InfiLink 200 Installation Guide
5
Warning
Be sure to have your grounds inspected before you begin the
installation process to be sure your municipality follows the National
Electrical Code. Many municipalities do not and often have
substandard electrical grounds.
An example of a substandard ground is a galvanized steel cold water
pipe. As the pipe corrodes, it does not act as a true ground. The corro-
sion acts as an insulator, raising the potential of the pipe with respect to
the ground.
When lightning strikes in the area of the installation, it drastically
changes the potential of the earth.
Surges of much lower potential also impact the reliability of Andover
Controls equipment.
Since properly grounded Andover Controls units respond to changes in
potential more rapidly than poorly grounded electrical systems, a poor-
ly grounded building tries to reach ground through the Andover
Controls system. The surge of current can destroy electronic compo-
nents on the controller board.