TC5-1N5FAB   rev.06

TC5-1N5FAB

The parameter settings can be locked to prevent accidentally modifying
them.  When the settings are locked, only the temperature set point and the
Stage 1 minimum ventilation speed can be modified (as long as the tem-
perature curve and the minimum ventilation speed curve are deactivated
respectively).

To lock the parameter settings:

n

Set internal switch # 1 to 

ON

.

To unlock the parameter settings:

n

Set internal switch # 1 to 

OFF

.

L

OCKING THE PARAMETER SETTINGS

78.0

St 2

2.3

(iii)  When the user turns the adjustment knob to make an adjustment to the
stage 2 differential, the relative value reappears on the display.

In the case of the mist and heating units, the starting temperature is displayed
with the letters "

STr

" when adjusting the differential and the stopping

temperature is displayed with the letters "

STP

" when adjusting the offset.

59

TC5-1N5FAB  rev.06

TC5-1N5FAB

SOLUTION

PROBLEM

CAUSE

Stage 1  fans
run continu-
ously at full
speed.

The wiring is incor-
rect.

The ambient tempera-
ture is above the set
point.

Fix the wiring.

Adjust the set point to the
desired value.

Stage 1  fans
run errati-
cally.

The selected motor
curve is inappropri-
ate.

Select an appropriate motor
curve.

The differential is too
small.

Adjust the differential to a
higher value.

The time on or time
off is too short.

Adjust the time on or time off to
a higher value.

Time off is set to zero.

Set time off to a value other than
zero.

Stage 1 fans do
not stop
running when
the controller
is operating in
minimum
ventilation
cycle.

The wiring is incorrect.

Correct the wiring. In particular,
make sure two different lines
are connected to each motor:
line L1 modulated by the
controller  should be combined
with another line (N for 115V or
L2 for 230V) to activate the motor.
Also, be sure the stage 1
COMMON is supplied by line L1.

Humidity compensation
is activated and relative
humidity exceeds set
point.

Adjust set point or deactivate
compensation as required.

Содержание TC5-1N5FAB

Страница 1: ...REV 01 M 890 00165 rev 06 TC5 1N5FAB Combined Ventilation Controller USER SMANUAL SETTINGS FUNCTIONS...

Страница 2: ...TURE SETTINGS 15 TemperatureUnits 15 ViewingTemperatures 15 TemperatureSetPoint 18 TemperatureCurve 19 VENTILATION SETTINGS 23 CoolingOperation 23 MinimumVentilationCycle 27 HumidityCompensation 29 Mi...

Страница 3: ...oad or overvoltage we recommend installing an additional protection device on the controller s supply circuit The room temperature where the controller is located MUST ALWAYS REMAIN BETWEEN 32 F AND 1...

Страница 4: ...hange in voltage will depend on the make and capacity of the motor In order to achieve a high degree of compatibility between controller and motor the user can choose from among ten different motor cu...

Страница 5: ...t the Stage 1 minimum speed automatically over a given time period The minimum speed increases over time as the animals grow OFFSET An offset is a temperature difference from the set point that normal...

Страница 6: ...evel HEAT 1 2 OFFSET DIFF Ht 1 Oft StP Heater 1 offset stop temperature Ht 1 diF Str Heater 1 differential start temperature Ht 2 Oft StP Heater 2 offset stop temperature Ht 2 diF Str Heater 2 differe...

Страница 7: ...N HEATER 2 IS ON DEF PROBE ALARM TURNS ON WHEN AN ALARM IS DETECTED BLINKS WHEN A DEFECTIVE PROBE IS DETECTED COMPENSATION TURNS ON WHEN THE COMPENSATION ON STAGE 1 MINIMUM VENTILATION SPEED IS IN EFF...

Страница 8: ...nclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order topreventwaterfromenteringthecontroller Insertthescrewsinthemounting holesandtighten...

Страница 9: ...apacityofthemotor Thevariousmotorsavailableintheindustryhavebeen divided into ten categories and the controller has been programmed with a different motor curve for each of these categories To ensure...

Страница 10: ...ble joint to ensure a proper contact between the two cables TEMPERATURE PROBES 3 4 ON 5 63 TC5 1N5FAB rev 06 TC5 1N5FAB NOTES i These initial parameter settings will not be retained in the controller...

Страница 11: ...o 9 9 9 o F 4 0 t o 3 7 7 o C 11 TC5 1N5FAB rev 06 TC5 1N5FAB CAUTION Do not run probe cables next to other power cables When crossing over other cables cross at 90 3 Installing the Outside Probe n R...

Страница 12: ...phases as Stage 1 overload and overvoltage protection fuse F9 fast blow 12VDCforACback upsupply canactivatestages2 6ifsupplied with DC back up voltage Stage 1 Variable output 60 Hz 10A FAN 1 2 HP 115...

Страница 13: ...lay will flash in certain cases and not in others The flash ing indicates that the value shown can be adjusted A value that is not flashing can not be adjusted CHANGING THE PARAMETER SETTINGS USING TH...

Страница 14: ...rev 06 TC5 1N5FAB SOLUTION PROBLEM CAUSE Stage 1 fans run continu ously at full speed The wiring is incor rect The ambient tempera ture is above the set point Fix the wiring Adjust the set point to th...

Страница 15: ...alue Stage 1 fans are not running 15 TC5 1N5FAB rev 06 Temperatures can be displayed in either Celsius or Fahrenheit units n Set internal switch 2 to the desired position ON to display temperatures in...

Страница 16: ...ature flashes on the display alternating with the letters Lo n Turn the adjustment knob clockwise one notch further The maximum temperature flashes on the display alternating with the letters Hi 57 TC...

Страница 17: ...knob to the ROOM TEMPERATURE position The current room temperature is displayed n Press and hold the push button for 5 seconds NOTE If no user activity is recorded after 5 minutes in test mode the co...

Страница 18: ...temperaturesetpointcanbeadjustedonlyifthetemperature curve is deactivated see following section 55 TC5 1N5FAB rev 06 TC5 1N5FAB n Use the adjustment knob to set the low alarm offset to the desired val...

Страница 19: ...range from 0 5o F to 40o F The critical temperature ranges from 40 0 F to 120 0 F 40 0 C to 48 9 C n Set the selection knob to ALARM OFFSETS CRITI CAL The current low alarm offset flashes on the displ...

Страница 20: ...nce the six points of the curve have been specified activate the curve as explainedbelow NOTE Make sure the temperature curve is deactivated before specifying new points see below 53 TC5 1N5FAB rev 06...

Страница 21: ...fferential to the desired value n Press the push button The current heating offset for Heater 2 is dis played alternating with the letters OFT n Use the adjustment knob to adjust the offset to the des...

Страница 22: ...SET POINT To CURVE The current tem perature set point is displayed n Press the push button to display the points of the curve actually de fined until the word ON appears fourteen clicks n Turn the adj...

Страница 23: ...SED MINIMUM HEAT ate the fans according to the probes of the zone with the highest tempera ture whenever the temperature difference between zones is greater than a user defined value 23 TC5 1N5FAB rev...

Страница 24: ...am above The heater 1 and 2 offsets can be adjusted between 10o F and 20 0o F 5 6o C and 11 1o C If the heater offset is negative the heating units will turn off at temperatures above the set point n...

Страница 25: ...N5FAB When room temperature Set Point stage 1 fans run at minimum speed according to the minimum ventilation cycle At Set Point stage 1 fans stop operating according to the minimum ventilation cycle a...

Страница 26: ...ting times as a function of outside temperature see above It can be adjusted between 40 0 F and 99 9 F 40 0 C and 37 7 C n Set the selection knob to OUTSIDE T SETTINGS The current outside tempera ture...

Страница 27: ...Temperature Temperature Outside Set Point Compensation Interval Current Outside Temperature Note that when the compensated TIME OFF value is less than 10 seconds it is set to zero 27 TC5 1N5FAB rev 0...

Страница 28: ...1 flashes on the display alternating with the letters Off n Use the adjustment knob to adjust time off to the desired value 45 TC5 1N5FAB rev 06 TC5 1N5FAB 1 Adjusting the Curtain Dead Band Thedeadban...

Страница 29: ...mal operations this applies only to users with a PF 5 controller connected to the TC5 1N5FAB 29 TC5 1N5FAB rev 06 TC5 1N5FAB This feature also applies when the minimum ventilation speed is activated N...

Страница 30: ...sate for the increase in humidity Note that the humidity compensation feature must be activated for this to work n Set the selection knob to STAGE 1 HUMIDITY CONTROL The current humidity reading is di...

Страница 31: ...the push button four times The current turn off level is dis played alternating with the letters StP and rh n Use the adjustment knob to set the turn off level to the desired value 31 TC5 1N5FAB rev...

Страница 32: ...urve is deactivated The controller maintains the minimum speed specified for this point until the curve is reactivated or until a new single minimum speed is specified using the first method MINIMUM V...

Страница 33: ...e temperature curve is already activated All points of the minimum speed curve other than the first one are automatically given day numbers identical to those specified for the tem perature curve Only...

Страница 34: ...and the temperature at which the stage 3 fans returns to a stop The Stage 3 Offset can be adjusted between 0 F and 20 F 0 C and 11 1 C n Set the selection knob to STAGE 2 3 The current differential f...

Страница 35: ...o the desired value DIFFERENTIAL SETTINGS 35 TC5 1N5FAB rev 06 TC5 1N5FAB 1 Specifying Minimum Speed Curve n Set the selection knob to STAGE 1 MINIMUM SPEED CURVE The current minimum speed flashes on...

Страница 36: ...ctions apply to reduce the risk of errors decreasing minimum speeds are not allowed the minimum speed variation cannot exceed 10 per day 37 TC5 1N5FAB rev 06 TC5 1N5FAB 3 Viewing Current Minimum Speed...

Страница 37: ...ctions apply to reduce the risk of errors decreasing minimum speeds are not allowed the minimum speed variation cannot exceed 10 per day 37 TC5 1N5FAB rev 06 TC5 1N5FAB 3 Viewing Current Minimum Speed...

Страница 38: ...o the desired value DIFFERENTIAL SETTINGS 35 TC5 1N5FAB rev 06 TC5 1N5FAB 1 Specifying Minimum Speed Curve n Set the selection knob to STAGE 1 MINIMUM SPEED CURVE The current minimum speed flashes on...

Страница 39: ...and the temperature at which the stage 3 fans returns to a stop The Stage 3 Offset can be adjusted between 0 F and 20 F 0 C and 11 1 C n Set the selection knob to STAGE 2 3 The current differential f...

Страница 40: ...e temperature curve is already activated All points of the minimum speed curve other than the first one are automatically given day numbers identical to those specified for the tem perature curve Only...

Страница 41: ...urve is deactivated The controller maintains the minimum speed specified for this point until the curve is reactivated or until a new single minimum speed is specified using the first method MINIMUM V...

Страница 42: ...the push button four times The current turn off level is dis played alternating with the letters StP and rh n Use the adjustment knob to set the turn off level to the desired value 31 TC5 1N5FAB rev...

Страница 43: ...sate for the increase in humidity Note that the humidity compensation feature must be activated for this to work n Set the selection knob to STAGE 1 HUMIDITY CONTROL The current humidity reading is di...

Страница 44: ...mal operations this applies only to users with a PF 5 controller connected to the TC5 1N5FAB 29 TC5 1N5FAB rev 06 TC5 1N5FAB This feature also applies when the minimum ventilation speed is activated N...

Страница 45: ...1 flashes on the display alternating with the letters Off n Use the adjustment knob to adjust time off to the desired value 45 TC5 1N5FAB rev 06 TC5 1N5FAB 1 Adjusting the Curtain Dead Band Thedeadban...

Страница 46: ...Temperature Temperature Outside Set Point Compensation Interval Current Outside Temperature Note that when the compensated TIME OFF value is less than 10 seconds it is set to zero 27 TC5 1N5FAB rev 0...

Страница 47: ...ting times as a function of outside temperature see above It can be adjusted between 40 0 F and 99 9 F 40 0 C and 37 7 C n Set the selection knob to OUTSIDE T SETTINGS The current outside tempera ture...

Страница 48: ...N5FAB When room temperature Set Point stage 1 fans run at minimum speed according to the minimum ventilation cycle At Set Point stage 1 fans stop operating according to the minimum ventilation cycle a...

Страница 49: ...am above The heater 1 and 2 offsets can be adjusted between 10o F and 20 0o F 5 6o C and 11 1o C If the heater offset is negative the heating units will turn off at temperatures above the set point n...

Страница 50: ...SED MINIMUM HEAT ate the fans according to the probes of the zone with the highest tempera ture whenever the temperature difference between zones is greater than a user defined value 23 TC5 1N5FAB rev...

Страница 51: ...SET POINT To CURVE The current tem perature set point is displayed n Press the push button to display the points of the curve actually de fined until the word ON appears fourteen clicks n Turn the adj...

Страница 52: ...fferential to the desired value n Press the push button The current heating offset for Heater 2 is dis played alternating with the letters OFT n Use the adjustment knob to adjust the offset to the des...

Страница 53: ...nce the six points of the curve have been specified activate the curve as explainedbelow NOTE Make sure the temperature curve is deactivated before specifying new points see below 53 TC5 1N5FAB rev 06...

Страница 54: ...range from 0 5o F to 40o F The critical temperature ranges from 40 0 F to 120 0 F 40 0 C to 48 9 C n Set the selection knob to ALARM OFFSETS CRITI CAL The current low alarm offset flashes on the displ...

Страница 55: ...temperaturesetpointcanbeadjustedonlyifthetemperature curve is deactivated see following section 55 TC5 1N5FAB rev 06 TC5 1N5FAB n Use the adjustment knob to set the low alarm offset to the desired val...

Страница 56: ...knob to the ROOM TEMPERATURE position The current room temperature is displayed n Press and hold the push button for 5 seconds NOTE If no user activity is recorded after 5 minutes in test mode the co...

Страница 57: ...ature flashes on the display alternating with the letters Lo n Turn the adjustment knob clockwise one notch further The maximum temperature flashes on the display alternating with the letters Hi 57 TC...

Страница 58: ...alue Stage 1 fans are not running 15 TC5 1N5FAB rev 06 Temperatures can be displayed in either Celsius or Fahrenheit units n Set internal switch 2 to the desired position ON to display temperatures in...

Страница 59: ...rev 06 TC5 1N5FAB SOLUTION PROBLEM CAUSE Stage 1 fans run continu ously at full speed The wiring is incor rect The ambient tempera ture is above the set point Fix the wiring Adjust the set point to th...

Страница 60: ...lay will flash in certain cases and not in others The flash ing indicates that the value shown can be adjusted A value that is not flashing can not be adjusted CHANGING THE PARAMETER SETTINGS USING TH...

Страница 61: ...phases as Stage 1 overload and overvoltage protection fuse F9 fast blow 12VDCforACback upsupply canactivatestages2 6ifsupplied with DC back up voltage Stage 1 Variable output 60 Hz 10A FAN 1 2 HP 115...

Страница 62: ...o 9 9 9 o F 4 0 t o 3 7 7 o C 11 TC5 1N5FAB rev 06 TC5 1N5FAB CAUTION Do not run probe cables next to other power cables When crossing over other cables cross at 90 3 Installing the Outside Probe n R...

Страница 63: ...ble joint to ensure a proper contact between the two cables TEMPERATURE PROBES 3 4 ON 5 63 TC5 1N5FAB rev 06 TC5 1N5FAB NOTES i These initial parameter settings will not be retained in the controller...

Страница 64: ...apacityofthemotor Thevariousmotorsavailableintheindustryhavebeen divided into ten categories and the controller has been programmed with a different motor curve for each of these categories To ensure...

Страница 65: ...nclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order topreventwaterfromenteringthecontroller Insertthescrewsinthemounting holesandtighten...

Страница 66: ...N HEATER 2 IS ON DEF PROBE ALARM TURNS ON WHEN AN ALARM IS DETECTED BLINKS WHEN A DEFECTIVE PROBE IS DETECTED COMPENSATION TURNS ON WHEN THE COMPENSATION ON STAGE 1 MINIMUM VENTILATION SPEED IS IN EFF...

Страница 67: ...evel HEAT 1 2 OFFSET DIFF Ht 1 Oft StP Heater 1 offset stop temperature Ht 1 diF Str Heater 1 differential start temperature Ht 2 Oft StP Heater 2 offset stop temperature Ht 2 diF Str Heater 2 differe...

Страница 68: ...t the Stage 1 minimum speed automatically over a given time period The minimum speed increases over time as the animals grow OFFSET An offset is a temperature difference from the set point that normal...

Страница 69: ...hange in voltage will depend on the make and capacity of the motor In order to achieve a high degree of compatibility between controller and motor the user can choose from among ten different motor cu...

Страница 70: ...TURE SETTINGS 15 TemperatureUnits 15 ViewingTemperatures 15 TemperatureSetPoint 18 TemperatureCurve 19 VENTILATION SETTINGS 23 CoolingOperation 23 MinimumVentilationCycle 27 HumidityCompensation 29 Mi...

Страница 71: ...oad or overvoltage we recommend installing an additional protection device on the controller s supply circuit The room temperature where the controller is located MUST ALWAYS REMAIN BETWEEN 32 F AND 1...

Страница 72: ...REV 01 M 890 00165 rev 06 TC5 1N5FAB Combined Ventilation Controller USER SMANUAL SETTINGS FUNCTIONS...

Отзывы: