USER INSTRUCTION
UNIVERSAL TRANSDUCER
AR594
Version 2.0.1
2016.03.01
APAR - SALES OFFICE
05-090 Raszyn, ul. Gałczyńskiego 6, Poland Tel.
+48 22 101-27-31, +48 22 853-49-30
E-mail:
[email protected]
Website:
www.apar.pl
Страница 1: ...INSTRUCTION UNIVERSALTRANSDUCER AR594 Version 2 0 1 2016 03 01 APAR SALES OFFICE 05 090 Raszyn ul Ga czy skiego 6 Poland Tel 48 22 101 27 31 48 22 853 49 30 E mail automatyka apar pl Website www apar...
Страница 2: ...TERMINAL STRIPSAND ELECTRICAL CONNECTIONS 6 8 LOCATIONAND DESCRIPTION OF ELEMENTS OF THE FRONT PANEL 6 9 SETTING OF THE CONFIGURATION PARAMETERS 7 10 CONFIGURATION OF THEALARM OUTPUT 9 11 SIGNALING OF...
Страница 3: ...inity of and parallel to power distribution and power supply cables it is recommended to use twisted pair signal cables in the case of sensing resistors in 3 wire connections use identical wires avoid...
Страница 4: ...9 4 CONTENTS OF THE SET a transducer with a set of connections a user instruction a warranty card 5 TECHNICAL DATA 1 universal programmable input measurement range Pt100 RTD 3 or 2 wire 200 850 C Ni10...
Страница 5: ...range 0 90 C no condensation Protection rating IP20 Operating position any Weight approx 70 g Separation in out sup 1 5 kV 50 Hz 1 min Electromagnetic compatibility EMC immunity according to the PN EN...
Страница 6: ...interface with a 120 resistor termination switched on when JP1 is closed 8 LOCATIONAND DESCRIPTION OF ELEMENTS OF THE FRONT PANEL Table 8 Description of the elements of the front panel Symbol Descrip...
Страница 7: ...485 converter or the AR956 programmer restart the computer if the AR955 programmer is used instead of the AR956 programmer connect the power supply voltage to the transducer 2 Use the autonomous AR950...
Страница 8: ...1 800 C 8 tc r thermoelectric sensor thermocouple type R 40 1 600 C 9 tc t thermoelectric sensor thermocouple type T 25 350 C 10 tc E thermoelectric sensor thermocouple type E 25 740 C 11 tc n thermo...
Страница 9: ...m characteristics for the OC output is determined by parameter 5 oVt1 see chapter 9 Table 9 For oVt1 retr the OC output is connected after the measured value exceeds the range defined by parameters 8...
Страница 10: ...he lines or clamps JP1 closed see chapter 7 Equipment from different manufacturers that form the RS485 network e g RS485 converters USB may have integrated polarizing and terminating resistors in such...
Страница 11: ...mber Example 14 5 Error frame for a non existing read register address 0x01 0x84 0x02 0x0001 0x5130 Table 14 6 Map of registers for the MODBUS RTU protocol Register address HEX DEC Value HEX or DEC De...
Страница 12: ...munication with the device via the PR port AR956 or AR955 The detailed descriptions of the aforementioned applications can be found in the installation folders NOTE Before a connection is established...