APPENDICES
69
Step 3: For water heaters using two temperature sensors, pressing the “Select” button again displays the Lower Sensor
temperature reading. “Lower Sensor” will be displayed in the lower left side of the status window of the water heater
display.
SELECT
SET
Status
°F
idle
Operational
Lower Sensor
To Display Flame Sense Current of the Pilot Flame Sensor:
The pilot flame sense current is available only when the burners are in operation. Step 1: Make sure the status displays
“Heating” or draw enough hot water to start the burners. Step 2: Enter the “Service Mode” described previously. Step 3:
Press the “Select” button until a number value is displayed with “Flame Current” to the right of the number. The value
displayed is in microamps (
ȝ
A).
SELECT
SET
Status
Operational
Flame
Current
Heating
ȝ
A
To Display and Change Temperature Setpoint:
Step 1: In “Service Mode” press the “Select” button until “Setpoint” is shown in the water heater display
SELECT
SET
Status
°F
idle
setpoint
Operational
Page 15
Troubleshooting
Содержание 24/39
Страница 11: ...11 INSTALLATION SECTION 3 Standard Range Hi FloRange Fig3a Fig3b ...
Страница 19: ...19 INSTALLATION SECTION 3 Fig 6A Fig 7 ...
Страница 23: ...23 INSTALLATION SECTION 3 WATER CONNECTIONS Fig 9 Fig 10 ...
Страница 26: ...26 INSTALLATION SECTION 3 WATER CONNECTIONS Fig 13 Fig 14 ...
Страница 29: ...29 INSTALLATION SECTION 3 WATER CONNECTIONS Fig 17 Fig 18 ...
Страница 50: ...46 Hi Flo Model 32 143 Hi Flo Models 65 173 and 81 264 50 PARTS LIST AND ILLUSTRATIONS SECTION 9 ...
Страница 52: ...52 PARTS LIST AND ILLUSTRATIONS SECTION 9 Hi Flo Models 62 341 and 54 418 440 ...
Страница 56: ...56 PARTS LIST AND ILLUSTRATIONS SECTION 9 24 Volt Auto System Kit B258 24 Volt Auto System Kit B217 ...
Страница 93: ...93 Notes ...
Страница 94: ...94 Notes ...
Страница 95: ...95 Notes ...