General
Battery Banks
1 or 2
Stages
2 or 3
Transient Resp.
< 2V for 10A Surge
Efficiency
> 75 % @ maximum output
Temp. Range
-25°C to +40°C: Continuous Operation
+40°C to +85°C: Intermittent Operation
Isolation
Input-Output & Input-Case: 1500 VDC
Output-Case 500 VDC (1500Vdc @ 48 V Out)
Length
14.5 in / 36.8 cm
Width
9.9 in / 25.1 cm
Height
3.0 in / 14.0 cm
Clearance
1 Inch (2.5 cm) all around
Material
Marine Grade Aluminum
Finish
Black Anodize / Black Powder Epoxy
Fastenings
18-8 Stainless
Weight
7.2 lb / 3.3 kg
* Specifications subjects to change without notice.
* This is Analytic Systems’ suggested range. Please consult your battery manufacturer for their recommendations.
Output
Nominal Voltage
12 VDC
24 VDC
32 VDC
48 VDC
Float Voltage
13.6 ± 0.05 VDC 27.2 ± 0.05 VDC 36.3 ± 0.05 VDC 54.4 ± 0.05 VDC
Absorption Voltage
14.4 VDC VDC
28.8 VDC
38.4 VDC
57.6 VDC
Charging Amps
40 A
22 A
16.5 A
11 A
Absorption to Float
6.0 Amps
3.3 Amps
2.48 Amps
1.65 Amps
Battery Size (Amp Hours)*
160 – 240
88 – 132
66 – 99
44 - 66
Output Adjust
± 1.0 Volts
Noise on Output
< 50 mV
Output Crowbar
16.0 ± 0.5 V
32.0 ± 1.0 V
42.7 ± 1.3 V
63.9 ± 2.0 V
Equalize Voltage
15.5 VDC
31 VDC
41.3 VDC
62 VDC
Temperature Compensation Coefficient
-30mV /
o
C
-60mV /
o
C
-80mV /
o
C
-120mV /
o
C
Output Fuses
ATC-40 x 2
ATC-30 x 2
ATC-20 x 2
ATC-15 x 2
Specifications
Input
Nominal Voltage
110 VAC
220 VAC
Actual Voltage
90 – 133 VAC
180 - 265 VAC
Frequency
45 - 65 Hz
Noise on Input
< 50 mV
Input Amps (max)
9.3 A
4.7 A
Input Fuse
MDA-12
MDA-6