4
INSTALLATION
MOUNTING
Mount the unit in a DRY location. Mount the unit in a ventilated area. Allow at least 1 inch of
clearance around the unit for adequate cooling.
It is NOT recommended that the unit be secured until it has been tested under the intended
load.
CAUTION:
Do not mount the unit where explosive gases may accumulate as a
slight arc may occur when the power leads are connected, and in the
unlikely event of a failure, sparks may be generated inside the unit.
POWER CONNECTION
Use a voltmeter to measure the input voltage to ensure the voltage of the battery is within the
Input Voltage range printed on the front of the unit.
The unit is supplied with two 5 foot power cables. This should be adequate to connect to a
power source.
Connect the wires as follows:
•
Red to Positive
•
Black to Negative
If you must extend the cable:
•
Use the smallest extension length possible.
•
Use at least AWG 8 gauge conductors.
•
Splice and solder the joint.
•
Protect the joints with heat shrink tubing.
Before plugging any devices into the unit, turn it on.
If the power switch is illuminated, the unit is working properly.