Operating Instructions
At the time of installation and at periodic intervals (about every 3
months), a visual check of the pilot and burner flames should be
made to determine if they are burning properly. The burner
flames should be blue with yellow tips. A blue-orange flame is
characteristic of operation on liquefied petroleum (LP) gas. If the
burner flame does not appear as described.
5.8 Burner flame check
Note
IMPORTANT
- In the event of an emergency, turn off the
gas and electric (if applicable) to the appliance.
IMPORTANT- The water heater should be inspected
at a minimum annually by a qualified service
technician for damaged components and/or joints
not sealed. DO NOT operate this water heater if any
part is found damaged or if any joint is found not
sealed.
Warning
Water heaters are heat producing appliances. To avoid
damage or injury there shall be no materials stored
against the water heater or vent system, and proper
care shall be taken to avoid unnecessary contact
(especially by children) with the water heater and vent
system.
UNDER NO CIRCUMSTANCES SHALL FLAMMABLE
MATERIALS, SUCH AS GASOLINE OR PAINT
THINNER BE USED OR STORED IN THE VICINITY
OF THIS WATER HEATER, VENT SYSTEM OR IN
ANY LOCATION FROM WHICH FUMES COULD
REACH THE WATER HEATER OR VENT SYSTEM.
“HOT SURFACE” IGNITION (HSI) SYSTEM COMPONENTS
(EC380/1900 MODEL ONLY)
Fenwal 35-655305-121 Hot Surface Ignition Control, CE listed. 3
Trials for Ignition, 15 second pre-purge timing, 15 second igniter
heat up time, 4 second trial for ignition, 24 volt input to control.
Omron G2R-1A-T-AC24 relays (VDE listed) used for high
voltage switching of hot surface igniter and combustion blower
from the 24 volt outputs of the Fenwal control.
Saint Gobain 230 volt hot surface mini igniter.
Honeywell VR8615 gas valve (negative pressure regulator) with
matched venturi size for mixing gas with combustion air.
EBM RG148E (117 kW/hr. input) pre-mix combustion blower.
230 volts, 50/60 Hz.
Burner: Acotech (Bekaert Combustion Technology) Pre- mix
burner with stainless steel mesh outside knit.
Blocked Vent Pressure Switch: Honeywell IS20378-5770
normally closed pressure switch. Contacts open in the event of a
severe blockage of the flue outlet.
5.9 Hot surface