![AND Multi Function Weighing Indicator AD-4402 Скачать руководство пользователя страница 52](http://html.mh-extra.com/html/and/multi-function-weighing-indicator-ad-4402/multi-function-weighing-indicator-ad-4402_instruction-manual_2941316052.webp)
Page
50
AD-4402
7.3.6.
7.3.6.
7.3.6.
7.3.6.
RRRRecipe
ecipe
ecipe
ecipe SSSSequence
equence
equence
equence
The recipe sequence mixes preset final weights of multiple materials that are stored
in a recipe code. One hundred recipe codes can be stored in the indicator. A recipe
code can store ten material codes and the order to mix them.
There are the following two modes that can be selected at
Recipe mode
.
Semi-automatic
[
5qf- 8
] [
1
] The mode that uses (external) start commands for
each material.
Automatic
[
5qf- 8
] [
2
] The mode that does not need each start command.
When an under weight occurs in a material, an error
code
SQ.ERR 2
is displayed and the sequence
stops.
Concerning Parameters of the Function
Selecting normal batching of built-in automatic program mode.
[
5q f- 8
]
Recipe mode
[
5q f- 8
] [
1
]
Semi-automatic mode
, or
[
5q f- 8
] [
2
]
Automatic mode
[Function] - [Function setting] - [Sequence] - [Basic] - [Recipe mode]
Setting the display to zero automatically when starting the recipe sequence.
[
5q f-16
]
[Function] - [Function setting] - [Sequence] - [Control] - [Recipe start action]
Clearing tare values, mixing them and discharging them when finishing the recipe
sequence.
[
5q f- 17
]
[Function] - [Function setting] - [Sequence] - [Control] - [Recipe finish action]
Changing the width of the finish signal output of the recipe sequence.
[
5q f-45
]
[Function] - [Function setting] - [Sequence] - [Timer] - [Recipe finish output
on]
Calculating totals in each recipe code.
[
5q f-62
]
[Function] - [Function setting] - [Sequence] - [Total] - [Automatic recipe code
total]
Weighing a single material code during a recipe sequence
When it is necessary to weigh the material code temporarily during a recipe sequence,
use recipe prohibition command of the external I/O or OP-05. When the prohibition
works, the material code can be used and total of the recipe is not total.
Setting of the I/O.
[
1n f-
nn] [
49
] Recipe interrupt (Prohibition of recipe sequence)
nn: terminal number of I/O.
[Function] - [Function setting] - [Control I/O] - [Input]
Содержание Multi Function Weighing Indicator AD-4402
Страница 1: ...ふ Multi Function Weighing Indicator WM PD4000243A This is a hazard alert mark ...
Страница 40: ...Page 38 AD 4402 Blank page ...
Страница 62: ...Page 60 AD 4402 Blank page ...
Страница 145: ...AD 4402 Page 143 MEMO ...