Andi-Co  Australia  Pty  Ltd                                                                                                                  Service  manual  for  K1  portable  Series 

 

5

on for 10 seconds, the whole unit will stop 

operation. The LED will display “P2” and the 

water full lamp will flash at 5Hz. After you have 

clear the problem, you should unplug the unit 

and plug again. Then the unit will be ready to 

operate. 

2.2.4.4.5 When the unit is standing by, if the unit 

displays “P1”, the pump will not operate. After 

the problem is cleared, the unit will be ready to 

operate. But if you push the power button, the 

unit will shut the “P1” display and shut down. 

2.2.5 Fan-only Mode Function Requirement 

2.2.5.1 The compressor and outdoor fan are OFF at 

Fan-only mode. 

2.2.5.2 The speed of indoor fan can be optionally 

chosen as High/Mid/Low. 

2.2.6 Cooling Mode Function Requirement 

2.2.6.1 The speed of indoor fan can be optionally 

selected as High/Mid/Low. 

2.2.6.2 The compressor operate as: 

O

C  

ro om t em per ature  (TA)

TS+1

TS

Comp ressor O N

Temp down

Temp up

Co mpressor O FF

 

2.2.7 Drying mode 

2.2.7.1 When the unit starts to operate in Drying 

mode, the compressor will start while the room 

temperature is over 13

o

C. After the compressor 

started, the compressor will operate as: 

O

C  

ro om t em per ature  (TA)

13 C

o

Comp ressor and outd o or
fan O N

Temp down

Temp up

Co mpressor and
ou t door fan OFF

15 C

o

 

2.2.7.2 The indoor fan will operate with high   

speed. The outdoor fan will operate with   

compressor.  

2.2.8 Heating mode 

2.2.8.1 The speed of indoor fan can be optionally 

chosen as High/Mid/Low. 

2.2.8.2 Electric heater operate as : 

O

C  

ro om t em per ature  (TA)

TS+1

TS

Elec t ric h eater O FF

Temp down

Temp up

El ec tric h eater O N

 

2.2.9 Temperature display 

2.2.9.1 The setting temperature will be displayed in 

Cooling and Heating mode. The room 

temperature will be displayed in Drying and Fan 

only mode. 

2.2.9.2 The setting temperature range is from 17

o

to 30

o

C or 62

o

F to 88

o

F. The display temperature 

range is from 10

o

C to 35

o

C or 48

o

F to 98

o

F. If the 

room temperature is lower than 10

o

C or 48

o

F, the 

display will be 10

o

C or 48

o

F.  

2.2.10 Timer Function 

2.2.10.1 The maximum length of Timer is 24 hours 

and the minimum is 0.5 hours. 

2.2.10.2 TIMER ON function: first turn OFF the unit, 

the unit will be automatically ON at the set time. 

2.2.10.3 TIMER OFF function: first turn ON the unit, 

the unit will be automatically OFF at the set time. 

2.2.10.4 TIMER ON/OFF function (ON TIMER is 

earlier than OFF TIMER): first turn OFF the unit, 

it will be automatically ON at set time, and later 

be OFF at the set time. 

2.2.10.5 TIMER OFF/ON function (OFF TIMER is 

earlier than ON TIMER): first turn ON the unit, it 

will be automatically OFF at set time, and later 

be ON at the set time. 

2.2.10.6 Timer function execution is applicable upon 

one operation only. 

2.2.10.7 Timer precision is less than 15 minutes. 

2.2.11 Auto restart function 

In case of a sudden power failure, this function 

automatically sets the unit to previous settings 

before the power failure when power returns. 

 

2.3 TROUBLESHOOTING GUIDE 

In general, possible trouble is classified in three kinds. One is called Starting Failure which is caused from 

an electrical defect, another is ineffective Air Conditioning caused by a defect in the refrigeration circuit and 

improper application, and the other is called the Structure Damage. 

Содержание MPK1-09CR-QB8

Страница 1: ...ebsite www andico com au Service manual CAUTION BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL ONLY FOR AUTHORISED SERVICE PERSONNEL MODELS MPK1 09CR QB8 MPK1 12ER QB6 MPK1 14ER...

Страница 2: ...NS 2 2 TROUBLE SHOOTING GUIDE 2 1 REFRIGERATION CYCLE DIAGRAM 4 2 2 ELECTRIC FUNCTION 4 2 3 TROUBLE SHOOTING GUIDE 6 3 WIRING DIAGRAM 3 1 WIRING DIAGRAM FOR COOLING ONLY MODELS 9 3 2 WIRING DIAGRAM FO...

Страница 3: ...d each exposed metallic part on the equipment at all the positions except OFF of the ROTARY SWITCH or POWER SWITCH 4 The value should be over 1M 1 3 FEATURES Water full alarm Anti icing function at co...

Страница 4: ...mp Low fan speed lamp Fan speed setting button Push this button to select fan speed High Med and Low POWE R Power button Push this button to start the unit FULL Water full alarm lamp Power lamp Remote...

Страница 5: ...tion for the compressor Water full alarm Anti icing function at cooling mode Temperature sensor err self diagnose Both temperature mode display 2 2 4 Protection 2 2 4 1 The compressor functions protec...

Страница 6: ...A TS 1 TS Electric heater OFF Temp down Tempup El ectric heater ON 2 2 9 Temperature display 2 2 9 1 The setting temperature will be displayed in Cooling and Heating mode The room temperature will be...

Страница 7: ...peed to low speed Replace the motor if the speed does not change Refrigerant The amount of the refrigerant is too much making the compressor load too big Recycle and recharge the refrigerant after che...

Страница 8: ...ange tubing not to contact cabinet compressor shroud and barrier Water tank full Check and pour if the water tank is full Water depth sensor if failure Check and replace if failure Water pump failure...

Страница 9: ...g Check and adjust the mode setting Compressor Check and replace if the compressor the over load protector or wiring is broken Electric heater failure Check and replace if the heater is damaged Over h...

Страница 10: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 9 3 2 FOR COOLING AND HEATING MODELS MPK1 12ER QB6 MPK1 14ER QB6...

Страница 11: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 10 3 3 ELECTRICAL CONTROL SCHEME...

Страница 12: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 11 3 4 MAIN CONTROL BOARD SCHEME...

Страница 13: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 12 3 5 DISPLAY BOARD SCHEME...

Страница 14: ...d disconnect the Air pipe from rear of the unit Move the unit to a replace where water can be poured Remove the rubber plug from back of the unit and drainage the water in from the unit Remove the wat...

Страница 15: ...ly just push the clasp and release the assembly Now it is easy to replace the display board Take care to release the connector which connected to the display board 4 4 To disassemble the front panel R...

Страница 16: ...attention to the wires in the enclosure 1 2 3 4 5 6 7 8 9 10 1 Terminate to display board 2 Terminate to condenser fan motor 3 Out put of transformer 4 Terminate to evaporator fan motor 5 Terminate to...

Страница 17: ...ng the air out frame Lift the frame up then pull the frame forward Remove the screws fixing the fan shell box Remove the fan motor fan scroll and blower wheel from the unit Take care to the wires for...

Страница 18: ...he screws fixing the evaporator Remove the screws fixing the condenser fan motor bracket Then remove the bracket with condenser fan motor and blower wheel from the unit 4 9 To repair the refrigerant s...

Страница 19: ...e cover Then remove the condenser fan scroll Now it is easy to repair the refrigerant system 4 10 To repair the water disposal system or replace the water depth switch or the pump Remove the screws fi...