-BL2LN87SB02D*CC20  16/20-

LINK does not flash

Remedy

Check the connection of this unit.

Check conditions of the master unit 

and slave unit.

Disconnect this unit once, and then reconnect it.

[Troubleshooting]

Things to be checked

Remedy

Things to be checked

Remedy

Things to be checked

Remedy

Things to be checked

Remedy

Things to be checked

1)  If LINK on the master unit is flashing and LINK on the slave unit is lit, it is possible that the master 

unit has a fault or power supply (24V-0V) is directly connected to the DP-DN pins of the slave unit.

*

 If LINK is lit while ALM is flashing, it means a failure in single unit simplified replacement. 

2)  If LINK on the master unit is flashing and LINK on the slave unit is unlit, it is possible that the power 

(24V DC) is not supplied to the master unit, there is a disconnection on the transmission line (DP, 
DN), or the slave unit has been damaged. 

3)  If LINK on the master unit is not flashing, check the power supply to the master unit. Also, since there 

is a possibility that some system error has occurred, refer to the user’s manual of the master unit.

4)  A slave unit incompatible with Ver.1.1 cannot be used in connection to the AnyWireASLINK system 

for word transmission. Check the setting of the master unit, and lot No. of the slave unit. 

ALM is lit

ALM is flashing

LINK and ALM flashes alternately

LINK is lit and ALM is flashing: Model mismatching error (Failure in single unit simplified replacement)

Check the connection of I/O terminals 

on the slave unit.

When IN flashes in synchronization with LINK while ALM is lit, the unit has I/O disconnection.
If only ALM is lit, the unit has I/O short-circuit or I/O voltage drop.
Check information by reading the status detail area

*

.

1)  Make sure that the slave unit I/O line and load are normally connected. Use caution about 

disconnection of the wiring and insufficient screw tightening.

2)  To connect a mechanical contact (relay, switch, etc.) as load, OFF signal cannot be differentiated 

from disconnection. In this case, set the equipment parameter for the disconnection detecting 
function to OFF.

3)  Check wiring of the slave unit terminals to ensure that the connected load meets the power supply 

and output specifications of ASLINKER, and adjust it as required. 

4)  Adjust the power supply voltage of an external power source connected to the slave unit I/O line, so 

that the power supply voltage does not exceed the rated voltage range (21.6V to 27.6V). Make sure 
that wires of the transmission line do not touch each other. Check for incorrect wiring of the terminals.

*

 Refer to the manual for the master unit. 

Adjust the voltage of external power supply to the master unit so that it will be in the range from 21.6 to 
27.6V. (Recommended voltage is 26.4V.) Check the total length.
Review the total length and wire diameter of transmission line so that the load will not exceed the current 
limit supplied by the transmission line and adjust the connected load. (In the case of the wire size of 
1.25mm

2

 and total length of 50m or less, the current supplied by the transmission line is 2A.)

*

 If ALM is flashing while LINK is lit, it means a failure in single unit simplified replacement. 

Check if the replacement slave unit is of the same type as that of the slave unit before the replacement.

Check if the function version for the replacement slave unit is older than that of the slave unit before the 
replacement.

*

 If the function version of the replacement slave unit is older, the single unit simplified replacement function does not 

work.

The address of the slave unit is either unregistered or duplicated.
Take the following actions. 

*

 The slave unit cannot be used with the factory-set address.

1)  Set a bit address correctly in a range of 0 to 254.
2)  Check if there is a slave unit on which the indicator lamps are flashing in the same manner and reset 

the addresses so that they are not duplicated.

Check the address of the slave unit.

Check the address of the slave unit.

Check the model of the slave unit.

Check the lot No. of the slave unit.

Check the connection of the slave 

unit.

Check the voltage (24V DC) of 

external power supply to the master 

unit.

Check if the address of the replacement slave unit is the same as the address before shipment (a bit 
address of 511).

*

 If the address of the replacement slave unit is not the same as the address before shipment, the single unit simplified 

replacement function does not work.

Defective connections and the like may have caused single unit simplified replacement to fail.
Remove the slave unit after replacement, and make connections again.

*

 When two or more replacement slave units are simultaneously connected, the single unit simplified replacement 

function does not work.

Содержание ASLINKER BL2LN87SB-02D CC20 Series

Страница 1: ...operty damage Note on use A separate Address Writer is required to set addresses and other data For more information refer to Various Settings on page 9 NPN input PNP input CAUTION WARNING System powe...

Страница 2: ...t Lot No About Word Transmission 3 Some products have no indication of function version Year Numbers Lower two digits of the Christian era Month Alphabet as per the table below 19E means May 2019 Sing...

Страница 3: ...ified replacement function see the lot No and the manual for the slave unit When a slave unit of a new function version is replaced with that of an old function version the single unit simplified repl...

Страница 4: ...onditions are satisfied Functions Bit transmission ASLINKER 4 wire isolated cable type General purpose sensors General purpose switches Word 1 2 transmission Single unit simplified replacement 3 Remot...

Страница 5: ...a four wire isolated terminal in the case of input and load driving using an external power supply How to Connect AnyWireASLINK AnyWireASLINK terminator One terminator should be connected to the DP DN...

Страница 6: ...r lines start running in parallel This will improve noise resistance suppress the adverse effects of crosstalk caused by transmitted signals and stabilize signals The above filters must be inserted re...

Страница 7: ...total length of the section where all the DP DN 24V and 0V lines run in parallel is more than 50m 24V DC stabilized power supply General purpose power supply filter Use it if necessary 2 wire termina...

Страница 8: ...tings are enabled or not Operation during restoration Power supply line disconnection error will be automatically reset by eliminating the cause of disconnection Signal line disconnection error will b...

Страница 9: ...reen Input indicator Orange Input indicator Orange Alarm indicator Red Name of Each Part Input line connection wires Pin No Wire color Applicable LP connector LP4 WW 10P Example of fitting the LP conn...

Страница 10: ...ction may be caused depending on the sensor to be connected If that happens change the setting as follows Example 1 Signal line disconnection occurs all the time Set to Monitoring enabled for power su...

Страница 11: ...n 3 subsequent to corresponding input signal address setting Example When this unit is set to address 4 Variable Address Description CH0 input CH1 input Bit input information area of master unit CH1...

Страница 12: ...voltage drop When ALM bit is normal ON mode When this unit is disconnected from the trunk line of the AnyWireASLINK system at occurrence of DP DN disconnection input signals and ALM bits are all turne...

Страница 13: ...ng equipment parameter 12 is manual restoration After execution of the short circuit notification cancel command set this parameter to OFF Otherwise operation of the short circuit notification cancel...

Страница 14: ...ion Bit input information area Number of bit input points 2 n 1 Number of bit input points 2 n Example When the number of bit transmission points for the master unit is input 64 points output 64 point...

Страница 15: ...rmally connected and the unit is set to the factory set address For S W version A or 3 digit lot No This condition is detected when the master unit executes automatic address recognition LINK Green AL...

Страница 16: ...djust the power supply voltage of an external power source connected to the slave unit I O line so that the power supply voltage does not exceed the rated voltage range 21 6V to 27 6V Make sure that w...

Страница 17: ...t ON voltage OFF voltage Allowable current at 24VL 24V DC 3 5mA 2 2mA or more 1mA or less 16V or more 24VL IN 8V or less 24VL IN 50mA max 24VL 0VL per point Internal circuit 4 wire isolated NPN input...

Страница 18: ...ear short circuit status after short circuit is detected Notification by differentiating disconnected CH When ALM bit is normal OFF Notification by differentiating disconnected CH When ALM bit is norm...

Страница 19: ...ransmission line disconnection transmission line short circuit transmission power supply drop and duplicated unregistered ID Transmission specifications 1 Do not use or store AnyWireASLINK devices in...

Страница 20: ...8 2019 2020 UMA 16324AK EN BL2LN87SB02D CC20 20 20 Anywire Corporation Headquarters 1 Babazusho Nagaokakyo shi Kyoto 617 8550 JAPAN Contact by mail Contact info_e anywire jp Contact by website http ww...

Отзывы: