16
AIR MAGNA 200
GREEN ENERGY SYSTEMS
Adjustment of the defrosting
1-Press on “ “ or ” “ for 3 seconds , you can see (for example)
The first number is the symbol of the item; and the second value is the setting value of the current
item.
Press the button “ ” or “ ” for increasing or decreasing the value.
2-Press on “ “ or ” “ again to enter next item, just like:
The content of each item :
Number 0 stand for << Flow switch detection >>: (0,1) adjustable ( invalidation in this system )
Number 1 stand for <<Defrost starts temperature>>: (-30°C to 0°C) adjustable Number 2 stand
for <<Defrost stops temperature>>: (0°C to 30°C) adjustable Number 3 stand for <<Interval of de-
frost>>: (30 min to 90 min) adjustable Number 4 stand for <<Time of defrost>>: (1 min to 20 min)
adjustable
Number 5 stand for <<The time of water temperature up 1 °C >>: (1 min to 10 min) adjustable
Number 6 stand for <<The minimum temperature difference of compressor star>>:
3 ° C to 15°C) adjustable
3-After setting the value, the defrosting setting will exit automatically after several seconds.
And the system will memorize the last value of each setting.
Temperature Display
You can check the correlative temperature by following step:
1-Press on “ ” for 4 seconds , you can see (for example)
The first letter is the symbol of the item; and the second value is the temperature of the current item.
2-Press on “ ” again to enter next item.
A stand for << Temperature of the water>>
B stand for <<Temperature of the ambient>>
C stand for <<Coil temperature in outdoor heat exchanger>>
D stand for <<Exhaust temperature from compressor>>
Reset button
when press the button “ “ for 4 seconds, and the following points will return to initial state
(Windows default):
0. Flow switch detection: 0
1. Enter defrost temperature: -7°C
2. Exit defrost temperature: 10°C
3. Defrost interval: 45 minutes
4. Defrost time: 8 minutes
5. The time of water temperature up 1°C : 3 minutes
6. The minimum temperature difference of compressor star : 5°C
1 . -7
2 . 10
A . 45