Andi-Co  Australia  Pty  Ltd                                                                                                                  Service  manual  for  K1  portable  Series 

Fan blower 

Replace the fan blower if cracked, out of balance, or partially 

missing. 

Loose screws

 

Tighten them.

 

Fan motor noise. 

Worn bearings

 

Replace the motor if knocking sounds continue when running or 

loose, or the motor hums or noise appears to be internal while 

running.

 

Voltage 

Check voltage. Call Supply Authority if not within limits. 

Wiring

 

Check the wire connections, if loose, repair or replace the 

terminal. If wires are off, refer to wiring diagram for identification, 

and replace. Check wire locations. If not per wiring diagram, 

correct.

 

Main PCB failure

 

Check voltage of main PCB. Replace the main PCB if open.

 

Capacitor (Discharge 

capacitor before testing)

 

Check the capacitor.                                                                                           

Replace if not /-10% of manufacturers rating. Replace if 

shorted, open, or damaged. 

 

Room temp sensor

 

Check the temperature setting if not at the coolest (in cooling 

mode) or the warmest (in heating mode). Set it if not. 

 

Compressor will not 

run while fan motor 

runs. 

Compressor

 

Check the compressor for open circuit or ground. If open or 

grounded, replace the compressor.

 

Excessive noise. 

Copper tubing 

Remove the cabinet and carefully rearrange tubing not to contact 

cabinet, compressor, shroud and barrier. 

Water tank full 

Check and pour if the water tank is full. 

Water depth sensor if failure

 

Check and replace if failure.

 

Water pump failure

 

Check and replace if the pump if failure.

 

Water depth is over load in 

chassis

 

Check and drainage the water in the chassis by open the drainage 

hose on the chassis.

 

Water full alarm 

Water depth sensing 

structure

 

Check and replace or realign if the structure is failure.

 

Air filter 

Clean or replace if restricted. 

Air discharge pipe

 

Realign and assemble if the installation of the air discharging pipe 

failure. Replace if damaged.

 

Unit undersized

 

Determine if the unit is properly sized for the area to be cooled or 

heated.

 

Condenser and Evaporator

 

Clean or replace if restricted.

 

Water shower failure

 

Check the structure of water showering system and clean if 

blocked.

 

Fan motor

 

Check the fan capacitor and replace if not /-10% of 

manufactures rating.

 

Air flow

 

Clean or remove if any barrier is found to block the inlet/outlet 

wind flow of the unit.

 

Less refrigerant

 

Check the tubes for reasons of leakage. Recycle the refrigerant, 

correct the leakage points and recharge.

 

Cooling or heating 

feels not good 

Capillary tube

 

Regulate the flow if capillary tube and make the evaporating 

temperature appropriate if the evaporator is frosted. Replace if 

blocked. Repair joint if leaking.

 

Содержание MPK1-09CR-QB8

Страница 1: ...ebsite www andico com au Service manual CAUTION BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL ONLY FOR AUTHORISED SERVICE PERSONNEL MODELS MPK1 09CR QB8 MPK1 12ER QB6 MPK1 14ER...

Страница 2: ...NS 2 2 TROUBLE SHOOTING GUIDE 2 1 REFRIGERATION CYCLE DIAGRAM 4 2 2 ELECTRIC FUNCTION 4 2 3 TROUBLE SHOOTING GUIDE 6 3 WIRING DIAGRAM 3 1 WIRING DIAGRAM FOR COOLING ONLY MODELS 9 3 2 WIRING DIAGRAM FO...

Страница 3: ...d each exposed metallic part on the equipment at all the positions except OFF of the ROTARY SWITCH or POWER SWITCH 4 The value should be over 1M 1 3 FEATURES Water full alarm Anti icing function at co...

Страница 4: ...mp Low fan speed lamp Fan speed setting button Push this button to select fan speed High Med and Low POWE R Power button Push this button to start the unit FULL Water full alarm lamp Power lamp Remote...

Страница 5: ...tion for the compressor Water full alarm Anti icing function at cooling mode Temperature sensor err self diagnose Both temperature mode display 2 2 4 Protection 2 2 4 1 The compressor functions protec...

Страница 6: ...A TS 1 TS Electric heater OFF Temp down Tempup El ectric heater ON 2 2 9 Temperature display 2 2 9 1 The setting temperature will be displayed in Cooling and Heating mode The room temperature will be...

Страница 7: ...peed to low speed Replace the motor if the speed does not change Refrigerant The amount of the refrigerant is too much making the compressor load too big Recycle and recharge the refrigerant after che...

Страница 8: ...ange tubing not to contact cabinet compressor shroud and barrier Water tank full Check and pour if the water tank is full Water depth sensor if failure Check and replace if failure Water pump failure...

Страница 9: ...g Check and adjust the mode setting Compressor Check and replace if the compressor the over load protector or wiring is broken Electric heater failure Check and replace if the heater is damaged Over h...

Страница 10: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 9 3 2 FOR COOLING AND HEATING MODELS MPK1 12ER QB6 MPK1 14ER QB6...

Страница 11: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 10 3 3 ELECTRICAL CONTROL SCHEME...

Страница 12: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 11 3 4 MAIN CONTROL BOARD SCHEME...

Страница 13: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 12 3 5 DISPLAY BOARD SCHEME...

Страница 14: ...d disconnect the Air pipe from rear of the unit Move the unit to a replace where water can be poured Remove the rubber plug from back of the unit and drainage the water in from the unit Remove the wat...

Страница 15: ...ly just push the clasp and release the assembly Now it is easy to replace the display board Take care to release the connector which connected to the display board 4 4 To disassemble the front panel R...

Страница 16: ...attention to the wires in the enclosure 1 2 3 4 5 6 7 8 9 10 1 Terminate to display board 2 Terminate to condenser fan motor 3 Out put of transformer 4 Terminate to evaporator fan motor 5 Terminate to...

Страница 17: ...ng the air out frame Lift the frame up then pull the frame forward Remove the screws fixing the fan shell box Remove the fan motor fan scroll and blower wheel from the unit Take care to the wires for...

Страница 18: ...he screws fixing the evaporator Remove the screws fixing the condenser fan motor bracket Then remove the bracket with condenser fan motor and blower wheel from the unit 4 9 To repair the refrigerant s...

Страница 19: ...e cover Then remove the condenser fan scroll Now it is easy to repair the refrigerant system 4 10 To repair the water disposal system or replace the water depth switch or the pump Remove the screws fi...

Страница 20: ...screw fixing the water switch which controls the water in tank Press the clamp fixing the water switches which control the water in the chassis Press downward here Then remove the screws fixing the s...

Отзывы: