 9 11 SIGNALING OF...

Страница 3: ...inity of and parallel to power distribution and power supply cables it is recommended to use twisted pair signal cables in the case of sensing resistors in 3 wire connections use identical wires avoid...

Страница 4: ...9 4 CONTENTS OF THE SET a transducer with a set of connections a user instruction a warranty card 5 TECHNICAL DATA 1 universal programmable input measurement range Pt100 RTD 3 or 2 wire 200 850 C Ni10...

Страница 5: ...range 0 90 C no condensation Protection rating IP20 Operating position any Weight approx 70 g Separation in out sup 1 5 kV 50 Hz 1 min Electromagnetic compatibility EMC immunity according to the PN EN...

Страница 6: ...interface with a 120 resistor termination switched on when JP1 is closed 8 LOCATIONAND DESCRIPTION OF ELEMENTS OF THE FRONT PANEL Table 8 Description of the elements of the front panel Symbol Descrip...

Страница 7: ...485 converter or the AR956 programmer restart the computer if the AR955 programmer is used instead of the AR956 programmer connect the power supply voltage to the transducer 2 Use the autonomous AR950...

Страница 8: ...1 800 C 8 tc r thermoelectric sensor thermocouple type R 40 1 600 C 9 tc t thermoelectric sensor thermocouple type T 25 350 C 10 tc E thermoelectric sensor thermocouple type E 25 740 C 11 tc n thermo...

Страница 9: ...m characteristics for the OC output is determined by parameter 5 oVt1 see chapter 9 Table 9 For oVt1 retr the OC output is connected after the measured value exceeds the range defined by parameters 8...

Страница 10: ...he lines or clamps JP1 closed see chapter 7 Equipment from different manufacturers that form the RS485 network e g RS485 converters USB may have integrated polarizing and terminating resistors in such...

Страница 11: ...mber Example 14 5 Error frame for a non existing read register address 0x01 0x84 0x02 0x0001 0x5130 Table 14 6 Map of registers for the MODBUS RTU protocol Register address HEX DEC Value HEX or DEC De...

Страница 12: ...munication with the device via the PR port AR956 or AR955 The detailed descriptions of the aforementioned applications can be found in the installation folders NOTE Before a connection is established...

Отзывы: