![Anybus CompactCom 30 Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/anybus/compactcom-30/compactcom-30_network-manual_2948755027.webp)
Anybus Module Objects
25 (36)
Instance Attributes (Instance #2, Baud Rate)
Basic
#
Name
Access
Data Type
Description
1
Name
Get
Array of
CHAR
“Baud Rate”
2
Data type
Get
UINT8
08h (= ENUM)
3
Number of elements
Get
UINT8
01h (one element)
4
Descriptor
Get
UINT8
07h (read/write/shared access)
5
Value
Get/Set
ENUM
Value:
ENUM string:
0:
“10 kbps”
1:
“20 kbps”
2:
“50 kbps”
3:
“reserved” (Firmware versions 3.xxx)
“100 kbps” (Firmware versions previous to 3.0)
4:
“125 kbps”
5:
“250 kbps”
6:
“500 kbps”
7:
“800 kbps”
8:
“1 Mbps”
9:
“Auto”
10:
“LSS” (default)
(Note that this value may be updated by the LSS service, see
Layer Setting Services (LSS), p. 13
)
Command Details: Reset
Details
Command Code:
05h
Valid for:
Object
Description
Resets Baud Rate and Device Address values to default
•
Command Details
Field
Comments
CmdExt[0]
(reserved)
CmdExt[1]
01h = Factory Default Reset
Anybus
®
CompactCom
™
30 Network Guide
HMSI-168-78 EN 4.1