Andi-Co  Australia  Pty  Ltd                                                                                                                  Service  manual  for  K1  portable  Series 

ROOM AIRCONDITIONER VOLTAGE LIMITS: 

NAMEPLATE RATING 

MINIMUM 

MAXIMUM 

220~240V 

 

196V 

 

253V 

 

 

 

PROBLEM

 

POSSIBLE CAUSE

 

REMEDY

 

Power failure 

Check the power supplier if the power supplier is supplied to the 

unit. Check the power cord and correct if damaged. 

Transformer (Discharge 

transformer before testing) 

Check resistance between the two input/output lines on 

transformer. Replace the transformer if either of the input/output is 

open or the transformer is damaged. 

No power display 

on panel or any one 

of the buttons 

failure. 

Display board or main PCB 

failure 

Check the voltage on display board. Replace the display board if it 

is +5V else replace the main PCB.   

Remote control 

failure.

 

Battery failure 

Check the voltage of battery. Replace batteries if the voltage is 

lower than 2.3V. 

Check voltage. Call an electrician if not within limits. 

Test capacitor.                                                    

Replace if not /-10% of manufacture's rating.

 

Check bearings. Replace the motor if the blower wheel cannot 

rotate freely.

 

Fan motor runs 

intermittently 

Cycles on overload. 

Pay attention to any change from high speed to low speed. 

Replace the motor if the speed does not change.

 

Refrigerant 

The amount of the refrigerant is too much, making the compressor 

load too big. Recycle and recharge the refrigerant after checking 

for the reason. 

Compressor stops 

instantly after 

startup. 

Compressor

 

The compressor is blocked inside. Replace after checking for the 

reason.

 

No power 

Check voltage at electrical outlet. Correct if none. 

Water alarm

 

Check and correct if water alarm happens.

 

Power supply cord

 

Check voltage at the power cord terminal on Main PCB. Replace 

the power cord if none.

 

Transformer (Discharge 

transformer before testing)

 

Check resistance between the two input/output lines on 

transformer. Replace the transformer if either of the input/output is 

open or the transformer is damaged.

 

Wire disconnected or 

connection loose

 

Connect wire. Refer to wiring diagram for terminal identification. 

Repair or replace loose terminal.

 

Main PCB failure

 

Select fan speed and Check the voltage on main PCB. Replace 

the main PCB if no voltage in anyone.

 

Capacitor (Discharge 

capacitor before testing)

 

Test capacitor.                                                    

Replace if not /-10% of manufacture's rating. Replace if 

shorted, open or damaged.

 

Fan motor will not 

run. 

Will not rotate

 

Fan blower hitting scroll. Realign assembly.                       

Check fan motor bearings. Replace the motor if motor shaft do not 

rotate.

 

Содержание MPK1-09CR-QB8

Страница 1: ...ebsite www andico com au Service manual CAUTION BEFORE SERVICING THE UNIT READ THE SAFETY PRECAUTIONS IN THIS MANUAL ONLY FOR AUTHORISED SERVICE PERSONNEL MODELS MPK1 09CR QB8 MPK1 12ER QB6 MPK1 14ER...

Страница 2: ...NS 2 2 TROUBLE SHOOTING GUIDE 2 1 REFRIGERATION CYCLE DIAGRAM 4 2 2 ELECTRIC FUNCTION 4 2 3 TROUBLE SHOOTING GUIDE 6 3 WIRING DIAGRAM 3 1 WIRING DIAGRAM FOR COOLING ONLY MODELS 9 3 2 WIRING DIAGRAM FO...

Страница 3: ...d each exposed metallic part on the equipment at all the positions except OFF of the ROTARY SWITCH or POWER SWITCH 4 The value should be over 1M 1 3 FEATURES Water full alarm Anti icing function at co...

Страница 4: ...mp Low fan speed lamp Fan speed setting button Push this button to select fan speed High Med and Low POWE R Power button Push this button to start the unit FULL Water full alarm lamp Power lamp Remote...

Страница 5: ...tion for the compressor Water full alarm Anti icing function at cooling mode Temperature sensor err self diagnose Both temperature mode display 2 2 4 Protection 2 2 4 1 The compressor functions protec...

Страница 6: ...A TS 1 TS Electric heater OFF Temp down Tempup El ectric heater ON 2 2 9 Temperature display 2 2 9 1 The setting temperature will be displayed in Cooling and Heating mode The room temperature will be...

Страница 7: ...peed to low speed Replace the motor if the speed does not change Refrigerant The amount of the refrigerant is too much making the compressor load too big Recycle and recharge the refrigerant after che...

Страница 8: ...ange tubing not to contact cabinet compressor shroud and barrier Water tank full Check and pour if the water tank is full Water depth sensor if failure Check and replace if failure Water pump failure...

Страница 9: ...g Check and adjust the mode setting Compressor Check and replace if the compressor the over load protector or wiring is broken Electric heater failure Check and replace if the heater is damaged Over h...

Страница 10: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 9 3 2 FOR COOLING AND HEATING MODELS MPK1 12ER QB6 MPK1 14ER QB6...

Страница 11: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 10 3 3 ELECTRICAL CONTROL SCHEME...

Страница 12: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 11 3 4 MAIN CONTROL BOARD SCHEME...

Страница 13: ...Andi Co Australia Pty Ltd Service manual for K1 portable Series 12 3 5 DISPLAY BOARD SCHEME...

Страница 14: ...d disconnect the Air pipe from rear of the unit Move the unit to a replace where water can be poured Remove the rubber plug from back of the unit and drainage the water in from the unit Remove the wat...

Страница 15: ...ly just push the clasp and release the assembly Now it is easy to replace the display board Take care to release the connector which connected to the display board 4 4 To disassemble the front panel R...

Страница 16: ...attention to the wires in the enclosure 1 2 3 4 5 6 7 8 9 10 1 Terminate to display board 2 Terminate to condenser fan motor 3 Out put of transformer 4 Terminate to evaporator fan motor 5 Terminate to...

Страница 17: ...ng the air out frame Lift the frame up then pull the frame forward Remove the screws fixing the fan shell box Remove the fan motor fan scroll and blower wheel from the unit Take care to the wires for...

Страница 18: ...he screws fixing the evaporator Remove the screws fixing the condenser fan motor bracket Then remove the bracket with condenser fan motor and blower wheel from the unit 4 9 To repair the refrigerant s...

Страница 19: ...e cover Then remove the condenser fan scroll Now it is easy to repair the refrigerant system 4 10 To repair the water disposal system or replace the water depth switch or the pump Remove the screws fi...

Страница 20: ...screw fixing the water switch which controls the water in tank Press the clamp fixing the water switches which control the water in the chassis Press downward here Then remove the screws fixing the s...

Отзывы: