Ansul AUTOMAN II-C Скачать руководство пользователя страница 9

MAINTENANCE

UL R5998      6-16-95      Page 7

MAINTENANCE

The ANSUL AUTOMAN II-C release is a mechanical device.
It requires periodic care. Maintenance, to provide maximum
assurance that your release will operate effectively and safe-
ly, should be conducted at regular intervals, not more than
six-months apart, or when specifically indicated by an
inspection.

1. Remove ring pin from STRIKE button and open enclo-

sure.

2. Insert ring pin as shown in Figure 9.

3. Remove cartridge and install safety shipping cap.

4. Perform steps 2 through 4 in the “TEST OF WIRING”

section on page 5.

5. Perform steps 1 through 11 in the “TEST ACTUATION

OF FIRE SUPPRESSION SYSTEM” section on page 5.

6. Perform the “SOLENOID CHECKOUT PROCEDURE”

on page 6.

7. After all fire suppression system maintenance proce-

dures have been completed, place the system back into
service by following steps 1 through 4 in the “ARMING
THE SYSTEM” section on page 6.

8. Record date of maintenance examination.

Содержание AUTOMAN II-C

Страница 1: ...INSTALLATION ANSUL OPERATION AND AUTOMAN II C MAINTENANCE RELEASING MANUAL DEVICE ANSUL 001799...

Страница 2: ...icular interest depending upon one s responsibility ANSUL AUTOMAN II C is an electrical mechanical device It requires periodic care Maintenance to provide maximum assurance that your releasing device...

Страница 3: ...remote manual cable pull station ANSUL AUTOMAN II C RELEASING DEVICE FIGURE 1 004300 1 VISUAL INDICATOR WINDOW 2 WIRING INSTRUCTIONS 3 RELEASE MECHANISM 4 RESET LEVER 5 STRIKE BUTTON 6 ELECTRIC SWITC...

Страница 4: ...tion Operation and Maintenance Manual pro vided with the Ansul Fire Suppression System for the maximum allowable length of actuation line piping INSTALLATION INSTRUCTIONS UL R5998 6 16 95 Page 2 TO EX...

Страница 5: ...secure 1 2 in 13 mm rigid conduit from ANSUL AUTOMAN II C release assembly to pull station using pulley elbows Part No 45771 for changes in direction Do not use more than 8 pulley elbows between the r...

Страница 6: ...d install jumper J2 across terminals 4 and 5 Terminals 1 through 3 are provided for auxiliary device con nections Auxiliary equipment is controlled through the action of switch S1 Refer to the followi...

Страница 7: ...the Installation Operation and Maintenance Manual s furnished with the Ansul Fire Suppression System and disarm remove the agent tank assembly actuation mechanism before test firing 2 Check ANSUL AUTO...

Страница 8: ...and replace if cartridge weight is 1 4 oz 7 1 g or more below weight stamped on car tridge Install fully charged cartridge and hand tighten Refer to the Installation Operation and Maintenance Manual p...

Страница 9: ...TRIKE button and open enclo sure 2 Insert ring pin as shown in Figure 9 3 Remove cartridge and install safety shipping cap 4 Perform steps 2 through 4 in the TEST OF WIRING section on page 5 5 Perform...

Страница 10: ......

Страница 11: ......

Страница 12: ...Part No 17788 09 1995 Ansul Incorporated Litho in U S A ANSUL INCORPORATED ONE STANTON STREET MARINETTE WI 54143 2542...

Отзывы: