INTRODUCTION

This  manual  is  designed  to  serve  as  a  guide  to  inspection
procedures  for ANSUL  Foam  Concentrates  and  Pre-mix
Solutions.

As Tyco Fire Protection Products manufactures many types
of foam concentrates, locate the product data sheet for the
specific concentrate to be tested. Product Data Sheets can
be accessed at 

www.ansul.com.

The  designated  inspector  should  be  a  responsible,  experi-
enced  person  with  sound,  basic  knowledge  of  fire  equip-
ment  hardware  and  extinguishing  agents. A  thorough
briefing on the procedures to be followed should include the
need for precise execution of each analysis step.

See  Field  Inspection  Record  at  the  end  of  this  manual  to
record proportioning results.

Form  Part  No.  428680,  Foam Analysis  Request,  is  for  use
in  recording  the  information  required  when  sending  in
samples  to  the  Tyco  Fire  Protection  Products Agents
Laboratory.    This  form  also  outlines  the  correct  procedure
for  submitting  samples.  Review  and  complete  the  form  as
thoroughly  as  possible.  This  form  is  included  in  the  Foam
Agent  Test  Kit,  Part  No.  428679.  It  is  also  available  on
www.ansul.com  under  “Foam  Products.”  (

Note:

There  is  a

charge for this testing service.)

FReqUeNCy aND aCCURaCy OF TesTs

Tyco Fire Protection Products recommends that proportion-
ing tests be done at system commissioning and every three
(3) years minimum thereafter.

exception: 

Pre-primed  foam-water  sprinkler  systems

should be flushed, drained and pre-primed with fresh solu-
tion  annually.  During  this  process  correct  proportioning
should be verified.

Tyco  Fire  Protection  Products  recommends  that  Standard
Quality Analysis Testing be done annually by the Tyco Fire
Protection Products Agents Laboratory which not only tests
the  chemical  properties  of  the  sample,  but  also  does  lab
scale  fire  testing  to  assure  the  product’s  performance.
Packages  of  two  (2)  sample  containers  with  labels  can  be
purchased under Part No. 428679.

sTORage CONDITIONs

Tyco Fire Protection Products recommends that its concen-
trates  be  stored  at  the  temperatures  indicated  on  the
specific product data sheet.

Accelerated  aging  studies  have  been  conducted  with  the
concentrate  and  pre-mix  solutions  stored  at  150  °F
(65.5 °C)  with  no  adverse  effect.  However,  Underwriters
Laboratory  Standard  No.  162  requires  that  the  maximum
storage temperature be listed at 120 °F (48.9 °C). 

Storage  of  concentrates  below  the  minimum  temperature
listed on the product data sheets could result in freezing.  If
the  agent  freezes,  it  should  be  thawed  at  or  near  room
temperature  and  agitated  or  stirred  to  ensure  a  homoge-
nous mixture.  If previous freezing is suspect, agitation will
again ensure a homogenous mixture.

To  maximize  life  of  concentrates  stored  in  atmospheric
storage  tanks, ANSUL  recommends  that  a  1/4  in.  (6  mm)
layer of mineral oil be added to the air-exposed surface of
the  concentrate.  This  is  critical  for Alcohol  Resistant
Concentrates.

RelaTeD INFORmaTION

The  following  is  a  list  of  Technical  Bulletins  that  can  be
found at the ANSUL internet home page 

www.ansul.com.

•  Technical Bulletin Number 52

(Environmental Impact of ANSULITE AFFF Products)

•  Technical Bulletin Number 54

(Shelf Life of ANSULITE AFFF Concentrates and Their
Pre-mixed Solutions)

•  Technical Bulletin Number 55

(Aspirated Versus Nonaspirated AFFF)

•  Technical Bulletin Number 59

(Acceptable Materials of Construction For Use With
ANSUL Foam Concentrates)

•  Technical Bulletin Number 60

(Foam and The Environment)

•  Technical Bulletin Number 64

(Compatibility of AFFF/Alcohol-Resistant AFFF
Concentrates)

ReFRaCTIve INDex vs. CONDUCTIvITy

Tyco Fire Protection Products recommends refractive index
testing  instead  of  conductivity  testing  in  the  field  because
there  is  less  chance  of  results  being  skewed  by  water
quality  or  temperature. Also,  continuous  stirring  is  required
during conductivity testing to obtain stable results.

INTRODUCTION

Page 1

Содержание 100/30

Страница 1: ...ANSUL FIRE SUPPRESSION SECURING SYSTEMS OPERATION AND MAINTENANCE MANUAL Part No 63390 01...

Страница 2: ......

Страница 3: ...ANSUL FIRE SUPPRESSING SECURING SYSTEM MODEL 100 30 TYCO FIRE PROTECTION PRODUCTS MARINETTE WISCONSIN 54143 2542...

Страница 4: ......

Страница 5: ...ecuring systems are mechanical devices They need periodic care Inspection to provide reasonable assurance that the fire suppressing securing system is fully charged and operable will vary from hourly...

Страница 6: ......

Страница 7: ...charge Guide 8 Inspection 9 Maintenance 10 11 Pressure Regulator Test 12 16 Nitrogen Cylinder Valve F 81397 Service and Repair F 8832 Field Inspection Manual PN31274 Parts Lists Prints TABLE OF CONTEN...

Страница 8: ...s situation in which a person could experience serious personal injury or death if the situation is not avoided Indicates a hazardous situation in which a person could experience minor or moderate per...

Страница 9: ...ving fill cap s as tank s may be pres surized If fill cap has a red indicator stem in the up position pres sure must be relieved from tank If fill cap vent starts relieving pressure while opening the...

Страница 10: ...e hose to nitrogen cylinder valve and wrench tighten Do not strike pull lever when connecting hose to cylinder valve Escaping gas is forceful enough to cause injury 8 Make certain visual inspection se...

Страница 11: ...ion System must be recharged immediately after use See Recharge Section Protection for personnel and property is not available until system is recharged IMPORTANT If the system cannot be actuated by u...

Страница 12: ...as 8 Ensure remaining dry chemical is dry and not caked If tank is empty make sure the tank is completely dry before adding dry chemical to tank Fill dry chemical tank by completing the fol lowing ste...

Страница 13: ...ing and pour in measured amount of only ANSULITE AFFF Aqueous Film Forming Foam 3 Concentrate determined from the corresponding Recharge Guide on Page 8 NOTICE Prior to adding the concentrate to the t...

Страница 14: ...If valve is accidentally operated velocity of unrestricted escaping gas is forceful enough to cause injury especially about the face and head f Secure cylinder shipping cap Safety shipping cap must a...

Страница 15: ...strike pull lever when connecting hose to cylinder valve velocity of unrestricted escaping gas is forceful enough to cause injury especially about the face and head 15 Make certain visual inspection...

Страница 16: ...699 24 25 616 21 00 533 17 75 450 14 50 368 11 25 286 8 00 203 4 75 121 0 00 AFFF CONCENTRATE REQUIRED 6 3 Gal L Gal L ___ __ ___ __ 0 0 0 0 0 0 0 0 2 0 8 0 1 0 4 0 4 1 5 0 2 0 8 0 6 2 3 0 3 1 1 0 8 3...

Страница 17: ...e careful when removing fill cap s as tank s may be pres surized If fill cap has a red indicator stem in the up position pres sure must be relieved from tank If fill cap vent starts relieving pressure...

Страница 18: ...tank is filled with only free flowing ANSUL dry chemical to a level of not more than 6 inches 152 mm from bottom of the fill opening e Secure fill cap and hand tighten Make certain gasket is in place...

Страница 19: ...ose and check for abrasions cuts or weather checking b Examine nozzle openings for obstructions and operate nozzle triggers to check valves for free movement c Make certain hose couplings are tight an...

Страница 20: ...e Quick Connect Couplers Part No 22592 1 4 in Male Quick Connect Plug Part No 24560 Not Shown 3 8 in Male Quick Connect Plug Part No 24559 Not Shown 1 4 in Female Quick Connect Plug Part No 24561 Not...

Страница 21: ...on the low pressure side Note Each hose has a swivel at one end only remove hose at swivel end first Plug one side of tee 4 Install the appropriate quick connect plug to the low pressure regulator out...

Страница 22: ...re on the test gauge for one minute This reading must be within the dead set range listed on the specification chart Page 16 for the model regulator being tested If the reading falls outside the speci...

Страница 23: ...itrogen cylinder gauge for proper minimum pres sure Use the temperature correction chart on the next page to find the true tank pressure If the pressure is below the rec ommended level the cylinder mu...

Страница 24: ...shows that this is above the tempera ture correction line and the cylinder does not require replace ment cylinder varies with changes in temperature Accordingly the chart below has been prepared to d...

Страница 25: ...78707 78707 N A 5 Safety Disc and Washer 78711 78711 419102 6 Plug Safety Relief 78709 78709 N A 4 5 6 2 3 1 002563 RS Standard Valve 4 6 2 1 002564 RS Quick Opening Valve 5 5 7 6 3 1 4 002565 2 Pneum...

Страница 26: ...ent hole with a stiff unbreakable wire probe of lesser diam eter that vent hole Threads corroded nicked cross Replace destroying affected cap to prevent reuse threaded or worn Cut checked deformed sti...

Страница 27: ...pplicable parts list Nitrogen Cylinder Rust spots pits and corrosion deposits Clean corroded areas with a wire brush replacing cylinder if there is any corrosion penetration or repaint using a primer...

Страница 28: ...adjust screw or bracket replace bracket Worn or missing protective cylinder Replace webbing Part No 3360 or grommet Part No 8688 bracket webbing or grommet Wrong cylinder retaining bracket Replace br...

Страница 29: ...ting other than the hose to reel connection Pneumatic Actuation Corroded jammed or broken Clean repair to free movement or replace System puncture lever Dull bent or damaged puncture pin Replace pin m...

Страница 30: ...Page 1 001330 FOAM CONCENTRATES AND FOAM PRE MIX SOLUTIONS Field Inspection Manual...

Страница 31: ...ges of two 2 sample containers with labels can be purchased under Part No 428679 sTORage CONDITIONs Tyco Fire Protection Products recommends that its concen trates be stored at the temperatures indica...

Страница 32: ...Y axis This plotted curve will serve as the known baseline for the proportioning test Meters may have different scales and the plotted resolution should be as large as possible with the complete range...

Страница 33: ...TypICal CalIbRaTION CURve ResUlTs WheN UsINg paRT NO 405713 haNDhelD ReFRaCTOmeTeR Page 3 006876...

Страница 34: ...NOTes NOTes Page 4...

Страница 35: ...E TYPE LOT NO ______________________________________________________________________ METER TYPE ________ CONDUCTIVITY ________ REFRACTOMETER MODEL __________________________________ PERCENT FOAM SOLUT...

Страница 36: ...Part No 31274 07 Copyright 2011 Tyco Fire Protection0 Products All rights reserved TYCO FIRE PROTECTION PRODUCTS ONE STANTON STREET MARINETTE WI 54143 2542...

Страница 37: ...d in this material are marks and or registered marks Unauthorized use is strictly prohibited ITEM NO DESCRIPTION PART NO 1 Recharge Nameplate 438214 2 Nameplate AFFF Tank 14206 3 Nameplate Dry Chemica...

Отзывы: