START UP AND SEQUENCE OF OPERATION

USING THE DEHUMIDIFIER CONTROL

1. 

Press the ON/OFF button to turn the dehumidifier control ON� The display will show the current setting, and the dehumidifier blower will turn on 
to start sampling the air�

   The setting will be replaced by the measured humidity and “AIR SAMPLING” will show on the display�

2. 

Use the UP or DOWN button to adjust the humidity setting as desired� 

3. 

After three (3) minutes of sampling, the measured humidity will be compared to the setting:

a. 

If the humidity is above the setting, the dehumidifier compressor turns on and “AIR SAMPLING” will be replaced by “DEHUMIDIFYING”� The 
compressor remains on until the measured humidity falls 3% RH below the setting�

b. 

If the measured humidity is below the setting, the blowers turn off and the display returns to showing the RH setting�

4. 

The dehumidifier will sample again after the number of minutes selected during the Air Sampling portion of the System Set Up (see page 7), or 
any time the humidity setting is lowered�

USING THE MODEL A77 REMOTE CONTROL

1. 

Press the ON/OFF button to turn the dehumidifier control ON� “REMOTE” will show on the display to indicate that an external control is wired to 
the dehumidifier�

2. 

At the Model A77, press the ON button; the Model A77 will display the measured RH�

3. 

Use the UP or DOWN button on the Model A77 to adjust the humidity setting as desired� 

4. 

If the RH measured by the Model A77 rises above the setting, the dehumidifier will turn on� “DEHUMIDIFYING” will appear on the dehumidifier 
control display to show that the Model A77 is calling for dehumidification� The dehumidifier will turn off when the RH measured by the Model A77 
drops 3% RH below the setting�

8

Содержание A95F

Страница 1: ...tions Pool chemicals can damage the dehumidifier 4 Do not use solvents or cleaners on or near the circuit board Chemicals can damage circuit board components 5 Wait 24 hours before running the unit if...

Страница 2: ...PERATION 8 Using the Dehumidifier Control 8 Using the Model A77 Remote Control 8 TROUBLESHOOTING 9 Table 1 Diagnostic Codes 9 Table 2 Troubleshooting Guide 10 SERVICE PARTS 11 LIMITED WARRANTY 12 SPEC...

Страница 3: ...emoval of the side panel shown Allow sufficient space for service on this side of the unit Always install the dehumidifier in a condensate pan when locating in or over a finished space CLIP OFF PLASTI...

Страница 4: ...l surface is required to ensure proper drainage from the dehumidifier CONDENSATE PAN CONDENSATE PUMP AND FLOAT SWITCH A condensate pan is recommended when locating in or above a finished space or susp...

Страница 5: ...en to secure 4 Restore dehumidifier power There is a delay of three minutes after restoring power before the dehumidifier will respond to the control 5 Go to REMOTE CONTROL on page 6 to configure the...

Страница 6: ...r for the installed application Use the UP or DOWN buttons to select items and use MODE to switch to the next set up option To exit installer set up all options must be scrolled through using the MODE...

Страница 7: ...red the dehumidifier and all of the wired components will turn on and off during Installer Test Mode to demonstrate that all are properly operating Installer Test Mode lasts for four 4 minutes If the...

Страница 8: ...he setting the blowers turn off and the display returns to showing the RH setting 4 The dehumidifier will sample again after the number of minutes selected during the Air Sampling portion of the Syste...

Страница 9: ...sensor temperature while also displaying ON Scroll through these values and by using the UP DOWN arrow buttons 7 Record values and call Technical Support Cycle Power E5 High Temperature Thermistor Fai...

Страница 10: ...ty condensate pan If no float switch installed check that the jumper is installed at the float switch terminals on the control board Coil frosting defrost Lack of or reduced airflow Check dehumidifier...

Страница 11: ...6 Wire Harness Power Deh 5454 7 Sensor Low Temperature Deh 5455 8 Sensor High Temperature Deh 5456 No Part Description Part No 9 Capacitor 45MFD 370VAC 70pt 95pt Deh compressor 5458 10 Capacitor 12MFD...

Страница 12: ...LIMITED IN DURATION TO THE AFORESAID FIVE YEAR PERIOD RESEARCH PRODUCTS CORPORATION S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OTHER THAN DAMAGES FOR PERSONAL INJURIES RESULTING FROM ANY BREA...

Отзывы: