REMOTE MANUAL PULL STATION INSTALLATION
(CABLE TYPE) (Continued)

FIGURE 6

001800

WIRING THE “ANSUL AUTOMAN” II-C RELEASE

The ANSUL AUTOMAN II-C is designed for use with the sep-
arately listed or approved fire detection and releasing control
unit which will initiate the electrical signal to operate the
release. Accordingly, conduit and wiring connections
between the release and the detection/alarm control system
should be made by or under the supervision of the detec-
tion/control system manufacturer’s technician.

Installation of Wiring

A terminal strip is provided inside the ANSUL AUTOMAN
II-C enclosure for making field terminations. It is to be con-
nected to a nominal 12 VDC or 24 VDC releasing circuit. The
activation current is 450 mA at 12 VDC or 750 mA at 24 VDC
for approximately 55 milliseconds. The wiring diagram shown
in Figure 7 provides the details for making the field wiring
connections.

All interconnecting wiring to the solenoid is to be a minimum
of 18 AWG. All wiring should be done in accordance with the
National Electric Code and/or local codes and standards.

The circuit connections from the output of the Releasing
Control Unit are made to Terminals 4 and 8 of the ANSUL
AUTOMAN II-C release. The release is shipped with a
jumper (J2) installed across Terminals 4 and 5. If the releas-

ing control unit that is to be connected to the release requires
an in-line supervisory device to maintain proper circuit super-
vision, jumper J2 should be removed and the appropriate in-

line supervisory device installed in its place. Refer to the
installation instructions from the manufacturer of the releas-
ing control unit for polarity requirements when installing an
in-line supervisory device.

Install the in-line supervisory device (SDx in Figure 7) across
terminals 4 and 5. Refer to the releasing control unit installa-
tion instructions for supervisory device requirements. If an in-
line supervisory device is not required, install jumper J2
across terminals 4 and 5.

Terminals 1 through 3 are provided for auxiliary device con-
nections. Auxiliary equipment is controlled through the action
of switch S1. Refer to the following ELECTRICAL DATA
SECTION for the contact ratings of S1.
Replace the protective cover over the terminal strip upon
completion of field wiring. Test the system by following the
procedures on the following pages.

ELECTRICAL DATA

Input Current: 750 mA at 24 VDC for 50 milliseconds

450 mA at 12 VDC for 50 milliseconds

Input Voltage: 12.5 – 30 VDC

Polarization:

Polarization will result only by installation of
a polarized in-line supervisory device (SDx).
Observe polarity when connected to a
release circuit; terminal 4 positive, terminal 8
negative.

Contact Ratings: S1 and S2 contact ratings are 15A, 1/3

HP, 125 or 250 VAC resistive; 1/2A, 125
VDC; 1/4A, 250 VDC; 5A, 120 VAC
inductive

SOL1 Coil Resistance: 28 ohms ± 10% at 77 °F (25 °C)

Operating Sequence

With solenoid cut-off switch (S2), in the normal position (the
release reset lever in the armed position), an electrical circuit
is formed between terminals 4 and 8. As the supervisory
release circuit of the control unit is activated, power is
applied between terminals 4 and 8 of TB1 causing solenoid
SOL1 to operate the ANSUL AUTOMAN II-C release. As the
release operates, S1 and S2 will change positions with S2
cutting power to the solenoid, which opens the release cir-
cuit. S1, being a condition switch, provides an isolated set of
form “C” contacts for auxiliary functions at terminals 1, 2 and
3 of TB1.

FIGURE 7

004302

INSTALLATION INSTRUCTIONS
UL R5998      6-16-95      Page 4

CAUTION

!

Do not install cartridge until all testing has been completed
and the system is ready to be armed as instructed on the
following pages.

1/2 IN.
(13 mm)

SEE
DETAIL “A”

DETAIL “A”

THESE SWITCH CONTACTS
TRANSFER UPON ACTUATION
OF RELEASE

“ANSUL AUTOMAN” II-C

VOLTAGE TRANSIENT SUPPRESSOR

OR

IN-LINE
SUPERVISORY
DEVICE

UL LISTED
SUPERVISED
RELEASING
CONTROL
UNIT

TB1

J1

TZ1

J2

S1

(+)

(+)

(–)

(–)

S2

SDx

SOL1

NC

NC

ACCESSORY
POWER
SOURCE

*

AUXILIARY ALARMING DEVICES, SEE S1 RATINGS

** FUEL SHUT-OFF VALVE, BLOWER MOTOR, DOOR CLOSER, ETC., SEE S1 RATINGS

HIGH

LOW

Содержание AUTOMAN II-C

Страница 1: ...INSTALLATION ANSUL OPERATION AND AUTOMAN II C MAINTENANCE RELEASING MANUAL DEVICE ANSUL 001799...

Страница 2: ...icular interest depending upon one s responsibility ANSUL AUTOMAN II C is an electrical mechanical device It requires periodic care Maintenance to provide maximum assurance that your releasing device...

Страница 3: ...remote manual cable pull station ANSUL AUTOMAN II C RELEASING DEVICE FIGURE 1 004300 1 VISUAL INDICATOR WINDOW 2 WIRING INSTRUCTIONS 3 RELEASE MECHANISM 4 RESET LEVER 5 STRIKE BUTTON 6 ELECTRIC SWITC...

Страница 4: ...tion Operation and Maintenance Manual pro vided with the Ansul Fire Suppression System for the maximum allowable length of actuation line piping INSTALLATION INSTRUCTIONS UL R5998 6 16 95 Page 2 TO EX...

Страница 5: ...secure 1 2 in 13 mm rigid conduit from ANSUL AUTOMAN II C release assembly to pull station using pulley elbows Part No 45771 for changes in direction Do not use more than 8 pulley elbows between the r...

Страница 6: ...d install jumper J2 across terminals 4 and 5 Terminals 1 through 3 are provided for auxiliary device con nections Auxiliary equipment is controlled through the action of switch S1 Refer to the followi...

Страница 7: ...the Installation Operation and Maintenance Manual s furnished with the Ansul Fire Suppression System and disarm remove the agent tank assembly actuation mechanism before test firing 2 Check ANSUL AUTO...

Страница 8: ...and replace if cartridge weight is 1 4 oz 7 1 g or more below weight stamped on car tridge Install fully charged cartridge and hand tighten Refer to the Installation Operation and Maintenance Manual p...

Страница 9: ...TRIKE button and open enclo sure 2 Insert ring pin as shown in Figure 9 3 Remove cartridge and install safety shipping cap 4 Perform steps 2 through 4 in the TEST OF WIRING section on page 5 5 Perform...

Страница 10: ......

Страница 11: ......

Страница 12: ...Part No 17788 09 1995 Ansul Incorporated Litho in U S A ANSUL INCORPORATED ONE STANTON STREET MARINETTE WI 54143 2542...

Отзывы: