INSTRUCTIONS FOR COMMISSIONING
SECTION 4
31
TEMPERATURE
SETTING
ADJ USTING
TEMPORARY
TEMPERATURE
CHANGE
The lower the temperature the lower the chance of lime deposits (less maintenance).
The risk of scalding is also less (think of children, those with special needs and the
elderly). To avoid the formation of legionella bacteria the water heater temperature must
be set to at least 60
°
C. Thermostatic mixing valves must be fitted at point of use in some
applications. Health Guidance TM3 scheme refers.
If use is made of the programme for temporary temperature change (see page 16) the
new temperature is set as follows:
Press the reset button down for longer than 5 seconds, L appears in the left segment of
the display. The water heater temperature is shown in the 2 right segments, the new
temperature can be entered using the + and - buttons. The new temperature is set by
pressing the reset button once again, C00 appears in the display. Pressing the reset button
again switches the display back to the normal menu. If the new temperature is not set
within 1 minute the display switches back to the normal menu without recording the new
value.
The water heater temperature can be set between 40
°
C and 70
°
C using the + and -
buttons on the control panel. The maximum temperature for the Legionella flushing
programme is 75
º
C.
MAXXflo_Manual_Dec08_QX2 12/1/09 1:13 pm Page 34
Содержание CWH120/200
Страница 43: ......