INSTALLATION
SECTION 3
25
Terminal Positions with Minimum Distance
mm
A
Directly below an opening, air brick, opening window etc.
300
B
Above an opening, air brick, opening window etc.
300
C
Horizontally to an opening, air brick, opening window etc.
300
D
Below a gutter or sanitary pipework
75
E
Below the eaves
200
F
Below a balcony or carport roof
200
G
Above ground, roof or balcony level
300
H
From vertical drain/soil pipework
150
J
From an internal or external corner
300
K
From a surface or
boundary
facing the terminal
600
L
Vertically from a terminal on the same wall
1500
M
Horizontally from a terminal on the same wall
(30 & 60 kW) 300
(90 & 120 kW) 600
N
From a terminal facing the terminal
1200
P
From a opening in a carport (e.g. door, windows)
into the building
1200
Q
Above roof
500
R
From a vertical structure on a roof
500
S
Above flat roof
1000
FLUE SYSTEMS
Likely flue positions requiring
a flue terminal guard
F
G
M
Q
R
L
G
F
P
B
C
R
K,N
A
A
H
J
J
D E
S
G
Q
S
Fig. 9