InfiLink 200 Installation Guide
9
Selecting the AC Input Voltage
The voltage is set to 115 V when shipped. To change the voltage, you
must reset the jumpers to the right of the AC power connection.
Table 1 shows jumper settings for the two voltages.
Table 1. Connecting Jumpers for AC Input Voltages
To change the voltage from 115 V to 230 V, proceed as follows:
1. Disconnect the jumper end from E2 and move it to E3 so it jumpers
TP2 to E3.
2. Disconnect the jumper end from E1 to E3 and entirely remove it
from the controller board.
Connecting the AC Power
Warning
Be sure the AC power is not connected to an electrical power source
while you are wiring the controller, or you could receive an electrical
shock that is life-threatening.
The AC power connection is in the lower left corner of the InfiLink 200.
You must wire the AC cable to the three screws on the far left.
115V Jumpers
230V Jumpers
From To
TP2 E2
E1 E3
From To
TP2 E3