SYSTEM SET-UP & CHECKOUT

Skip set up and proceed to 

INSTALLER TEST MODE

 on page 7 unless:

•  A Model A77 or other external control is to be installed

•  changing the air sampling rate

1. 

Make sure the wire access cover has been snapped back onto the 
on-board control�

2. 

Plug unit in and turn power switch to ON�

3. 

The on-board control screen should display OFF�

90-1854

NOTE:

 If the display backlight is not on, the first button press (any 

button) will only turn on the backlight� Press the button a second time 
to achieve function� 

4. 

Hold the MODE button on the on-board control for 3 seconds to 
enter the Installer Set-up Menu�

5. 

Navigate through the following screens to set up the dehumidifier 
for the installed application�

   Use the UP or DOWN buttons to select items and use MODE to 

switch to the next set-up option� To exit installer set-up, all options 
must be scrolled through using the MODE button� 

6. 

After the installer set up options have been completed, DONE will 
blink for 3 seconds and the control will return to the OFF screen�

90-1854

90-1854

REMOTE CONTROL

90-1854

If not installing an A77, leave 
DISABLED and press MODE to go 
to the next screen�� 
 
 

90-1854

If installing an A77, use the UP or 
DOWN button to select ENABLED, 
then press MODE to go to the next 
screen� 
 

EXTERNAL CONTROL

90-1854

If using the dehumidifier on-board 
control, leave DISABLED and press 
MODE to go to the next screen� 
 
 

90-1854

If using a Model 8800 series 
thermostat or alternate control as 
an external control, use the UP or 
DOWN button to select ENABLED, 
then press MODE to go to the next 
screen�

6

Содержание A95F

Страница 1: ...tions Pool chemicals can damage the dehumidifier 4 Do not use solvents or cleaners on or near the circuit board Chemicals can damage circuit board components 5 Wait 24 hours before running the unit if...

Страница 2: ...PERATION 8 Using the Dehumidifier Control 8 Using the Model A77 Remote Control 8 TROUBLESHOOTING 9 Table 1 Diagnostic Codes 9 Table 2 Troubleshooting Guide 10 SERVICE PARTS 11 LIMITED WARRANTY 12 SPEC...

Страница 3: ...emoval of the side panel shown Allow sufficient space for service on this side of the unit Always install the dehumidifier in a condensate pan when locating in or over a finished space CLIP OFF PLASTI...

Страница 4: ...l surface is required to ensure proper drainage from the dehumidifier CONDENSATE PAN CONDENSATE PUMP AND FLOAT SWITCH A condensate pan is recommended when locating in or above a finished space or susp...

Страница 5: ...en to secure 4 Restore dehumidifier power There is a delay of three minutes after restoring power before the dehumidifier will respond to the control 5 Go to REMOTE CONTROL on page 6 to configure the...

Страница 6: ...r for the installed application Use the UP or DOWN buttons to select items and use MODE to switch to the next set up option To exit installer set up all options must be scrolled through using the MODE...

Страница 7: ...red the dehumidifier and all of the wired components will turn on and off during Installer Test Mode to demonstrate that all are properly operating Installer Test Mode lasts for four 4 minutes If the...

Страница 8: ...he setting the blowers turn off and the display returns to showing the RH setting 4 The dehumidifier will sample again after the number of minutes selected during the Air Sampling portion of the Syste...

Страница 9: ...sensor temperature while also displaying ON Scroll through these values and by using the UP DOWN arrow buttons 7 Record values and call Technical Support Cycle Power E5 High Temperature Thermistor Fai...

Страница 10: ...ty condensate pan If no float switch installed check that the jumper is installed at the float switch terminals on the control board Coil frosting defrost Lack of or reduced airflow Check dehumidifier...

Страница 11: ...6 Wire Harness Power Deh 5454 7 Sensor Low Temperature Deh 5455 8 Sensor High Temperature Deh 5456 No Part Description Part No 9 Capacitor 45MFD 370VAC 70pt 95pt Deh compressor 5458 10 Capacitor 12MFD...

Страница 12: ...LIMITED IN DURATION TO THE AFORESAID FIVE YEAR PERIOD RESEARCH PRODUCTS CORPORATION S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OTHER THAN DAMAGES FOR PERSONAL INJURIES RESULTING FROM ANY BREA...

Отзывы: