Ansul 100/30 Скачать руководство пользователя страница 32

FOam sOlUTION CONCeNTRaTION DeTeRmINaTION

Page 2

FOam sOlUTION CONCeNTRaTION DeTeRmINaTION
ReFRaCTIve INDex OR CONDUCTIvITy

This test is used to determine the percent concentrate of a
foam concentrate in the water being used to generate foam.
It is typically used as a means to determine the accuracy of
the system’s proportioning equipment.

This  method  is  based  upon  comparing  foam  solution  test
sample  to  pre-measured  solutions  (Calibration  Standard)
that  are  plotted  on  a  baseline  graph  of  percent  concentra-
tion versus instrument reading.

A hand-held refractometer is used to measure the refractive
index  of  the  foam  solution  sample.  Scales  on  refractome-
ters  vary,  but  what  is  actually  being  used  to  determine
concentration  is  a  change  in  reading  from  one  pre-
measured  solution  to  another  (Calibration  Standards
“Curve” vs. Discharge Samples “Reading”). The philosophy
applies when using a conductivity meter which is measuring
the  changes  in  the  solution’s  conductivity.  (Refer  to
Proportioning Test Instruments Data Sheet, F-2007003, for
more detailed information about the specific meters.)

A base curve is prepared by using the following apparatus:

1. Four 100 ml or larger plastic bottles with leak-resistant

screw caps

2. One 10 ml (10 cc) measuring syringe

3. One 100 ml graduated cylinder

4. Four or more eye droppers

5. One Test Meter – Model PA 202, 10419, 1500-32

6. Graph paper

7. Ruler or straight edge

Using  water  and  foam  concentrate  from  the  system  to  be
tested, make up three 100 ml calibration standard solutions.
For a 6% concentrate, typically a 4%, 6% and 8% samples;
for a 3% concentrate, typically a 2%, 3% and 4% samples;
and  for  a  1%  concentrate,  typically  a  0.5%,  1%  and  1.5%
samples are made.

Label  bottles  with  percent  sample  calibration  solution  that
will  be  utilized,  i.e.  2%,  3%  and  4%  for  a  3%  concentrate.
As  an  example,  for  the  2%  calibration  solution  sample,
measure  98  ml  of  system  water  in  the  graduate  cylinder,
then pour into the bottle labeled 2%. Then with the measur-
ing syringe, transfer 2 ml (2 cc) of the concentrate into the
labeled  bottle.  Secure  the  cap  on  the  bottle  and  shake  to
thoroughly  mix  the  solution.  Repeat  for  the  3%  calibration
sample (97 ml water and 3 ml concentrate) and for the 4%
calibration  sample  (96  ml  water  and  4  ml  concentrate).

Increasing sample sizes will increase accuracy relative
to  the  measurement  instrument. 

After  thoroughly  mixing

the foam sample, a meter reading is taken of each percent-
age foam solution sample. It is important that temperatures
between discharge samples and calibration standards have
normalized with temperatures above 50 °F (10 °C) working
best.  Each  instrument  has  specific  instructions  for  its
correct operation.

Using the graph paper, plot the meter reading on the X axis
and  the  percent  concentrate  reading  on  the  Y  axis.  This
plotted  curve  will  serve  as  the  known  baseline  for  the
proportioning  test.  Meters  may  have  different  scales  and
the  plotted  resolution  should  be  as  large  as  possible  with
the complete range of the calibration solutions known. The
scale you set must be linear.

Collect  foam  solution  sample(s)  from  the  proportioning
system, using care to ensure that each sample is taken at
an  adequate  distance  downstream  from  the  proportioner
being  tested.  (Usually  any  place  downstream  of  the  first
change in direction is adequate if samples are taken in the
riser  room.)  Stabilize  a  water  flow  through  your  discharge
device  within  the  known  acceptable  range  for  the  propor-
tioner  and  open  the  concentrate  control  valve.  Take  the
sample  about  30  to  60  seconds  after  foam  appears  from
the  test  connection.  Take  meter  readings  of  the  sample(s)
and compare readings to the plotted curve to determine the
percentage for each sample.

Per  NFPA  11, 

Standard  for  Low-,  Medium-,  and  High-

Expansion  Foam,

acceptable  ranges  of  proportioning

systems  are  not  less  than  the  rated  concentration  and  not
more  than  30%  above  the  rated  concentration  or  one
percentage point above the rated concentration, whichever
is  less.  For  example,  the  acceptable  range  for  a  3%
concentrate is from 3 to 3.9%.

Note: 

There is some variability dependent on the accuracy

of the meter, the accuracy to which the calibration samples
were  made,  and  if  temperatures  between  calibration  stan-
dards  and  discharge  samples  have  not  normalized.
Conductivity is especially susceptible to reading fluctuation,
thus the sample should be continuously stirred until a stabi-
lized  reading  can  be  estimated.  Care  should  be  taken  to
not  bump  the  sides  or  bottom  of  the  sample  container  or
contaminate the sample with salts or solids, i.e. dirty fingers
while  stirring.  The  conductivity  of  water  stored  in  or  for
systems can vary throughout a discharge which may affect
results.  Conductivity  should  not  be  used  for  sea,  salt,  or
brackish  water  supplies. Although  conductivity  can  be  the
most  accurate  means  of  measuring  foam  solution  in  clean
water  supplies  under  ideal  conditions,  the  refractive  index
method is best for most real world testing.

If  discharge  samples  are  sent  to  the  Tyco  Fire  Protection
Products  Test  Lab  for  analysis,  they  should  be  packaged
per the instructions with the Test Kit and sent in for immedi-
ate processing. Largely dependent on water quality and the
type  of  concentrate  used,  foam  solutions  may  start  to
biodegrade in a short period of time which can affect results
(possibly  as  little  as  three  to  five  days  with  nutrient-rich
water and detergent-based foam concentrates).

The  following  graphs  are  examples  of  typical  refractive
index  values  for  various  concentrate  pre-mixes.  Results
may  vary  depending  on  the  concentrate  pre-mix  type,  site
water supply, and actual concentrate lot number. Therefore,
it is important that a new calibration curve be developed on
each date a proportioning test is required.

Содержание 100/30

Страница 1: ...ANSUL FIRE SUPPRESSION SECURING SYSTEMS OPERATION AND MAINTENANCE MANUAL Part No 63390 01...

Страница 2: ......

Страница 3: ...ANSUL FIRE SUPPRESSING SECURING SYSTEM MODEL 100 30 TYCO FIRE PROTECTION PRODUCTS MARINETTE WISCONSIN 54143 2542...

Страница 4: ......

Страница 5: ...ecuring systems are mechanical devices They need periodic care Inspection to provide reasonable assurance that the fire suppressing securing system is fully charged and operable will vary from hourly...

Страница 6: ......

Страница 7: ...charge Guide 8 Inspection 9 Maintenance 10 11 Pressure Regulator Test 12 16 Nitrogen Cylinder Valve F 81397 Service and Repair F 8832 Field Inspection Manual PN31274 Parts Lists Prints TABLE OF CONTEN...

Страница 8: ...s situation in which a person could experience serious personal injury or death if the situation is not avoided Indicates a hazardous situation in which a person could experience minor or moderate per...

Страница 9: ...ving fill cap s as tank s may be pres surized If fill cap has a red indicator stem in the up position pres sure must be relieved from tank If fill cap vent starts relieving pressure while opening the...

Страница 10: ...e hose to nitrogen cylinder valve and wrench tighten Do not strike pull lever when connecting hose to cylinder valve Escaping gas is forceful enough to cause injury 8 Make certain visual inspection se...

Страница 11: ...ion System must be recharged immediately after use See Recharge Section Protection for personnel and property is not available until system is recharged IMPORTANT If the system cannot be actuated by u...

Страница 12: ...as 8 Ensure remaining dry chemical is dry and not caked If tank is empty make sure the tank is completely dry before adding dry chemical to tank Fill dry chemical tank by completing the fol lowing ste...

Страница 13: ...ing and pour in measured amount of only ANSULITE AFFF Aqueous Film Forming Foam 3 Concentrate determined from the corresponding Recharge Guide on Page 8 NOTICE Prior to adding the concentrate to the t...

Страница 14: ...If valve is accidentally operated velocity of unrestricted escaping gas is forceful enough to cause injury especially about the face and head f Secure cylinder shipping cap Safety shipping cap must a...

Страница 15: ...strike pull lever when connecting hose to cylinder valve velocity of unrestricted escaping gas is forceful enough to cause injury especially about the face and head 15 Make certain visual inspection...

Страница 16: ...699 24 25 616 21 00 533 17 75 450 14 50 368 11 25 286 8 00 203 4 75 121 0 00 AFFF CONCENTRATE REQUIRED 6 3 Gal L Gal L ___ __ ___ __ 0 0 0 0 0 0 0 0 2 0 8 0 1 0 4 0 4 1 5 0 2 0 8 0 6 2 3 0 3 1 1 0 8 3...

Страница 17: ...e careful when removing fill cap s as tank s may be pres surized If fill cap has a red indicator stem in the up position pres sure must be relieved from tank If fill cap vent starts relieving pressure...

Страница 18: ...tank is filled with only free flowing ANSUL dry chemical to a level of not more than 6 inches 152 mm from bottom of the fill opening e Secure fill cap and hand tighten Make certain gasket is in place...

Страница 19: ...ose and check for abrasions cuts or weather checking b Examine nozzle openings for obstructions and operate nozzle triggers to check valves for free movement c Make certain hose couplings are tight an...

Страница 20: ...e Quick Connect Couplers Part No 22592 1 4 in Male Quick Connect Plug Part No 24560 Not Shown 3 8 in Male Quick Connect Plug Part No 24559 Not Shown 1 4 in Female Quick Connect Plug Part No 24561 Not...

Страница 21: ...on the low pressure side Note Each hose has a swivel at one end only remove hose at swivel end first Plug one side of tee 4 Install the appropriate quick connect plug to the low pressure regulator out...

Страница 22: ...re on the test gauge for one minute This reading must be within the dead set range listed on the specification chart Page 16 for the model regulator being tested If the reading falls outside the speci...

Страница 23: ...itrogen cylinder gauge for proper minimum pres sure Use the temperature correction chart on the next page to find the true tank pressure If the pressure is below the rec ommended level the cylinder mu...

Страница 24: ...shows that this is above the tempera ture correction line and the cylinder does not require replace ment cylinder varies with changes in temperature Accordingly the chart below has been prepared to d...

Страница 25: ...78707 78707 N A 5 Safety Disc and Washer 78711 78711 419102 6 Plug Safety Relief 78709 78709 N A 4 5 6 2 3 1 002563 RS Standard Valve 4 6 2 1 002564 RS Quick Opening Valve 5 5 7 6 3 1 4 002565 2 Pneum...

Страница 26: ...ent hole with a stiff unbreakable wire probe of lesser diam eter that vent hole Threads corroded nicked cross Replace destroying affected cap to prevent reuse threaded or worn Cut checked deformed sti...

Страница 27: ...pplicable parts list Nitrogen Cylinder Rust spots pits and corrosion deposits Clean corroded areas with a wire brush replacing cylinder if there is any corrosion penetration or repaint using a primer...

Страница 28: ...adjust screw or bracket replace bracket Worn or missing protective cylinder Replace webbing Part No 3360 or grommet Part No 8688 bracket webbing or grommet Wrong cylinder retaining bracket Replace br...

Страница 29: ...ting other than the hose to reel connection Pneumatic Actuation Corroded jammed or broken Clean repair to free movement or replace System puncture lever Dull bent or damaged puncture pin Replace pin m...

Страница 30: ...Page 1 001330 FOAM CONCENTRATES AND FOAM PRE MIX SOLUTIONS Field Inspection Manual...

Страница 31: ...ges of two 2 sample containers with labels can be purchased under Part No 428679 sTORage CONDITIONs Tyco Fire Protection Products recommends that its concen trates be stored at the temperatures indica...

Страница 32: ...Y axis This plotted curve will serve as the known baseline for the proportioning test Meters may have different scales and the plotted resolution should be as large as possible with the complete range...

Страница 33: ...TypICal CalIbRaTION CURve ResUlTs WheN UsINg paRT NO 405713 haNDhelD ReFRaCTOmeTeR Page 3 006876...

Страница 34: ...NOTes NOTes Page 4...

Страница 35: ...E TYPE LOT NO ______________________________________________________________________ METER TYPE ________ CONDUCTIVITY ________ REFRACTOMETER MODEL __________________________________ PERCENT FOAM SOLUT...

Страница 36: ...Part No 31274 07 Copyright 2011 Tyco Fire Protection0 Products All rights reserved TYCO FIRE PROTECTION PRODUCTS ONE STANTON STREET MARINETTE WI 54143 2542...

Страница 37: ...d in this material are marks and or registered marks Unauthorized use is strictly prohibited ITEM NO DESCRIPTION PART NO 1 Recharge Nameplate 438214 2 Nameplate AFFF Tank 14206 3 Nameplate Dry Chemica...

Отзывы: