background image

TABLE 1 

– DIAGNOSTIC CODES

Diagnostic 

Code

Failure Mode

Action

Reset

E1

Internal Humidity or 

Temperature Sensor 

Open or Shorted

1. 

Check the connection between the sensor board and control board�

2. 

If connection okay, replace sensor board, Part No� 5460�

Cycle Power

E3

Model A77 

Remote Control 

Communication Loss

1. 

Check connections between Model A77 and dehumidifier control board� Terminals should be fully 

inserted and secured in the control board and Model A77 control terminals�

2. 

If connections are correct and secure, turn off the dehumidifier and remove the Model A77� Use a 

short section of 4-wire cable to reconnect the Model A77 to the control board� Turn the dehumidifier 

back on and increase the dryness level setting on the Model A77� If the dehumidifier turns on, the 

problem is with the wiring between the dehumidifier and control�

3. 

If the dehumidifier does not turn on, call Technical Support�

Self-Correcting

E4

Insufficient Capacity

1. 

Check the frost sensor connection at the power board� Terminal should be fully seated on the power 

board pins�

2. 

Remove the side access panel and verify that the sensor is secured to the suction line�

3. 

If the sensor is connected and secured to the refrigeration line proceed to the next step� 

4. 

Reset the fault by cycling power to the dehumidifier�

5. 

Turn the humidity setting down (below room/home humidity level) to make a dehumidification call� 

6. 

Allow the fan and compressor to run for approximately 10-15 minutes and then enter diagnostic 

test mode by simultaneously pressing the UP ARROW and MODE buttons for 3 seconds� The LCD 

will display the temperature measured by the internal sensor while also displaying AIR SAMPLING 

and ON, the humidity measured by the internal sensor while also displaying %RH and ON, and the 

frost sensor temperature while also displaying ON� Scroll through these values and by using the UP/

DOWN arrow buttons� 

7. 

Record values and call Technical Support�

Cycle Power

E5

High Temperature 

Thermistor Failure

1. 

Check the high temperature sensor connection at the power board� Terminal should be fully seated 

on the power board pins�

2. 

Remove the side access panel and verify the sensor is not damaged and connected to the 

refrigeration line coming from the compressor�

3. 

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part 

No� 5456 – contact Technical Support to confirm�

Cycle Power

E6

Low Temperature 

Thermistor Failure

1. 

Check the low temperature sensor connection at the power board�

2. 

Remove the side access panel and verify the sensor is not damaged and connected to the suction line�

3. 

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part 

No� 5455 – contact Technical Support to confirm�

Self-Correcting

E7

Float Switch Open

1. 

Empty the condensate pan�

2. 

Check the float switch connection at the control board�

3. 

If not using a float switch, verify jumper is between float switch terminals on dehumidifier control board�

4. 

If the problem persists, replace the float switch�

Self-Correcting

E8

Inlet Air Temperature 

Out of 50°F – 104°F 

range or dew point 

below 40°F

1. 

Verify all ductwork is properly sealed�

2. 

If no signs of leak points, contact Technical Support�

Self-Correcting

TROUBLESHOOTING

Technical Support is available Monday through Friday, 7:00 a�m� to 5:00 p�m� CST, at (800) 972-3710� Use the guides on the following pages to identify 
and correct system faults� Contact Technical Support before replacing the unit or any components and for additional troubleshooting�

DIAGNOSTIC CODES

When an error occurs, the Diagnostic Code along with SERVICE REQUIRED will be displayed on the control 
screen� If a 5818 Alert Light is used, the light will turn on when an error occurs�

90-1854

9

Содержание A95F

Страница 1: ...tions Pool chemicals can damage the dehumidifier 4 Do not use solvents or cleaners on or near the circuit board Chemicals can damage circuit board components 5 Wait 24 hours before running the unit if...

Страница 2: ...PERATION 8 Using the Dehumidifier Control 8 Using the Model A77 Remote Control 8 TROUBLESHOOTING 9 Table 1 Diagnostic Codes 9 Table 2 Troubleshooting Guide 10 SERVICE PARTS 11 LIMITED WARRANTY 12 SPEC...

Страница 3: ...emoval of the side panel shown Allow sufficient space for service on this side of the unit Always install the dehumidifier in a condensate pan when locating in or over a finished space CLIP OFF PLASTI...

Страница 4: ...l surface is required to ensure proper drainage from the dehumidifier CONDENSATE PAN CONDENSATE PUMP AND FLOAT SWITCH A condensate pan is recommended when locating in or above a finished space or susp...

Страница 5: ...en to secure 4 Restore dehumidifier power There is a delay of three minutes after restoring power before the dehumidifier will respond to the control 5 Go to REMOTE CONTROL on page 6 to configure the...

Страница 6: ...r for the installed application Use the UP or DOWN buttons to select items and use MODE to switch to the next set up option To exit installer set up all options must be scrolled through using the MODE...

Страница 7: ...red the dehumidifier and all of the wired components will turn on and off during Installer Test Mode to demonstrate that all are properly operating Installer Test Mode lasts for four 4 minutes If the...

Страница 8: ...he setting the blowers turn off and the display returns to showing the RH setting 4 The dehumidifier will sample again after the number of minutes selected during the Air Sampling portion of the Syste...

Страница 9: ...sensor temperature while also displaying ON Scroll through these values and by using the UP DOWN arrow buttons 7 Record values and call Technical Support Cycle Power E5 High Temperature Thermistor Fai...

Страница 10: ...ty condensate pan If no float switch installed check that the jumper is installed at the float switch terminals on the control board Coil frosting defrost Lack of or reduced airflow Check dehumidifier...

Страница 11: ...6 Wire Harness Power Deh 5454 7 Sensor Low Temperature Deh 5455 8 Sensor High Temperature Deh 5456 No Part Description Part No 9 Capacitor 45MFD 370VAC 70pt 95pt Deh compressor 5458 10 Capacitor 12MFD...

Страница 12: ...LIMITED IN DURATION TO THE AFORESAID FIVE YEAR PERIOD RESEARCH PRODUCTS CORPORATION S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OTHER THAN DAMAGES FOR PERSONAL INJURIES RESULTING FROM ANY BREA...

Отзывы: