OPERATION (Continued)

FIGURE 2

004294

MOUNTING “ANSUL AUTOMAN” II-C RELEASE

The reliability of an Ansul fixed nozzle fire suppression sys-
tem depends greatly upon proper installation of the releasing
device, associated equipment and wiring. Unless noted oth-
erwise in the fire suppression system manual, the mounting
location for the ANSUL AUTOMAN II-C release must be
maintained within a temperature range of 32 °F to 120 °F
(0 °C to 49 °C). This requirement and the following instruc-
tions are critical for reliable operation.

Installing the Release

1. Select a shock and vibration free surface in a clean dry

area for mounting the ANSUL AUTOMAN II-C release
enclosure. The mounted release should be completely
visible and accessible for maintenance.

NOTICE

The STRIKE button must be accessible for
manual operation. Follow local, state, or
federal regulations for proper location. If the
release cannot be mounted in this manner,
a remote manual pull station should be
installed to facilitate manual actuation.

2. Open the release cover and secure the enclosure at the

selected location utilizing the four mounting holes. Use
lag screws or toggle bolts depending on the mounting
surface. Figure 3 provides detailed mounting data.

FIGURE 3

001804

3. Connect the release and the extinguishing agent

tank(s)/activating mechanism with 1/4 in. (6 mm)
Schedule 40 or Schedule 80 pipe, starting from the gas
outlet port in the release as shown in Figure 4. Refer to
the Installation, Operation and Maintenance Manual pro-
vided with the Ansul Fire Suppression System for the
maximum allowable length of actuation line piping.

INSTALLATION INSTRUCTIONS
UL R5998      6-16-95      Page 2

TO EXTINGUISHING AGENT
TANK ACTIVATING DEVICE

CONTROL

UNIT

POWER INPUT

“ANSUL AUTOMAN”

TO
DETECTORS

CAUTION

!

A number of basic variations are available in the ANSUL
AUTOMAN II-C assembly. Your ANSUL AUTOMAN II-C
may have either a carbon dioxide actuation cartridge or a
nitrogen actuation cartridge. Ansul Incorporated recom-
mends that all systems employing carbon dioxide actua-
tors be restricted to installations in areas where the ambi-
ent temperature is never less that 32 °F (0 °C) or greater
than 120 °F (49 °C). If ambient temperatures in the area of
the actuation cartridge fall below 32 °F (0 °C) or exceed
120 °F (49 °C), it is mandatory that a nitrogen cartridge be
used. In every case be certain when replacing cartridges
that the proper type is used, and that it meets the temper-
ature range and weight requirements outlined in the
instruction manual for that type of system. The pressure
relief device in the actuation line may be either the actua-
tion line vent (which relieves automatically) or the pressure
relief valve (pull ring to effect total relief). Refer to the
Installation, Operation and Maintenance Manual provided
with the Ansul Fire Suppression System.

CAUTION

!

Do not install cartridge until all testing has been completed
and the system is ready to be armed as instructed on the
following pages.

KNOCKOUTS ON 4 SIDES OF BOX

SURFACE
MOUNTING

12.13 IN.
(308.1 mm)

1.13 IN.
(28.7 mm)

1 IN.
(25.4 mm)

5/15 IN. DIA.
HOLES
(8.5 mm)

4.13 IN.
(104.9 mm)

24.13 IN.
(612.9 mm)

Содержание AUTOMAN II-C

Страница 1: ...INSTALLATION ANSUL OPERATION AND AUTOMAN II C MAINTENANCE RELEASING MANUAL DEVICE ANSUL 001799...

Страница 2: ...icular interest depending upon one s responsibility ANSUL AUTOMAN II C is an electrical mechanical device It requires periodic care Maintenance to provide maximum assurance that your releasing device...

Страница 3: ...remote manual cable pull station ANSUL AUTOMAN II C RELEASING DEVICE FIGURE 1 004300 1 VISUAL INDICATOR WINDOW 2 WIRING INSTRUCTIONS 3 RELEASE MECHANISM 4 RESET LEVER 5 STRIKE BUTTON 6 ELECTRIC SWITC...

Страница 4: ...tion Operation and Maintenance Manual pro vided with the Ansul Fire Suppression System for the maximum allowable length of actuation line piping INSTALLATION INSTRUCTIONS UL R5998 6 16 95 Page 2 TO EX...

Страница 5: ...secure 1 2 in 13 mm rigid conduit from ANSUL AUTOMAN II C release assembly to pull station using pulley elbows Part No 45771 for changes in direction Do not use more than 8 pulley elbows between the r...

Страница 6: ...d install jumper J2 across terminals 4 and 5 Terminals 1 through 3 are provided for auxiliary device con nections Auxiliary equipment is controlled through the action of switch S1 Refer to the followi...

Страница 7: ...the Installation Operation and Maintenance Manual s furnished with the Ansul Fire Suppression System and disarm remove the agent tank assembly actuation mechanism before test firing 2 Check ANSUL AUTO...

Страница 8: ...and replace if cartridge weight is 1 4 oz 7 1 g or more below weight stamped on car tridge Install fully charged cartridge and hand tighten Refer to the Installation Operation and Maintenance Manual p...

Страница 9: ...TRIKE button and open enclo sure 2 Insert ring pin as shown in Figure 9 3 Remove cartridge and install safety shipping cap 4 Perform steps 2 through 4 in the TEST OF WIRING section on page 5 5 Perform...