-L*A1AW 3/12-
[Notes on Combined Use with Four-Wire (Isolated) Terminals]
Insert the "ASLINK filter [Type ANF-01]" regardless of installation
method and distance when complying with CE Standard.
If any of the side-by-side lines of DP, DN, 24V, or 0V exceeds the total length of
50m in a power supply system to be supplied, serially connect the "ASLINK filter
[Type ANF-01]" or "filter of COSEL Co., Ltd. [Type EAC-06-472]" to 24V and 0V in
the starting position of the side-by-side lines.
This will improve noise resistance, reduce the impact of crosstalk by transmission
signals, and stabilize the signals.
Insert a filter whether using a master power supply for the entire system or using a
local power supply.
ASLINK filter
ANF-01
MAX 5A/24V DC
Filter of COSEL Co., Ltd.
EAC-06-472
MAX 6A/24V DC
Model
Type
Allowable power current
■
Filter allowable power current
■
AnyWire Type: ANF-01 Connection example
①
Power supply to the entire system
DP
DN
24V
0V
POWER IN
SLAVE
LG
24V
0V
L N FG
~
DP
DN
DP
DN
24V
0V
DP
DN
BT0
ANF-01
24V DC
stabilized
power supply
Two-wire
terminal
Four-wire
terminal
24V
0V
24V
0V
PE
AnyWireASLINK master
General-purpose
power supply filter
(Use if necessary)
If any of the side-by-side lines
of DP, DN, 24V, or 0V exceeds
the total length of 50m
②
Local power supply/branching
POWER IN
SLAVE
DP
DN
24V
0V
LG
24V
0V
L N FG
~
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
BT0
ANF-01
24V DC
stabilized
power
supply
Two-wire
terminal
DP
DN
Two-wire
terminal
DP
DN
Two-wire
terminal
Four-wire
terminal
DP
DN
24V
0V
Four-wire
terminal
Four-wire
terminal
DP
DN
24V
0V
Four-wire
terminal
DP
DN
24V
0V
Four-wire
terminal
24V
0V
24V
0V
PE
AnyWireASLINK master
24V
0V
L
N
FG
~
24V DC
stabilized
power supply
ANF-01
24V
0V
24V
0V
PE
DP
DN
24V
0V
Four-wire
terminal
DP
DN
24V
0V
Four-wire
terminal
A
B
ANF-01
For details of ANF-01,
refer to ANF-01 Products Guide.
24V
0V
24V
0V
PE
■
Filter notation in the drawing
General-purpose
power supply filter
(Use if necessary)
General-purpose
power supply filter
(Use if necessary)
POWER IN
SLAVE
POWER IN
SLAVE
If (A+B) of the side-by-side
lines of DP, DN, 24V, or 0V
exceeds the total length of 50m
If any of the side-by-side lines
of DP, DN, 24V, or 0V exceeds
the total length of 50m