3-3 Electric connections
CAUTION: before connecting the appliance, make sure that the supply power line in
disconnected from the network.
Characteristies of the general power supply:
•
mode of neutral TT and TN.S; the circuit of heat pump must be connected to an earthing circuit
Connections:
•
The electric Installation must be carried out by a professional qualified (like an electrician)
according to the rules und standards in force in the country of installation.
•
The power supply of the heat pump must come preferably from an exclusive circuit und having
the bodies of lawful protection.
•
Controller must be installed or indoor wall and the plane is easy for use.
Electric protection of which must lay out the heat pump:
•
circuit breaker curves D or standard fuse of protection Am, gauged with 16A
•
differential protection of 30 mA
In the event of connection to an electrical plug by the user:
•
The heat pump is being provided with an electric cable, set possible to connect it with a plug.
•
The plug must be checked in conformity with the power of the appliance by a qualified
technician.
•
The plug must be safe from the rain, of easy access to be cleaned and one will have to regularly
check the good condition of this plug.
BEFORE THE STARTUP OF HEAT PUMP, IT IS SIGNIFICANT TO
INCLUDE/UNDERSTAND THE OPERATING AND THE SETTINGS OF WHICH YOU WILL
TAKE NOTE IN THE FOLLOWING PARAGRAPHS