ROOM AIRCONDITIONER VOLTAGE LIMITS:
NAMEPLATE RATING
MINIMUM
MAXIMUM
220~240V
196V
253V
PROBLEM
POSSIBLE CAUSE
REMEDY
Power failure
Check the power supplier if the power supplier is supplied to the
unit. Check the power cord and correct if damaged.
Transformer (Discharge
transformer before testing)
Check resistance between the two input/output lines on
transformer. Replace the transformer if either of the input/output is
open or the transformer is damaged.
No power display
on panel or any one
of the buttons
failure.
Display board or main PCB
failure
Check the voltage on display board. Replace the display board if it
is +5V else replace the main PCB.
Remote control
failure.
Battery failure
Check the voltage of battery. Replace batteries if the voltage is
lower than 2.3V.
Check voltage. Call an electrician if not within limits.
Test capacitor.
Replace if not /-10% of manufacture's rating.
Check bearings. Replace the motor if the blower wheel cannot
rotate freely.
Fan motor runs
intermittently
Cycles on overload.
Pay attention to any change from high speed to low speed.
Replace the motor if the speed does not change.
Refrigerant
The amount of the refrigerant is too much, making the compressor
load too big. Recycle and recharge the refrigerant after checking
for the reason.
Compressor stops
instantly after
startup.
Compressor
The compressor is blocked inside. Replace after checking for the
reason.
No power
Check voltage at electrical outlet. Correct if none.
Water alarm
Check and correct if water alarm happens.
Power supply cord
Check voltage at the power cord terminal on Main PCB. Replace
the power cord if none.
Transformer (Discharge
transformer before testing)
Check resistance between the two input/output lines on
transformer. Replace the transformer if either of the input/output is
open or the transformer is damaged.
Wire disconnected or
connection loose
Connect wire. Refer to wiring diagram for terminal identification.
Repair or replace loose terminal.
Main PCB failure
Select fan speed and Check the voltage on main PCB. Replace
the main PCB if no voltage in anyone.
Capacitor (Discharge
capacitor before testing)
Test capacitor.
Replace if not /-10% of manufacture's rating. Replace if
shorted, open or damaged.
Fan motor will not
run.
Will not rotate
Fan blower hitting scroll. Realign assembly.
Check fan motor bearings. Replace the motor if motor shaft do not
rotate.