Component

Disorder

Corrective Action

Nitrogen Cylinder

Unreadable, faded, or corroded dial

Depressurize cylinder and replace valve assembly, or consult

(Continued)

Product Services, Tyco Fire Protection Products,
Marinette, Wisconsin 54143-2542.

Gauge pointer below acceptable 

Check pressure with test gauge (Part No. 2737), tapping valve

operating range

gauge lightly to check for mechanical disorder (gauge pointer
loose or immovable). If test gauge pressure reading confirms
valve gauge pressure reading, perform leakage test as outlined in
‘’Valve Leakage Suspected,’’ taking the appropriate action indicat-
ed. If valve leak test is negative, test cylinder for pin hole leaks,
discard cylinder after rendering it unusable by depressurization,
removal of valve, and destruction of internal and external threads.
If leak is detectable, consult Product Services, Tyco Fire
Protection Products, Marinette, Wisconsin 54143-2542.

Gauge pointer above acceptable 

Check pressure with test gauge (Part No. 2737), tapping valve

operating range

gauge lightly to check for mechanical disorder (gauge pointer
loose or immovable) and then bleed off excess pressure, or
depressurize cylinder and replace valve assembly.

Corroded, bent, or worn cylinder

Clean and refinish; repair and refinish; or replace.

retaining bracket

Loose or binding cylinder retaining 

Adjust fit by tightening or loosening bracket; adjust screw, or

bracket

replace bracket.

Worn or missing protective cylinder 

Replace webbing (Part No. 3360) or grommet (Part No. 8688).

bracket webbing or grommet

Wrong cylinder retaining bracket

Replace bracket with type specified by ANSUL only.

Pressure

Corroded, dented, or otherwise

Replace regulator(s).

Regulator

damaged

Regulator safety relief valve corroded, 

Replace valve.

plugged, dented, broken, or missing

Expellant Gas and

Broken or missing visual inspection seals Replace seals.

Agent Control
Valve

Bent, corroded or binding ring pin

Replace ring pin.

Valve immovable, stiff, inoperable, 

Disconnect, disassemble, and clean, replacing parts as required.

or leaking

Pressure Relief

Corroded, plugged, dented, broken,

Clean, repair, and test before reinstalling; or replace valve.

Valve

or missing

Hose (Expellant Gas

Cut, cracked, abraded, or deformed

Replace entire hose assembly or hose only if coupling

and Agent)

exterior

is reusable type.

Corroded, or cracked coupling, 

Replace entire hose assembly or coupling only if reusable type.

swivel joint or ferrule

Corroded, cross-threaded or worn 

Replace entire hose assembly or coupling only if reusable type.

coupling threads

Internal blockage

Clear by blowing dry air or nitrogen at 220 psi (15.17 bar)
through hose.

Coupling gasket brittle, compression 

Replace, lubricating clean new gasket lightly with a good grade of

set, cut, cracked, or missing

high heat resistant grease before insertion.

SERVICE AND REPAIR

CAUTION

!

Do not leave open end of hose unattended unless adequate-
ly restrained to prevent whipping, endangering life/safety.

Содержание 100/30

Страница 1: ...ANSUL FIRE SUPPRESSION SECURING SYSTEMS OPERATION AND MAINTENANCE MANUAL Part No 63390 01...

Страница 2: ......

Страница 3: ...ANSUL FIRE SUPPRESSING SECURING SYSTEM MODEL 100 30 TYCO FIRE PROTECTION PRODUCTS MARINETTE WISCONSIN 54143 2542...

Страница 4: ......

Страница 5: ...ecuring systems are mechanical devices They need periodic care Inspection to provide reasonable assurance that the fire suppressing securing system is fully charged and operable will vary from hourly...

Страница 6: ......

Страница 7: ...charge Guide 8 Inspection 9 Maintenance 10 11 Pressure Regulator Test 12 16 Nitrogen Cylinder Valve F 81397 Service and Repair F 8832 Field Inspection Manual PN31274 Parts Lists Prints TABLE OF CONTEN...

Страница 8: ...s situation in which a person could experience serious personal injury or death if the situation is not avoided Indicates a hazardous situation in which a person could experience minor or moderate per...

Страница 9: ...ving fill cap s as tank s may be pres surized If fill cap has a red indicator stem in the up position pres sure must be relieved from tank If fill cap vent starts relieving pressure while opening the...

Страница 10: ...e hose to nitrogen cylinder valve and wrench tighten Do not strike pull lever when connecting hose to cylinder valve Escaping gas is forceful enough to cause injury 8 Make certain visual inspection se...

Страница 11: ...ion System must be recharged immediately after use See Recharge Section Protection for personnel and property is not available until system is recharged IMPORTANT If the system cannot be actuated by u...

Страница 12: ...as 8 Ensure remaining dry chemical is dry and not caked If tank is empty make sure the tank is completely dry before adding dry chemical to tank Fill dry chemical tank by completing the fol lowing ste...

Страница 13: ...ing and pour in measured amount of only ANSULITE AFFF Aqueous Film Forming Foam 3 Concentrate determined from the corresponding Recharge Guide on Page 8 NOTICE Prior to adding the concentrate to the t...

Страница 14: ...If valve is accidentally operated velocity of unrestricted escaping gas is forceful enough to cause injury especially about the face and head f Secure cylinder shipping cap Safety shipping cap must a...

Страница 15: ...strike pull lever when connecting hose to cylinder valve velocity of unrestricted escaping gas is forceful enough to cause injury especially about the face and head 15 Make certain visual inspection...

Страница 16: ...699 24 25 616 21 00 533 17 75 450 14 50 368 11 25 286 8 00 203 4 75 121 0 00 AFFF CONCENTRATE REQUIRED 6 3 Gal L Gal L ___ __ ___ __ 0 0 0 0 0 0 0 0 2 0 8 0 1 0 4 0 4 1 5 0 2 0 8 0 6 2 3 0 3 1 1 0 8 3...

Страница 17: ...e careful when removing fill cap s as tank s may be pres surized If fill cap has a red indicator stem in the up position pres sure must be relieved from tank If fill cap vent starts relieving pressure...

Страница 18: ...tank is filled with only free flowing ANSUL dry chemical to a level of not more than 6 inches 152 mm from bottom of the fill opening e Secure fill cap and hand tighten Make certain gasket is in place...

Страница 19: ...ose and check for abrasions cuts or weather checking b Examine nozzle openings for obstructions and operate nozzle triggers to check valves for free movement c Make certain hose couplings are tight an...

Страница 20: ...e Quick Connect Couplers Part No 22592 1 4 in Male Quick Connect Plug Part No 24560 Not Shown 3 8 in Male Quick Connect Plug Part No 24559 Not Shown 1 4 in Female Quick Connect Plug Part No 24561 Not...

Страница 21: ...on the low pressure side Note Each hose has a swivel at one end only remove hose at swivel end first Plug one side of tee 4 Install the appropriate quick connect plug to the low pressure regulator out...

Страница 22: ...re on the test gauge for one minute This reading must be within the dead set range listed on the specification chart Page 16 for the model regulator being tested If the reading falls outside the speci...

Страница 23: ...itrogen cylinder gauge for proper minimum pres sure Use the temperature correction chart on the next page to find the true tank pressure If the pressure is below the rec ommended level the cylinder mu...

Страница 24: ...shows that this is above the tempera ture correction line and the cylinder does not require replace ment cylinder varies with changes in temperature Accordingly the chart below has been prepared to d...

Страница 25: ...78707 78707 N A 5 Safety Disc and Washer 78711 78711 419102 6 Plug Safety Relief 78709 78709 N A 4 5 6 2 3 1 002563 RS Standard Valve 4 6 2 1 002564 RS Quick Opening Valve 5 5 7 6 3 1 4 002565 2 Pneum...

Страница 26: ...ent hole with a stiff unbreakable wire probe of lesser diam eter that vent hole Threads corroded nicked cross Replace destroying affected cap to prevent reuse threaded or worn Cut checked deformed sti...

Страница 27: ...pplicable parts list Nitrogen Cylinder Rust spots pits and corrosion deposits Clean corroded areas with a wire brush replacing cylinder if there is any corrosion penetration or repaint using a primer...

Страница 28: ...adjust screw or bracket replace bracket Worn or missing protective cylinder Replace webbing Part No 3360 or grommet Part No 8688 bracket webbing or grommet Wrong cylinder retaining bracket Replace br...

Страница 29: ...ting other than the hose to reel connection Pneumatic Actuation Corroded jammed or broken Clean repair to free movement or replace System puncture lever Dull bent or damaged puncture pin Replace pin m...

Страница 30: ...Page 1 001330 FOAM CONCENTRATES AND FOAM PRE MIX SOLUTIONS Field Inspection Manual...

Страница 31: ...ges of two 2 sample containers with labels can be purchased under Part No 428679 sTORage CONDITIONs Tyco Fire Protection Products recommends that its concen trates be stored at the temperatures indica...

Страница 32: ...Y axis This plotted curve will serve as the known baseline for the proportioning test Meters may have different scales and the plotted resolution should be as large as possible with the complete range...

Страница 33: ...TypICal CalIbRaTION CURve ResUlTs WheN UsINg paRT NO 405713 haNDhelD ReFRaCTOmeTeR Page 3 006876...

Страница 34: ...NOTes NOTes Page 4...

Страница 35: ...E TYPE LOT NO ______________________________________________________________________ METER TYPE ________ CONDUCTIVITY ________ REFRACTOMETER MODEL __________________________________ PERCENT FOAM SOLUT...

Страница 36: ...Part No 31274 07 Copyright 2011 Tyco Fire Protection0 Products All rights reserved TYCO FIRE PROTECTION PRODUCTS ONE STANTON STREET MARINETTE WI 54143 2542...

Страница 37: ...d in this material are marks and or registered marks Unauthorized use is strictly prohibited ITEM NO DESCRIPTION PART NO 1 Recharge Nameplate 438214 2 Nameplate AFFF Tank 14206 3 Nameplate Dry Chemica...

Отзывы: