GENERAL INSTRUCTIONS

UL R5998      6-16-95      Page 1

INTRODUCTION

The ANSUL AUTOMAN II-C Releasing Device is designed
for use with Ansul fire suppression systems. It provides auto-
matic-pneumatic actuation of fixed nozzle fire suppression
systems when connected to a suitable listed fire
detection/alarm system.

DESCRIPTION

The ANSUL AUTOMAN II-C is shown in Figure 1 and 2. It is
comprised of a metal enclosure which contains a spring-
loaded puncture pin release mechanism, an actuation car-
tridge (order separately), an auxiliary function switch, and a
terminal strip for making electrical connections. Knockouts
for the connection of conduit are provided in the top, bottom
and sides of the steel enclosure. The enclosure also con-
tains four surface mounting holes.

OPERATION

When energized, a solenoid mounted on the actuator trips
the release mechanism puncturing the cartridge. Actuation
gas from the cartridge is directed through piping to pneumati-
cally activate the fire suppression system.

Manual actuation is provided by means of an integral
STRIKE button at the release enclosure which may be sup-
plemented by use of a remote manual cable pull station.

“ANSUL AUTOMAN” II-C RELEASING DEVICE

FIGURE 1

004300

1. VISUAL INDICATOR WINDOW
2. WIRING INSTRUCTIONS
3. RELEASE MECHANISM
4. RESET LEVER
5. STRIKE BUTTON
6. ELECTRIC SWITCH
7. TERMINAL BOARD
8. ACTUATION CARTRIDGE

CAUTION

!

A number of basic variations are available in the ANSUL
AUTOMAN II-C assembly. Your ANSUL AUTOMAN II-C
may have either a carbon dioxide actuation cartridge or a
nitrogen actuation cartridge. In every case Ansul
Incorporated recommends that all systems employing car-
bon dioxide actuators be restricted to installations in areas
where the ambient temperature is never less that 32 °F
(0 °C) or greater than 120 °F (49 °C). If ambient tempera-
tures in the area of the actuation cartridge fall below 32 °F
(0 °C) or exceed 120 °F (49 °C), it is mandatory that a
nitrogen cartridge be used. Be certain when replacing car-
tridges that the proper type is used, and that it meets the
temperature range and weight requirements outlined in
the instruction manual for that type of system. The pres-
sure relief device in the actuation line may be either the
actuation line vent (which relieves automatically) or the
pressure relief valve (pull ring to effect total relief). Refer to
the Installation, Operation and Maintenance Manual pro-
vided with the Ansul Fire Suppression System.

2

1

5

8

6

4

3

7

Содержание AUTOMAN II-C

Страница 1: ...INSTALLATION ANSUL OPERATION AND AUTOMAN II C MAINTENANCE RELEASING MANUAL DEVICE ANSUL 001799...

Страница 2: ...icular interest depending upon one s responsibility ANSUL AUTOMAN II C is an electrical mechanical device It requires periodic care Maintenance to provide maximum assurance that your releasing device...

Страница 3: ...remote manual cable pull station ANSUL AUTOMAN II C RELEASING DEVICE FIGURE 1 004300 1 VISUAL INDICATOR WINDOW 2 WIRING INSTRUCTIONS 3 RELEASE MECHANISM 4 RESET LEVER 5 STRIKE BUTTON 6 ELECTRIC SWITC...

Страница 4: ...tion Operation and Maintenance Manual pro vided with the Ansul Fire Suppression System for the maximum allowable length of actuation line piping INSTALLATION INSTRUCTIONS UL R5998 6 16 95 Page 2 TO EX...

Страница 5: ...secure 1 2 in 13 mm rigid conduit from ANSUL AUTOMAN II C release assembly to pull station using pulley elbows Part No 45771 for changes in direction Do not use more than 8 pulley elbows between the r...

Страница 6: ...d install jumper J2 across terminals 4 and 5 Terminals 1 through 3 are provided for auxiliary device con nections Auxiliary equipment is controlled through the action of switch S1 Refer to the followi...

Страница 7: ...the Installation Operation and Maintenance Manual s furnished with the Ansul Fire Suppression System and disarm remove the agent tank assembly actuation mechanism before test firing 2 Check ANSUL AUTO...

Страница 8: ...and replace if cartridge weight is 1 4 oz 7 1 g or more below weight stamped on car tridge Install fully charged cartridge and hand tighten Refer to the Installation Operation and Maintenance Manual p...

Страница 9: ...TRIKE button and open enclo sure 2 Insert ring pin as shown in Figure 9 3 Remove cartridge and install safety shipping cap 4 Perform steps 2 through 4 in the TEST OF WIRING section on page 5 5 Perform...

Страница 10: ......

Страница 11: ......

Страница 12: ...Part No 17788 09 1995 Ansul Incorporated Litho in U S A ANSUL INCORPORATED ONE STANTON STREET MARINETTE WI 54143 2542...

Отзывы: