Installation
9
Mio Modero Device Family
Wiring guidelines
The Mio Modero requires 12 VDC power to operate properly. The necessary power is supplied via the
AxLink cable. The maximum AxLink wiring distance is determined by power consumption, supplied
voltage, and the wire gauge used for the cable. The following table lists wire sizes and the maximum
lengths allowable based on the maximum power consumption rating of 170 mA.
The maximum wiring lengths for using AxLink power are based on a minimum of 13.5 volts available.
Connecting the Wiring
The following paragraphs describe wiring connections for using the AxLink and relay connectors.
AxLink Data and Power Connections
Connect the control system's AxLink connector to the AxLink connector on the rear panel of the Mio
Modero for data and 12 VDC power as shown in FIG. 6.
Wiring Guidelines at 170 mA
Wire
Size
Maximum Wiring
Length
18 AWG
690.42 feet (210.43 m)
20 AWG
436.80 feet (133.13 m)
22 AWG
272.33 feet (83.00 m)
24 AWG
171.66 feet (52.32 m)
If using power from AxLink, disconnect the wiring from the control system before
wiring the Mio Modero.
FIG. 6
AxLink straight-thru wiring
PWR +
AXP
AXM
GND -
PWR +
AXP
AXM
GND -
Mio Modero
Control System
Содержание Mio Modero Classic
Страница 1: ...Operation Reference Guide Control System Accessories Mio Modero Device Family Last Revised 09 05 2008...
Страница 4: ......
Страница 6: ...ii Mio Modero Device Family Table of Contents...
Страница 10: ...Overview 4 Mio Modero Device Family...
Страница 25: ...Mio Modero IR 19 Mio Modero Device Family FIG 16 Attaching the faceplate to the mounting frame...
Страница 26: ...Mio Modero IR 20 Mio Modero Device Family...
Страница 33: ...Programming The Mio Modero 27 Mio Modero Device Family...