Antriebstechnik GmbH
Technical Documentation EC863 and ECE3AP-00-01
Page 14 of 18
(02/99) R0047GB.DOC
tH
Run-up time of the set value integrator
tR
Reverse running time of the set value integrator
Setting the set value slope
Specify set value jump (0
→
10 V) at the set value input and set the
desired speed slope with trimmer „tH„ and/or „tR„.
Setting range:
100 ms ... 2 s
Works setting:
2 s
internal
Set value
10V
100ms
Signal after set value jump
tH
tR
2s
0V
t
100ms
2s
PI
Setting of the speed control behaviour. When necessary adjust to
the respective application. Clockwise rotation increases the
proportional amplification.
Incorrectly set control behaviour leads to vibrations of the drive
which can destroy the motor or other components connected
downstream (gears etc.).
The manufacturer is not liable for damages which are caused by
incorrect parametrisation.
Works setting
Middle
n1, n2
Fixed speeds n1 and n2. This function can be selected with the plug
bridge STB3 „set value source„ (see chapter 0).
Works setting:
n1 = 4538 r.p.m.
n2 = 1396 r.p.m