Analox 50 – Carbon Dioxide Analyser – User Manual 

 
 

 

Document Ref:  A50-811-19 – September 2014 

 

 

   

 

      Page 9 

 

 

 

 

 

 

 

 

1. 

SAFETY NOTES  

 

Every gas monitor installation should be risk assessed.  The correct 
location of monitor(s) must consider the potential sources of gas leaks 
and the location of expected human occupation in the area.   Where 
large areas must be monitored, it is often advised that no single monitor 
should cover a volume in excess of 80m3.  The installation of more 
monitors should be considered where an area is complex in shape, filled 
with obstacles, has a lack ventilation or air circulation, or if there are 
dead zones where gas can collect 
 

a)  The Ax 50

TM

 must be installed according to these instructions which 

should be read entirely before commencing installation. 

b)  For your convenience the Remote Alarm Repeater is pre-wired to the 

Ax 50

TM

 sensor unit. 

c) If you need to disconnect the cable for ease of installation. 

DISCONNECT FROM THE REMOTE ALARM REPEATER END 

d)  The system MUST NOT be switched on until all connections have been 

correctly made. 

e)  We do not recommend you access the main unit.  Potentially lethal 

voltages exist within the Ax 50

TM

.  It should only be opened by a 

Qualified Technician, and must be isolated from the electrical supply 
before opening. 

f) The 

Ax 

50

TM

 does not require routine maintenance.  All you need to do 

is check that the green light is flashing and press the mode button 
periodically to make sure that the Horn and alarm lights are functioning. 

 

2. 

PACKAGING CONTENTS CHECK 

 
The following items are enclosed: 
 

a) Ax 50

TM

 main unit, with power lead to a plug (where necessary) 

b)  User manual for standard Ax 50

TM

 

c) Test certificate 
d)  Rawl plugs and screws for wall mounting  
e) Remote Alarm Repeater and 8 metres of interconnecting cable 

connected to the Ax 50

TM

f) Warning 

label 

 

Содержание Ax 50

Страница 1: ...kshire TS9 5PT UK T 44 0 1642 711400 F 44 0 1642 713900 W www analox net E info analox net This support line is closed on UK public holidays Ax 50 Carbon Dioxide Analyser WARNING Please read the safet...

Страница 2: ......

Страница 3: ...Analox 50 Carbon Dioxide Analyser User Manual Document Ref A50 811 19 September 2014 Page 2 How to fit an Ax 50TM 2 450mm 1...

Страница 4: ...Analox 50 Carbon Dioxide Analyser User Manual Document Ref A50 811 19 September 2014 Page 3 3 4...

Страница 5: ...Analox 50 Carbon Dioxide Analyser User Manual Document Ref A50 811 19 September 2014 Page 4 5 6...

Страница 6: ...Analox 50 Carbon Dioxide Analyser User Manual Document Ref A50 811 19 September 2014 Page 5 7 8...

Страница 7: ...Analox 50 Carbon Dioxide Analyser User Manual Document Ref A50 811 19 September 2014 Page 6 Ax 50TM Accessories b h g e c i a...

Страница 8: ...fects of Carbon Dioxide 1 000ppm 0 1 5 000ppm 0 5 10 000ppm 1 15 000ppm 1 5 20 000ppm 2 30 000ppm 3 40 000 50 000ppm 4 5 50 000 100 000ppm 5 10 100 000 1 000 000ppm 10 100 For a more detailed outline...

Страница 9: ...onnect a Hard Wired Remote Alarm Repeater 13 4 2 2 To connect a Quick Connect Remote Alarm Repeater 14 4 2 3 To connect a Strobe LED Remote Alarm Repeater 14 4 3 Alarm Relay Output Models 15 4 4 Relay...

Страница 10: ...Repeater is pre wired to the Ax 50TM sensor unit c If you need to disconnect the cable for ease of installation DISCONNECT FROM THE REMOTE ALARM REPEATER END d The system MUST NOT be switched on unti...

Страница 11: ...e The Remote Alarm Repeater mimics the status indicators on the main Ax 50TM It also provides a push button which operates in the same manner as the Mode switch on the Ax 50TM If you have more than on...

Страница 12: ...ower failure some examples are listed below Instrument Type Battery Back up Endurance Standard Ax 50TM with 1 Remote Alarm 14 Hours Ax 50TM including 4 20mA Output 1 Relay Output and 2 Remote Alarms 1...

Страница 13: ...l must be placed by the local disconnection point for the Ax 50TM stating REMOVE PLUG TO DISCONNECT Ax 50TM The Ax 50TM should be mounted onto a wall using the mounting lugs on the unit Rawl plugs and...

Страница 14: ...g the 4 screws in the front of the case and carefully pulling the case apart The connecting wires from the Ax 50TM pass through one of the cable glands on the Remote Alarm Repeater 3 Terminate the wir...

Страница 15: ...ter unit by removing the 4 screws in the front of the case and carefully pulling the case apart The connecting wires from the Ax 50TM pass through one of the cable glands on the Remote Alarm Repeater...

Страница 16: ...e Volt Free single pole Changeover and are rated 50VAC DC 1 Amps max External relays A pre wired junction box is supplied with the Ax 50TM main sensor unit There is no need to open the main sensor uni...

Страница 17: ...gland must be used Ensure that the gland is properly tightened Test that the cable is adequately gripped by the cable gland Ensure that the cable is suitable for purpose the load is within the limits...

Страница 18: ...a 4 to 20mA output A 2m cable is factory fitted to the instrument The 4 to 20mA output current is generated by the instrument The customer system should be connected to this cable as follows and as pe...

Страница 19: ...gas molecules not the percentage in the atmosphere therefore at altitudes above 900 metres 3000 feet alarms will operate below the factory calibration point Please refer to our website www analox net...

Страница 20: ...ioxide continues to rise above the third alarm level then the red third Alarm indicator will also begin to flash and the pace of the Horn will increase This condition will be repeated on any Remote Al...

Страница 21: ...procedure As long as the green light is flashing the instrument is working If there are no indicator lamps lit on the Ax 50TM check that power is connected and that the fuses are OK 1 If the OK indica...

Страница 22: ...l Display Optional 4 to 20mA Output or 0 1V Gas Concentration Output Max load 150 Alarms 2 3 x Carbon Dioxide Visual Indicators 1 x System Fault Indicator 1 x Status Indicator 1 x Optional Oxygen Visu...

Страница 23: ...e but in our discretion we may elect instead to provide to you which ever is the lesser of the cost of replacement or a refund of net purchase price paid as per our Invoice on initial purchase from us...

Страница 24: ...ument Ref A50 811 19 September 2014 Page 23 9 DISPOSAL According to WEEE regulation this electronic product can not be placed in household waste bins Please check local regulations for information on...

Страница 25: ...Alarm Repeater Battery Backup and Relay Terminal Junction Box all have ingress protection to IP65 low pressure water jets from all directions and totally protected from dust in accordance with EN 605...

Страница 26: ...Analox 50 Carbon Dioxide Analyser User Manual Document Ref A50 811 19 September 2014 Page 25 11 DECLARATION OF CONFORMITY...

Страница 27: ......

Отзывы: